507768-02B
Page 19 of 56
Issue 1904
Table 5.
BG961UHE Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number of
90° Elbows
Used
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
1
76
61
39
19
110
95
63
38
132
132
113
113
2
71
56
34
14
105
90
58
33
127
127
108
108
3
66
51
29
9
100
85
53
28
122
122
103
103
4
61
46
24
n/a
95
80
48
23
117
117
98
98
5
56
41
19
90
75
43
18
112
112
93
93
6
51
36
14
85
70
38
13
107
107
88
88
7
46
31
9
80
65
33
8
102
102
83
83
8
41
26
n/a
75
60
28
n/a
97
97
78
78
9
36
21
70
55
23
92
92
73
73
10
31
16
65
50
18
87
87
68
68
Standard Termination at Elevation 4,501 - 10,000 ft
Number of
90° Elbows
Used
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
1
76
61
39
n/a
110
95
63
38
132
132
113
113
2
71
56
34
105
90
58
33
127
127
108
108
3
66
51
29
100
85
53
28
122
122
103
103
4
61
46
24
95
80
48
23
117
117
98
98
5
56
41
19
90
75
43
18
112
112
93
93
6
51
36
14
85
70
38
13
107
107
88
88
7
46
31
9
80
65
33
8
102
102
83
83
8
41
26
n/a
75
60
28
n/a
97
97
78
78
9
36
21
70
55
23
92
92
73
73
10
31
16
65
50
18
87
87
68
68
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Table 5A.
Содержание BG961UHE
Страница 3: ...507768 02B Page 3 of 56 Issue 1904 Figure 1 Parts Arrangement ...
Страница 22: ...507768 02B Page 22 of 56 Issue 1904 Figure 25 Figure 26 ...
Страница 37: ...507768 02B Page 37 of 56 Issue 1904 Figure 59 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Страница 43: ...507768 02B Page 43 of 56 Issue 1904 Figure 67 Typical Wiring Diagram ...