TROUBLES AND TROUBLESHOOTING
TROUBLE
POSSIBLE REASONS
TROUBLESHOOTING
The fan does not get started.
No power supply.
Check the electric connections and the operation status of the
circuit breaker.
Motor jam.
Turn the fan off. Troubleshoot clogging of the impeller. Restart
the fan.
Automatic circuit breaker tripping
during the unit turning on.
Overcurrent as a result of short circuit in
the electric circuit leads to tripping of
the circuit breaker.
Disconnect the fan from power supply and contact the product
Seller. Do not turn the fan on again!
Low air flow.
Air ducts or other components of the
ventilation system are clogged. The
impeller is clogged. The air ducts are
damaged. The air dampers are closed.
Clean the air ducts, the impeller and other components of
the ventilation system. Make sure that the air ducts are not
damaged. Make sure that the air dampers and louvre shutters
are open.
STORAGE AND TRANSPORTATION REGULATIONS
• Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range
from +5 ˚C to +40 ˚C and relative humidity up to 70 %.
• Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing
deformation.
• Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
• Follow the handling requirements applicable for the particular type of cargo.
• The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and
mechanical damage. The unit must be transported only in the working position.
• Avoid sharp blows, scratches, or rough handling during loading and unloading.
• Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at
least 3-4 hours.
The fan maintenance includes regular cleaning of the surfaces of dust and dirt. Replace the filter as required, but at least every 6 months.
The impeller cleaning is shown below. Clean the impeller blades thoroughly every 6 months.
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE
OPERATIONS!
ENSURE THAT THE UNIT IS SWITCHED OFF FROM THE SUPPLY MAINS BEFORE
REMOVING THE GUARD.