8.2.7
Status messages during commissioning (SS…)
The following status messages are possible during commissioning (setup):
Status message
Meaning
SS000 OK
Auto setup routine has been carried out.
SS001 PC Phase 1
The plausibility check (PC) of the motor data is active.
SS002 PC Phase 2
The calculation of dependent parameters is active.
SS003 STO
The parameter identification demands enable on digital input
STOA and STOB.
SS004 Parameter identifica-
tion
The rated motor values are checked by the parameter identifica-
tion feature.
SS010 Setup already active
The setup routine via the operator panel is being carried out.
SS030 No Release
No enable signal. The parameter identification demands enable on
digital input STOA and STOB.
SS031 Error – see 259
Error during the auto set-up routine. Check the value of
Actual
error
259.
SS032 Warning Phase
Asymmetry
The parameter identification feature diagnosed an unbalance dur-
ing the measurements in the three motor phases.
SS099 Setup not carried out The setup is not carried out until now.
8.2.8
Warnings during commissioning (SA…)
Warning Messages
Code
Measures / Remedy
SA000 No warning message present. This message can be read out via an option-
al communication board.
SA001
The value of the parameter
Rated voltage
370 is out of the rated voltage
range of the frequency inverter. The maximum reference voltage is indi-
cated on the nameplate of the frequency inverter.
SA002
For a three-phase motor, the calculated efficiency is in the limit range.
Check the values entered for the parameters
Rated voltage
370,
Rated
current
371 and
Rated power
376.
SA003 The value entered for parameter
Rated cos phi
374 is outside of the nor-
mal range (0.6 to 0.95). Check the value.
SA004
For three-phase motor, the calculated slip is in the limit range.
Check the values entered for parameters
Rated speed
372 and
Rated fre-
quency
375.
SA011 Current Controller non typical value; refer to
SA012 Current Controller non typical value with 2 kHz; refer to chapter
SA014 Current Controller non typical value with 4 kHz; refer to chapter
SA018 Current Controller non typical value with 8 kHz; refer to chapter
SA021 The stator resistance is very high. The following causes are possible:
−
The motor cable cross-section is not sufficient.
−
The motor cable is too long.
−
The motor cable is not connected correctly.
−
The contacts are not in a proper condition (corrosion).
SA022 The rotor resistance is very high. The following causes are possible:
−
The motor cable cross-section is not sufficient.
−
The motor cable is too long.
−
The motor cable is not connected correctly.
−
The contacts are not in a proper condition (corrosion).
SA031 Shorten Motor Line using Switching frequency 16 kHz.
SA032 Shorten Motor Line using Switching frequency 12 kHz and higher.
SA033 Shorten Motor Line using Switching frequency 8 kHz and higher.
SA041 The slip speed was not determined correctly. Check the values entered for
parameters
Rated speed
372 and
Rated frequency
375.
SA042 The slip speed was not determined correctly. Check the values entered for
parameters
Rated speed
372 and
Rated frequency
375.
108
Operating Instructions ACU
06/13