Logging In
Logging in through HTML requires directing the HTML client to the configured IP address of the unit.
To log in by HTML:
1. In the login window, enter a valid username and password and press
OK
.
If you enter an invalid username or password, you will be prompted again.
You are given three attempts to enter a valid username and password combination. If all three fail, the
session ends and a protected page will be displayed.
Outlet Control
The Outlet Control section offers access to the Individual and Group outlet control pages. From the
Individual and Group pages, the user can review and manipulate power control functions for all outlets
and groups assigned to the current user. Both pages include the outlets absolute and descriptive names,
the Outlet Status reported to the Power View by the outlet, the current Control State being applied by the
Power View and the outlet load in amperes.
Available outlet and group power states may be set to on, off or reboot; the reboot operation turns the
outlet(s) off, delays for a period of 15 seconds and then turns the outlet(s) on.
Outlet State/Control State Field Values
Outlet State Control State
Description
On
On
Outlet is on
Off
Off
Outlet is off
Off
Pend On
Outlet is off and about to turn on in response to a sequence timer
Off
Reboot
Outlet is off and a Reboot action has been initiated
On
Idle On
A restart has occurred – Last Control State has been maintained
Off
Idle Off
A restart has occurred – Last Control State has been maintained
On
Wake On
A power-loss has occurred – Wakeup State has been applied
Off
Wake Off
A power-loss has occurred – Wakeup State has been applied
On/Wait
Off
Outlet state in transition – Requery of outlet status required
Off/Wait
On
Outlet state in transition – Requery of outlet status required
On/Error
varies
Error State – Outlet should be off but current is sensed at the outlet
Off/Error
varies
Error State – Outlet should be on but no current is sensed at the outlet
No Comm
varies
Communication to the outlet has been lost*
* Control State will be applied when communication is re-established
Individual
The Individual outlet control page displays all outlets assigned to the current user. The user may apply
on, off or reboot actions to individual, multiple or all accessible outlets.
To apply actions to individual or multiple outlets:
In the Individual Outlet Control section, select the desired action from the Control Action drop-down
menu for each individual outlet to be changed and press
Apply
.
To apply an action to all outlets:
In the Global Control section, select the desired action from the Control Action drop-down menu and press
Apply
.
Group
The Group outlet control page displays all groups assigned to the current user as well as the outlets for
each group.
To select a group:
Select the group name from the drop-down menu and press
Select
. The page will refresh to display all
outlets associated to the selected group name.
To apply an action to a group:
Select the desired action from the drop-down menu and press
Apply
.
Power View Enhanced PDU
Operations
•
11
Installation and Operations Manual