Blue Box - 47
4.16.5 Circulating pump electrical connections
The external interlocks of unit must close for the unit to operate. The normally open external water circulating
pump contactor terminals must be wired in series with terminals 1 and 2, on the unit control panel, to ensure that
the chiller can only start after the pump is in operation.
Turn on the pump before the unit starts and stop it after the unit has
stopped (recommended time delay: 60 sec).
4.16.3 Potential free contacts
The following potential free contacts are available:
- 1 potential free contact for general alarm (terminals 100 - 101 - 102)
- 1 potential free contact for each compressor (option)
4.16.4 Flow switch electrical connections
Flow switch electrical connections (see paragraph 4.5 ) must be connected to terminal 1-14 for chiller units.
For heat pump units evaporator (user exchanger) flow switch must be connected to terminals 1-15 while condenser
(source exchanger) flow switch must be connected to terminals 14-15.
4.16.6 External interlock
If a remote ON-OFF is required connect the external interlock to terminals 1 and 2. If an external interlock is not
required, bridge therminals 1 and 2 to enable the unit to start.
4.16.2 Power supply to crankcase heaters
1) Close the main disconnect switch by turning it from position "0" to position "1"
2) Check that the word "OFF" is shown on the display
3) Ensure that the unit is in "OFF" status and that the external enabling contact is open
4) After a few moments, if the phase sequence is incorrect the alarm "INCORRECT PHASE SEQUENCE" will be
displayed (4-compressor models from 14.4 to 26.4 only, with pCO
2
controller). In this case invert the connections
of two of the power line phase wires.
5) Leave the unit in this condition for at least 12 hours to allow the crankcase heaters to perform their function
4.17 MICROPROCESSOR CONTROLLERS
Chillers in the SIGMA 2002 series with 2 scroll compressors, models from 3.2 to 13.2, are equipped with the
m
CHILLER type microprocessor controller.
Chillers in the SIGMA 2002 series with 4 scroll compressors, models from 14.4 to 26.4, are equipped with the
pCO
2
microprocessor controller.
Содержание SIGMA 2002
Страница 2: ......
Страница 99: ...Blue Box 93 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 3 2 13 2...
Страница 100: ...Blue Box 94 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 14 4 26 4...
Страница 101: ...Blue Box 95 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 3 2 8 2 14 4 16 4...
Страница 102: ...Blue Box 96 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 9 2 13 2 18 4 26 4...
Страница 103: ...Blue Box 97 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE SIGMA 2002 LE DC MODELS 3 2 26 4...
Страница 104: ...Blue Box 98 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE HP MODELS 3 2 26 4...
Страница 105: ...Blue Box 99 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 3 2 13 2...
Страница 106: ...Blue Box 100 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 14 4 26 4...
Страница 107: ...Blue Box 101 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 3 2 13 2...
Страница 108: ...Blue Box 102 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 14 4 26 4...
Страница 109: ...Blue Box 103 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 3 2 13 2...
Страница 110: ...Blue Box 104 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 14 4 26 4...
Страница 123: ......