BLUE NOVA RacPower 52V Series Скачать руководство пользователя страница 1

 

 

 

 
 

Product User Manual 

52V Series / Single unit models 

 
UDS House – Section 1 

 

 Office: 

          

  

+27 21 205 2000     

22 Gardner Williams Ave 

                

 Technical Support:     

  

[email protected]o.za

    

Paardevlei, 7130 

 Website: 

    

www.bluenova.co.za

 

 
 

A.

 

INTRODUCTION 

 

Congratulations on purchasing a high quality BlueNova® product. 
 
This document covers product assembly & installation, troubleshooting, safety & maintenance 
instructions, storage guidelines as well as emergency & first aid procedures.  
 
Please do not discard this document as it contains valuable information that might have to be 
referenced at a later stage. 
 
Should you have any queries, kindly contact BlueNova® Technical Support: 
 

 

 Office: +27 21 205 2000       

 E-mail

[email protected]

    

 

B.

 

COMPONENT DIAGRAM 

 

A BlueNova® single unit battery requires no assembly before installation: 

 

 

 

C.

 

INSTALLATION 

 

The following highlighted values have to be set on the inverter/charger. 

Note:

 Disable 

equalisation.

 

 

Parameter  Cell V 

Value 

12V Eq 

Comment 

high cut-off

 

4.00 V 

64.0 V 

16.0 V 

Over voltage. Battery will isolate automatically. 

high set

 

3.51 V 

56.2 V 

14.1 V 

100% SoC. Constant voltage set point. Charger must 
pause until V 

float

 is reached. 

bypass

 

3.50 V 

56.0 V 

14.0 V 

Internal set to battery for balancing. 

float

 

3.40 V 

54.4 V 

13.6 V 

Charger must reconnect when this voltage is reached. 

reconnect

 

3.00 V 

48.0 V 

12.0 V 

Mains or generator must reconnect to charge batteries. 

low set

 

2.90 V 

46.4 V 

11.6 V 

Inverter must switch off the load. 

low cut-off

 

2.80 V 

44.8 V 

11.2 V 

Under voltage. Battery will isolate automatically. 

Отзывы: