RACKMOUNT REMOTE POWER MANAGER USER’S MANUAL
3.2 Connection to Switched Outlets
Connect the power cord from each switched device to a switched AC outlet on the
power manager. When power is applied to the power manager, the switched AC
outlets will be switched on. The power manager includes a power bus. The PS580A
bus supports a total of 15 amps; the PS581A bus supports a total of 10 amps.
3.3 COM/RS-232 Port Connection
The COM/RS-232 port is a male, DB9 connector, wired in a DTE configuration. In
the default state, the COM/RS-232 port is configured for 9600 bps, eight data bits,
one stop bit, and no parity. The COM/RS-232 port can be connected to either an
external modem or a local PC, but not to both items at the same time. Figure 3-1
shows the COM/RS-232 port interface.
Figure 3-1. COM/RS-232 port interface.
The Rackmount Remote Power Manager can be controlled via a TCP/IP network,
controlled by a local PC that communicates with the unit via cable, or controlled
via an external modem. To switch plugs or select parameters, commands are issued
to the power manager either via the network or via the COM/RS-232 port.
NOTE
It’s optional to connect both the network and console ports.
The COM/RS-232 port can be connected to either a local PC or an
external modem.
• Network port: Connect your 10BASE-T or 100BASE-T network interface to the
Rackmount Remote Power Manager’s network port. For more information,
refer to
Section 3.4
.