  1. Locate the most visible location to install control panel.

  2.  Securely (not permanently) mount control panel to wall.

  3.  Assemble gauge (do not install to tank).

  4.  Loosen thumbscrews on sensor.

  5. Slide sensor to desired depth (high or low).

  6.  Connect an ohmmeter to sensor leads.

  7.  Slowly move float arm up and down to confirm circuit is closed at desired level.

  8.  Once proper setting is achieved, lock sensor in place using thumbscrews - tighten 

firmly, approximately 1 or 2 turns past hand tight, but do not overtighten.

  9.  Remove glass jar and linkage assembly from bung adaptor - do not disturb sensor 

setting.

10.  Use appropriate sealant on the male threads of bung adaptor.

11.  Screw bung adaptor into tank bung opening - tighten firmly, approximately 1 or 2 turns 

past hand tight, but do not overtighten.

12.  Install linkage assembly into bung adaptor. Float arm must travel freely and not contact 

any baffles or the sides of tank (use groove on top assembly as a guide).

13.  Reinstall glass jar - tighten firmly, approximately 1 or 2 turns past hand tight, do not 

overtighten.

14.  Solder (or wire nut) sensor leads then tape the connections.

15.  Seal hole with silicone or appropriate sealant.

16.  Connect wire to printed circuit board terminals marked "FLOAT".

17.  Install 9-volt battery.

18. Test control panel to confirm audible siren sounds.

DO NOT OVERTIGHTEN. DO NOT USE SIGHT GLASS AS A WRENCH.

TESTING / MAINTENANCE / INSPECTION

Jarhead

WARNING   

Never use with gasoline or highly flammable liquids.

Important safety instructions - save these instructions in a readily accessible location.

Husky Corporation • 2325 Husky Way • Pacific, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com 

Page 1                                                                            009313-6 7/2019

INSTALLATION INSTRUCTIONS

Daily

•  Confirm siren toggle switch is in the 

"ON" position.

•  Confirm audible siren sounds.

Monthly

•  Remove sensor from tank and 

manually raise / lower float to verify 

system goes into alarm mode.

•  Confirm all wires are properly 

connected to control panel and 

sensor(s).

Biannually

•  Replace 9-volt battery.

Replace 9-volt battery if tank alarm 

occurs.

•  Follow all city, state, or federal wiring 

code requirements as appropriate.

•  Apply city, state, or federal testing 

regulations as appropriate.

ANY TEST / INSPECTION FAILURE 

REQUIRES IMMEDIATE EQUIPMENT 

REPLACEMENT OR REMOVAL FROM 

SERVICE.

MADE IN THE USA

Sentry Wall Mount Tank Monitor with 

Jarhead Tank Gauge

Recommended Installation, Maintenance 

and Inspection Instructions

007685

007686

008646

008664

008677

009969