ADDRESSABLE EIGHT-INPUT MODULE
S2000-AR8
User’s Manual
Страница 1: ...ADDRESSABLE EIGHT INPUT MODULE S2000 AR8 User s Manual ...
Страница 2: ...8 2 2 3 Mounting 8 2 2 4 Connecting the Module 9 2 2 5 Settings 9 2 3 Usage 10 2 3 1 Functional Testing 10 2 3 2 Extreme Situation Actions 10 2 3 3 Troubleshooting 11 3 Maintenance 11 3 1 General 11 3 2 Safety Precautions 11 3 3 Maintenance Procedures 11 3 4 Performance Testing 12 3 5 Technical Examination 12 3 6 Preservation Depreservation Represervation 12 4 Routine Repair 12 5 Storage 13 6 Tran...
Страница 3: ...al are allowed to operation activities All activities on mounting adjusting commissioning and testing shall be performed in compliance with the requirements of the regulatory documentation in force at the place of operation Abbreviations ADC Analog to Digital Conversion ISS Integrated Security System LED Light Emitting Diode MC Monitored Circuit PCB Printed Circuit Board PL Polling Loop ...
Страница 4: ... with dry contact outputs 1 1 2 Product application Standalone or centralized protection of buildings and facilities offices stores banks warehouses residential houses institutions enterprises against unauthorized intrusion and fire Monitoring of control and auxiliary systems 1 1 3 The functions of the module are Monitors conditions of the monitored circuits aka supervised circuits Monitors condit...
Страница 5: ...Relative humidity Up to 93 at 40 С 1 2 11 Weight kg 0 3 max 1 2 12 Overall dimensions mm 156 107 39 max 1 2 13 Non stop operation 24 7 1 2 14 MTBF in quiescent mode hours 80000 1 2 15 Survival probability 0 98758 1 2 16 Average service life years 10 1 2 17 The module passes the standards of industrial radio disturbance prescribed for Class B equipment as per GOST 30805 22 1 2 18 The module withsta...
Страница 6: ...ates and ADC values is represented in Table 3 4 1 1 4 2 A unique address for communicating data over the polling loop is assigned to each monitored circuit of the module Each address is stored in the non volatile memory of the module and allows sending messages about conditions at the relevant address point in response to a request of the polling loop controller 1 4 3 The module is powered via and...
Страница 7: ...ks 1 6 3 The fastening screw is factory sealed with paint 1 6 4 Tampering with the seal automatically voids all warranties 1 7 Packaging S2000 AR8 with accessories kit and operations manual are packaged into a separate cardboard box 2 Intended Use 2 1 Operating Restrictions The design of the module doesn t provide operating it in aggressive and dusty environments and in explosion hazardous premise...
Страница 8: ...f Works Fire and Intrusion Alarm Installations The module should be attached at a height suitable for operating and maintenance If the S2000 AR8 is housed in unwatched premises it should be at least 2 2 m higher than the floor level The module design provides installing it either on a flat surface using the woodscrews provided or onto a DIN rail It is acceptable to install the module within mounti...
Страница 9: ... Norm Fire Alarm Open Circuit and Short Circuit for the inputs with Input Type 2 Combined Fire For operating intrusion detectors Input Type is to be defined as 4 Intrusion 5 Intrusion and Tamper 6 Auxiliary 7 Lobby or 11 Panic and the detectors are connected as shown in Variant C The module enclosure open a Tamper Alarm message is generated for all the monitored circuits except for the one for whi...
Страница 10: ...munication with the module on the old addresses and restoring communication with it on the assigned addresses To assign the address to the module you also can use an S2000 APA standalone addressable device programmer 2 3 Usage To be admitted to work with the module the personnel are obliged to have studied this manual and to have a certificate of verification of knowledge of safety regulations S20...
Страница 11: ...t of the module and the detector Check integrity of the cable and connections 3 Maintenance 3 1 General Maintenance works for the module should be performed according to a scheduled preventive system which provides annual service 3 2 Safety Precautions The equipment should be maintained by personnel with Safety Qualification Level II or higher 3 3 Maintenance Procedures The scheduled maintenance w...
Страница 12: ...ontroller give a command to disable inputs used by the S2000 AR8 and then open the S2000 AR8 enclosure and close it again Ensure Tamper Alarm followed by Tamper Restored messages for the required addresses appear 3 4 6 Network controller s not receiving messages Intrusion Alarm or Fire Alarm means that the S2000 AR8 is defective and must be replaced 3 4 7 In addition the monitored circuit paramete...
Страница 13: ...e content of precious materials does not require accountability for storage retirement and disposal Clause 1 2 of GOST 2 608 78 7 3 The content of non ferrous metals does not require accountability for retirement and further disposal 8 Manufacturer Warranty 8 1 The manufacturer guaranties this product meets with technical requirements specified in the manuals if the user follows the instructions f...