Manual V1.1 

EB-IO-LINK 

 

 

BLOCK Transformatoren-Elektronik GmbH 

 

 

Max-Planck-Straße 36-46 27283 

Verden, Germany 

17-06-20 / Schl 
Subject to technical changes 

 

EB-IO-LINK 

 

Communication Module Between PLC/PC  

And  

EasyB - Single Channel Circuit Breaker System 

 

 

 
 

 
 

Содержание EB-IO-LINK

Страница 1: ...K BLOCK Transformatoren Elektronik GmbH Max Planck Straße 36 46 27283 Verden Germany 17 06 20 Schl Subject to technical changes EB IO LINK Communication Module Between PLC PC And EasyB Single Channel Circuit Breaker System ...

Страница 2: ...5 2 3 Dimensions 6 2 4 Assembly 6 2 5 Connections and Signaling 7 3 Initialization 8 3 1 Operating statuses 8 3 2 Communication 9 4 Process Data and Parameters 10 4 1 Process Data 10 4 2 Acyclic I O Data of the Communication Module 12 4 3 Acyclic I O Data of the Network 13 4 3 1 Coding of the Circuit Breaker Currents 14 4 3 2 Coding of the Circuit Breaker Status 14 4 3 3 Coding of the Circuit Brea...

Страница 3: ... respective task in particular the safety instructions and warnings contained therein Qualified personnel can as a result of their training and experience help to ensure that the use of the described product meets all safety requirements as well as applicable regulations provisions standards and laws 1 3 Intended Use This device is designed for installation within an enclosure and is suitable for ...

Страница 4: ...INK communication module serves as an interface for connection to a higher level controller and is compatible with circuit breakers of the variants EB 08 EB 18 and EB 38 The communication module supports IO Link standard V1 1 and works with the COM 3 speed of 230 4 kB The cyclic data exchange is 2 0 ms and contains 6 bytes of process data To ensure error free operation the maximum number of 40 cir...

Страница 5: ...al changes Page 5 2 2 System Design Illustration 1 Establishing a Network with EB GND4 8 Modules used in the system structure X1 EB IO LINK F1 EB 0824 100 0 F2 EB 0824 100 0 F3 EB 0824 100 0 F3 1 EB PMM GND4 EB GND4 GND8 EB GND8 Note Deviations in the wiring can destroy the modules The IO LINK cable must not exceed a maximum length of 20m ...

Страница 6: ...O LINK BLOCK Transformatoren Elektronik GmbH Max Planck Straße 36 46 27283 Verden Germany 17 06 20 Schl Subject to technical changes Page 6 2 3 Dimensions Illustration 2 Dimensions 2 4 Assembly Illustration 3 Assembly ...

Страница 7: ...Schl Subject to technical changes Page 7 2 5 Connections and Signaling Illustration 4 Overview of Connections and Signaling 1 Mounting EB BAR cross connector 2 Power terminal up to a max of 40A 3 C Q Communication 4 RE reset input 5 Unlocking latch 6 L Communication 7 L Communication 8 LED Indicator 9 Labeling field ...

Страница 8: ... 40 circuit breaker channels can be addressed and managed To simplify initialization and configuration the associated IODD can be downloaded from the following via the following link Note When applying the supply voltage to IN it is imperative that a separate GND line is connected to one of the circuit breaker channels Initialization without a series of circuit breaker modules can lead to faulty b...

Страница 9: ...INK communication module communicates according to the V1 1 IO LINK standard and is backwards compatible with the V1 0 1 IO LINK standard For communication with the communication module and the connected network a version V1 1 or V1 0 IO Link Master is required The communication module operates in COM 3 mode 230 4 kB and exchanges 6 bytes of process data with the Master per cycle 2 ms ...

Страница 10: ...Process Data Collective Message Byte 1 Byte 1 MSB LSB Description Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 00 Collective Message Channel Tripped Switched Off 0 0 0 0 0 0 0 1 01 Collective Message Current 90 Nominal 0 0 0 0 0 0 1 0 02 Group Reset 0 0 0 0 0 1 0 0 03 Internal Communication Failure 0 0 0 0 1 0 0 0 04 Reserved 0 0 0 1 0 0 0 0 05 Reserved 0 0 1 0 0 0 0 0 06 Reserved 0 1 0 0 0 0 0...

Страница 11: ...Tripped 0 0 0 0 1 0 0 0 28 eBreaker 21 Tripped 0 0 0 1 0 0 0 0 29 eBreaker 22 Tripped 0 0 1 0 0 0 0 0 30 eBreaker 23 Tripped 0 1 0 0 0 0 0 0 31 eBreaker 24 Tripped 1 0 0 0 0 0 0 0 Table 6 Process Data eBreaker Tripped Byte 5 Byte 5 MSB LSB Description Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 32 eBreaker 25 Tripped 0 0 0 0 0 0 0 1 33 eBreaker 26 Tripped 0 0 0 0 0 0 1 0 34 eBreaker 27 Tripped...

Страница 12: ...n V1 1 2 20 Product Text String RO IO Link Interface and System Specification V1 1 2 21 Product Serial Number String RO IO Link Interface and System Specification V1 1 2 22 Hardware Revision String RO IO Link Interface and System Specification V1 1 2 23 Firmware Revision String RO IO Link Interface and System Specification V1 1 2 24 Application Specific Tag String R W IO Link Interface and System ...

Страница 13: ...ent 74 eBreaker RC_Status 33 40 8 Bit RO Check bit for the setting of the current 80 eBreaker Command ON OFF RESET 8 Bit WO Switching on Switching off Resetting the individual circuit breakers 82 eBreaker Set Options to ALL 8 Bit WO Transfer the first circuit breaker options to all modules 83 eBreaker Reset Trip Counter 1 40 8 Bit WO Reset the trip counter Automatically 0 after restart 201 240 eBr...

Страница 14: ... Tripping current 6A 80 8 Tripping current 8A 100 10 Tripping current 10A 4 3 2 Coding of the Circuit Breaker Status Coding of the status Index 501 540 is shown in Table 11 Table 11 Coding of the Status Dec value Functions Comments 0 N C Not connected 1 Switched Off Switched off via interface 2 Switched On Switched on 3 Tripped Tripped 6 Current 90 Nominal Current 90 Nominal 14 Current 100 Nominal...

Страница 15: ...ailable as of the circuit breaker firmware version 1 12 RO and indicates whether automatic address assignment is switched on or off 4 3 4 Coding of the Circuit Breaker Types Coding of the types Index 901 940 is shown in Table 13 Table 13 Coding of Types Dec Value Name Type Tripping Currents 170 EB 3824 100 0 Circuit breakers Tripping currents can only be set via the interface 0 5 10A 138 EB 0824 1...

Страница 16: ...ON Channel 3 On 12 OFF Channel 3 Off 13 RESET Channel 3 Reset Note The addresses of the channels are formed using an offset of decimal 5 4 3 6 Coding for Reset of the Circuit breaker Trip Counter The coding of the reset function Index 83 for the trip counter is shown in Table 30 Table 15 Coding of the Reset Dec value Functions Comments 1 RESET Channel 1 Reset Trip Counter 2 RESET Channel 2 Reset T...