SEQUENCE OF OPERATION FOR BLAZE 400 D/G
With “Selector Switch” in “ON” position and selector switch in “STAT ON” position and remote
thermostat plugged into receptacle:
1: Remote Thermostat senses a drop in temperature and the ignition control module is energized.
2: The module performs a safe start check and the burner and spark generator start. Burner lights, ignition
stops, and flame current is sensed.
For oil: the Genisys primary control contacts close, the burner motor and ignitor are
energized after a 15 second delay. The primary control energizes the pump solenoid valve and flame is
established. The cad cell senses flame and the burner continues to fire.
3: Temperature controller thermocouple heats up to factory set point (90F) OR after Time Delay of 1
minute and circulating air blower starts.
4: When the remote thermostat senses space temperature at set point, the burner shuts down.
5: The circulating blower continues to operate until the air in the unit cools to the factory set point (80 ºF)
then turns off.
With selector switch in “BYPASS” position:
1: The module performs a safe start check and the burner and spark generator start.
2: Burner lights, ignition stops, and flame current is sensed.
3: Temperature controller thermocouple heats up to factory set point (90F) and circulating air blower starts.
4: When the selector switch is placed to the off position the burner shuts down.
5: The circulating blower continues to operate until the air in the unit cools to the factory set point (80F)
then turns off.
OPERATING INSTRUCTIONS FOR BLAZE 400 D/G
STARTING HEATER
1.)
ENSURE HEATER IS ON FLAT, LEVEL GROUND BEFORE STARTING, CANOPY AND FAN GUARDS
MUST BE CLOSED.
2.)
MAKE SURE “SELECTOR SWITCH” IS IN “OFF” POSITION.
3.)
WIRE IN SUPPLY CORD TO 120V SUPPLY WITH GROUND.
INSTALLATION
12/3 AWG UPTO 50FT
10/3 AWG BEYOND 50FT
4.)
TURN “SELECTOR SWITCH” TO “ON” POSITION.
5.)
FOR THERMOSTAT OPERATION FLIP SELECTOR SWITCH TO “STAT ON” POSITION. IF YOU ARE NOT
USING A THERMOSTAT FLIP SELECTOR SWITCH TO “BYPASS” POSITION.
Please Note: When using a generator for electrical supply, make sure the generator is properly grounded and
is running at a 60HZ frequency. In the event that a generator is being used and the generator runs out of fuel,
make sure the heater “SELECTOR SWITCH” is in the “OFF” position before restarting generator, failure to do
so may damage heater.
STOPPING HEATER
1.) Close main gas supply valve while heater is operating or if operating heater with oil skip to # 2.)
2.) Flip “SELECTOR SWITCH” to “OFF” position. The supply fan will continue to operate until the heat exchanger
has sufficiently cooled. Do not disconnect main power until supply fan has stopped running and “SELECTOR
SWITCH” is on “OFF” position.
3.) Disconnect heater from gas supply OR disconnect fuel oil lines.