12.5
Device Profile Objects (0x6nnn)
12.5.1
0x6007/0 Abort Connection option code
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x6007
0
Abort Connection option code
Integer16
rw
No
1
Object
abort connection option code specifies the operational behaviour of the fre-
quency inverter if the bus connection fails due to BusOff, guarding, heartbeat, SYNC
error, RxPDO length error or NMT state change (leaving NMT state operational).
Depending on the setting of parameter
Local/Remote
412 the reaction of the setting
of Object 0x6007 changes like displayed in the next table.
Object 0x6007/0
Operation mode
Function with
“Control via Statemachine”
Function with
“Control via Con-
tacts”
0 - No reaction Operating point is maintained.
Operating point is
maintained.
1 -
Error
(factory
setting)
Device state machine changes to state “fault”
immediately.
Device state machine
changes to state
“fault” immediately.
2 - Switch-off
Device state machine processes command ‘
disa-
ble voltage’ and changes to state “switch on dis-
abled”
3 - Quick stop Device state machine processes command ‘quick
stop’ and changes to state “switch on disabled”
-1 -
(Minus 1)
Ramp stop +
Error
Device state machine processes command ‘
disa-
ble operation’ and changes to state “fault” after
the drive is stopped
-2 -
(Minus 2)
No reaction
Operating point is maintained.
NOTE
The object
abort connection option code corresponds to the inverter parameter
Bus
Error behaviour
388.
The settings of
Bus Error behaviour
388 = -2…3 are evaluated depending on pa-
rameter
Local/Remote
412.
07/13
CM-EtherCAT
69