Make patching transitions from horizontal cable  

to typical stranded cable.

Meet Category 6 component performance requirements.

GigaTrue

®

 CAT6 Component Level Patch Panels

Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500)

FREE technical support 24 hours a day, 7 days a week: Call 877-877-2269 or fax 724-746-0746

Mailing address: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018

Web site: www.blackbox.com   •   E-mail: [email protected]

Customer 

Support 

Information

JPM610A-R8 

JPM612A-R8 

JPM614A-R8

Содержание GigaTrue CAT6 JPM610A-R8

Страница 1: ... Panels Order toll free in the U S Call 877 877 BBOX outside U S call 724 746 5500 FREE technical support 24 hours a day 7 days a week Call 877 877 2269 or fax 724 746 0746 Mailing address Black Box Corporation 1000 Park Drive Lawrence PA 15055 1018 Web site www blackbox com E mail info blackbox com Customer Support Information JPM610A R8 JPM612A R8 JPM614A R8 ...

Страница 2: ...ry 6 component level performance requirements and universal wiring enables each cable to be terminated to either T568A or T568B wiring schemes In addition this patch panel supports an optional rear cable management bar to assist and organize your final bulk cable termination Simply follow the color coded guides on the panel they identify the sequence of cable pair terminations After ordering a Gig...

Страница 3: ...e careful not to damage the twisted wire 3 Next punch down the cable Place each wire pair next to the appropriate wiring color label Refer to Figures 1 and 2 for T568A and T568B color codes Figure 1 Color codes for T568A T568B wiring on the wiring label NOTE For best performance keep the untwisted part of the wire less than 0 5 inches 1 3 cm long Using a punchdown tool terminate each wire Push the...

Страница 4: ...ce the stuffer caps on the terminated 110 blocks for added strain relief 5 Optional If you choose to use the cable management bar assemble the support bar as shown in Figure 3 There are two screws supplied for each cable management bar supplied Use one screw at each end to assemble the support bar Figure 3 Assemble the support bar ...

Страница 5: ... the bar to the plastic covers on the panel See Figure 4 Figure 4 Remove the top screws After the cable management bar in attached in place re install the two screws to firmly secure the cable management bar to the panel Repeat for all other support bars you wish to install 6 Secure the horizontal cable to the cable management bar Loosen the single screw and attach the horizontal cable under the c...

Страница 6: ...Page 6 NOTES 877 877 2269 blackbox com ...

Страница 7: ...Page 7 NOTES 877 877 2269 blackbox com ...

Страница 8: ...ge protection products to media converters and Ethernet switches all supported by free live 24 7 Tech support available in 60 seconds or less Copyright 2018 Black Box Corporation All rights reserved Black Box the Double Diamond logo and GigaTrue are registered trademarks of BB Technologies Inc Any third party trademarks appearing in this manual are acknowledged to be the property of their respecti...