BlueNova BN13V-240-3.2k HC Скачать руководство пользователя страница 1

 

 

 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

User Manual 

HC (High Current) 

Product Range 

 

 
 
 
 

 

 

Document Revision No. 

Ver. 1.0.1 

Revision Date 

2021-01-22 

Approved by 

J.P. Verster 

Содержание BN13V-240-3.2k HC

Страница 1: ...User Manual HC High Current Product Range Document Revision No Ver 1 0 1 Revision Date 2021 01 22 Approved by J P Verster...

Страница 2: ...of each enclosure are listed below Product Name Enclosures per battery Qty Dimensions L x W x H Weight total 1 BN13V 240 3 2k HC 1 51 x 21 x 31cm 38kg 2 BN13V 480 6 3k HC 1 80 x 21 x 31cm 75kg 3 BN26V...

Страница 3: ...ce 27 21 205 2000 Somerset West Business Park Technical Support support bluenova co za Somerset West 7130 Website www bluenova co za C ASSEMBLY INSTRUCTIONS Note Single enclosure batteries require no...

Страница 4: ...05 2000 Somerset West Business Park Technical Support support bluenova co za Somerset West 7130 Website www bluenova co za STEP 2 Connect enclosures with bus bars Connect the enclosures in serie B1 to...

Страница 5: ...rge batteries V low set 3 06 V 24 5 V Inverter must switch off the load If the battery is not connected to hardware that is serial communication compatible the following values highlighted in blue mus...

Страница 6: ...ll as BMMC firmware version 2 5 higher include MultiCap technology Batteries with MultiCap can be connected in parallel to each other to increase overall capacity regardless of the age difference and...

Страница 7: ...Press the CTRL button to scroll to the next page in sequence Page 1 Vbat 53 14V Ibat 0 000A SOC 99 99 Battery voltage actual Current positive value charge negative value discharge State of charge Page...

Страница 8: ...tage actual Cell 8 voltage actual Cell 9 voltage actual Page 3 4 Vc10 3 321V Vc11 3 321V Vc12 3 321V Cell 10 voltage actual Cell 11 voltage actual Cell 12 voltage actual Page 3 5 Vc13 3 322V Vc14 3 32...

Страница 9: ...prevent the open circuit voltage falling below 40V g Ensure that the stored battery s state of charge is always above 50 100 SOC is optimal F TROUBLESHOOTING All BlueNova products contain integrated c...

Страница 10: ...VprechFAIL 1 Check fuse s terminal connections 2 Switch battery off disconnect from inverter charger 3 Switch battery on again Reconnect to inverter charger Error 12 State Err Fuse Error 1 Check fuse...

Страница 11: ...rged by checking that the value for Ibat on the display is positive Once the battery s contactor can be heard closing the CTRL button can be let go G EMERGENCY FIRST AID 1 In case of fire a Evacuate d...

Страница 12: ...User Manual High Current Product Range 2 Erica Way Office 27 21 205 2000 Somerset West Business Park Technical Support support bluenova co za Somerset West 7130 Website www bluenova co za H NOTES...