Blue Box - 2
SIGMA UNIT VERSIONS
SIGMA 2002/HP: reverse cycle heat pump
The heat pump version operates as a water cooled chiller in summer and a water to water heat pump in winter
by reversing the refrigerant flow to suit the required operating mode.
In addition to the components of version SIGMA 2002, the heat pump version includes:
REFRIGERANT CIRCUIT: 4-way reversing valve and a second thermostatic expansion valve.
ELECTRICAL PANEL: Microprocessor programmed for summer/winter changeover (the Macroplus microprocessor
is used on 4 compressor HP units).
SIGMA 2002/LE: motocondensing unit
The unit is designed to operate with a remotely located refrigerant to air evaporator. It is supplied without a
refrigerant to water evaporator and thermostatic expansion valve. The solenoid valve on the liquid line is supplied
as standard. Models 3.2 to 13.2 have mchiller control and the remainder of the range is supplied without control.
The standard supply is ON/OFF for each compressor from a digital entry.
SIGMA 2002/LE/HP: motocondensing unit
The unit is designed to operate with a remotely located refrigerant to air evaporator. It is supplied without a
refrigerant to water evaporator and thermostatic expansion valve.
The solenoid valve on the liquid line and liquid receivers are supplied as standard. Models 3.2 to 13.2 have
m
CHILLER control and the remainder of the range is supplied without control. The standard supply is ON/OFF for
each compressor from a digital entry.
SIGMA 2002/LC: motoevaporating unit.
The unit is supplied without a water cooled condenser and is designed to be connected to a remotely located air
cooled condenser.
SIGMA 2002 / LC /HP: motoevaporating unit
The unit is supplied without a water cooled condenser and is designed to be connected to a remotely located air
cooled condenser.
The solenoid valve on the liquid line and the liquid receivers are supplied as standard.
ACCESSORY VERSIONS
SIGMA 2002 /DC: unit with heat recovery condenser.
Not available for HP versions.
In addition to the components of version SIGMA 2002 this unit includes a 100% heat recovery condenser, for the
production of hot water, and a liquid receiver on each refrigerant circuit.
SIGMA 2002 /DS: unit with desuperheaters
Available for all models. A brazed plate type heat recovery exchanger (desuperheater) is arranged in series with
the condenser. Also available on all HP models. In this case an isolating valve must be fitted on the water
recovery circuit and be closed during heat pump mode operation as described in the manual.
CONTROLS AND SAFETY DEVICES
- High pressure switch with manual reset.
- High pressure safety, with manual reset, controlled by the unit controller on four compressors models.
- Low pressure safety switch, with manual reset, controlled by the unit controller for four compressor models, low
pressure switch, with manual reset, controlled by the unit microprocessor for the two compressors models.
- High pressure relief valve
- Chilled water temperature sensor (at the evaporator inlet); on four compressors model it is installed on one
evaporator only.
- Freeze protection sensor at the outlet of each evaporator.
- Mechanical flow switch supplied as standard as kit with the unit.
- Compressor over-temperature protection
TESTING
The units are subjected to a dry run in the factory and supplied complete with oil and refrigerant.
Содержание SIGMA 2002
Страница 2: ......
Страница 99: ...Blue Box 93 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 3 2 13 2...
Страница 100: ...Blue Box 94 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 14 4 26 4...
Страница 101: ...Blue Box 95 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 3 2 8 2 14 4 16 4...
Страница 102: ...Blue Box 96 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 9 2 13 2 18 4 26 4...
Страница 103: ...Blue Box 97 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE SIGMA 2002 LE DC MODELS 3 2 26 4...
Страница 104: ...Blue Box 98 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE HP MODELS 3 2 26 4...
Страница 105: ...Blue Box 99 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 3 2 13 2...
Страница 106: ...Blue Box 100 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 14 4 26 4...
Страница 107: ...Blue Box 101 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 3 2 13 2...
Страница 108: ...Blue Box 102 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 14 4 26 4...
Страница 109: ...Blue Box 103 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 3 2 13 2...
Страница 110: ...Blue Box 104 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 14 4 26 4...
Страница 123: ......