![BLUE NOVA RacPower 52V Series Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/blue-nova/racpower-52v-series/racpower-52v-series_product-user-manual_2775886001.webp)
Product User Manual
52V Series / Single unit models
UDS House – Section 1
Office:
+27 21 205 2000
22 Gardner Williams Ave
Technical Support:
Paardevlei, 7130
Website:
A.
INTRODUCTION
Congratulations on purchasing a high quality BlueNova® product.
This document covers product assembly & installation, troubleshooting, safety & maintenance
instructions, storage guidelines as well as emergency & first aid procedures.
Please do not discard this document as it contains valuable information that might have to be
referenced at a later stage.
Should you have any queries, kindly contact BlueNova® Technical Support:
Office: +27 21 205 2000
E-mail:
B.
COMPONENT DIAGRAM
A BlueNova® single unit battery requires no assembly before installation:
C.
INSTALLATION
The following highlighted values have to be set on the inverter/charger.
Note:
Disable
equalisation.
Parameter Cell V
Value
12V Eq
Comment
V
high cut-off
4.00 V
64.0 V
16.0 V
Over voltage. Battery will isolate automatically.
V
high set
3.51 V
56.2 V
14.1 V
100% SoC. Constant voltage set point. Charger must
pause until V
float
is reached.
V
bypass
3.50 V
56.0 V
14.0 V
Internal set to battery for balancing.
V
float
3.40 V
54.4 V
13.6 V
Charger must reconnect when this voltage is reached.
V
reconnect
3.00 V
48.0 V
12.0 V
Mains or generator must reconnect to charge batteries.
V
low set
2.90 V
46.4 V
11.6 V
Inverter must switch off the load.
V
low cut-off
2.80 V
44.8 V
11.2 V
Under voltage. Battery will isolate automatically.