background image

USER MANUAL & INSTALLATION GUIDE

BLÜCHER

®

 Connected Roof

SIPHONIC

ROOF

GREEN 

ROOF

BLUE 

ROOF

GRAVITY 

ROOF

INTELLIGENT 

ROOF

BALCONY

& PARKING

REV. 03 / APRIL 2021

Содержание Connected Roof

Страница 1: ...USER MANUAL INSTALLATION GUIDE BL CHER Connected Roof C INTELLIGENT ROOF BALCONY PARKING REV 03 APRIL 2021...

Страница 2: ...14 7 1 1 Menu structure 14 7 1 2 Menu content 15 7 1 3 Display information 16 7 2 Info button 16 7 3 Relay 17 7 4 Measurement values 18 7 4 1 Water Level 18 7 4 2 Temperature 18 7 5 Diagnostics 18 7...

Страница 3: ...ays must be installed if you have more than 16 Monitors in the system You can set the system up in different ways to receive the information 1 The information can be read directly on the Gateway displ...

Страница 4: ...instructions 1 Optional accessories Item Description External antenna 868 MHz SMA connection w 3 m cable Must to be ordered separately item number 900 900 000 3 Safety instructions and regulations In...

Страница 5: ...ecification 4 1 Product overview GATEWAY 1 Antenna 2 Info button 3 SD card 4 Input for power supply 5 Relay output 6 Internal power supply 7 Modbus 8 Jumper switch MONITOR 9 Mounting bracket 10 Level...

Страница 6: ...icroSDHC Class 4 or higher Size 4 GB Relay Type 1RT NO NC Load limit 230VAC 5A Connection 3 pin screw terminals Max 1 5mm MODBUS Physical Layer RS485 Baud rate Up to 115200 Bauds Connection 3 pin scre...

Страница 7: ...recommend that the Gateway is placed centrally in relation to the Monitors and in line of sight to ensure the best possible signal strength Please note that obstructions such as concrete and metal can...

Страница 8: ...mm and screws are not included Ensure there is enough free space around the unit to enable access to the SD card and to allow space for the antenna and cable glands If there is no room for the gatewa...

Страница 9: ...Relay Relay can be wired as NO or NC Internal power As an alternative to the power connector on the right side of the Gateway a 5V DC power supply can be wired directly to the power terminals Modbus...

Страница 10: ...ommend that one Monitor is installed next to each drain on your roof Monitors should be installed at the primary drainage system and not at emergency outlets and drains This gives the system the best...

Страница 11: ...water levels on the Monitor in the config file see chapter 7 5 Before installing the Monitor ensure that the surrounding roof area and the bracket are cleaned carefully before application of the recom...

Страница 12: ...r Test mode to reduce time see capture 7 6 7 Verify that there are no errors or warnings in the display 8 Verify Modbus values and functionality As an alternative to power OFF ON the Remove SD card mo...

Страница 13: ...the Monitor Label One Gateway supports up to 16 Monitors Omit all zeros 0 in front of monitor ID See label and configuration file examples below General Settings Optional Gateway system settings No c...

Страница 14: ...ded into 3 sections start up waiting for data and operation During start up the Gateway software version can be read Every time the Gateway has been re booted it will wait up to 30 minutes until the f...

Страница 15: ...REV 02 MARCH 2021 BL CHER CONNECTED ROOF 15 7 1 2 Menu content...

Страница 16: ...years 100 10 years Signal strength No messages received from the Monitor for 40 hours Signal unstable and can cause intermittent operation Low signal consider distance or any obstructions distrurbing...

Страница 17: ...ocked sensor Low battery Lost connection Internal leak Temp One setpoint For application where only one setpoint is needed Temp Two setpoints For application where two setpoints are needed For more in...

Страница 18: ...ed more frequently 7 5 Diagnostics There are two types of diagnostics Roof diagnostics and Monitor systems diagnostics See detail in chapter 7 5 1 and 7 5 2 7 5 1 Roof diagnostics The Gateway incorpor...

Страница 19: ...ALARM_TEMPERATURE_LIMIT Roof alarms deactivated when temperature is 5 C on any Monitor This is to avoid false alarms due to ice and snow The roof alarms will reactivate when the temperature is 5 C on...

Страница 20: ...agnostics and system data are transmitted when measurement values change or at least every 30 minutes Out of the box the Monitor operates in OPERATION MODE ready to use and connect to a Gateway 7 6 2...

Страница 21: ...on resistor is connected OFF Internal termination resistor is disconnected NB Power off before changing the jumper switch position 9 Gateway software update To install the new software follow these st...

Страница 22: ...H 2021 10 Service and maintenance We recommend regular service and maintenance around the area of a drain with a Monitor Dirt and other obstructions can affect the performance of your drainage system...

Страница 23: ...Distance too far Wait up to 4 hours Check signal strength Move the Gateway closer to the Monitor Add external antenna Add additional Gateway Permanent connection loss Wrong ID in config file Distance...

Страница 24: ...lace any defective Connected Roof Product in whole or in part according to BL CHER s General Terms and Conditions of Sale However the warranty does not cover device defects that result from abuse acci...

Страница 25: ...255 Factory setting 4 SAMPLE_PERIOD 1 to 255 Factory setting 1 BLOCKED_SENSOR_LIMIT_FACTOR 1 to 255 Factory setting 20 BLOCKED_SENSOR_ALARM_SET_COUNTER 1 to 255 Factory setting 5 BLOCKED_SENSOR_NOALAR...

Страница 26: ...16 decimal place 2 0 100 00 00131 humidity max 32 uint16 decimal place 2 0 100 00 00132 battery level 33 uint16 decimal place 2 0 100 00 00133 communication signal level 34 uint16 decimal place 2 0 10...

Страница 27: ...ctet 12431 8 15 hex 2nd octet 12431 0 7 hex 3rd octet 12432 8 15 hex 4th octet 12432 0 7 1 HW version2 1 uint8 A 0 256 12501 8 15 uint8 B 0 256 12501 0 7 16 HW version2 16 uint8 A 0 256 12516 8 15 uin...

Страница 28: ...sensor alarm Monitor 11 bool 12952 10 Blocked sensor alarm Monitor 12 bool 12952 11 Blocked sensor alarm Monitor 13 bool 12952 12 Blocked sensor alarm Monitor 14 bool 12952 13 Blocked sensor alarm Mo...

Страница 29: ...14616 0 7 1 diagnostic battery voltage min 1 uint8 x20 and decimal place 3 0 4 000 V 14701 0 7 16 diagnostic battery voltage min 16 uint8 x20 and decimal place 3 0 4 000 V 14716 0 7 1 diagnostic error...

Страница 30: ...umber of configured sensors 05 uint8 0 99 00005 0 7 gateway tag 06 string of 32 ASCII characters 1st character 00006 8 15 2nd character 00006 0 7 31st character 00021 8 15 32nd character 00021 0 7 rel...

Страница 31: ...REV 02 MARCH 2021 BL CHER CONNECTED ROOF 31...

Страница 32: ...ALCONY PARKING 2020 blucher com T 45 99 92 08 00 blucher com BL CHER 04 MAINTENANCE 0 5 S U S T A I N A B I L I T Y 0 1 S P ECIFICATION 02 INSTALL A T I O N 0 3 U S E O P E R A T I O N 100 recyclable...

Отзывы: