ST-150-2
7
Monitored
function
Com-
pressor
Measuring sensor
Discharge
gas tem-
perature
HS./OS.
Discharge gas temperature
sensor (R2)
Oil temper-
ature
CSW105
Oil temperature sensor (R2)
Oil supply
HS./OS.
Opto-electronic oil monitor-
ing (F7)
Minimum
oil level
CSW105
Opto-electronic oil monitor-
ing (F8)
Motor tem-
perature
HS./
CSW105
PTC sensor in motor wind-
ings (R3..8)
Rotation
direction
HS./
CSW105
Instrument leads on the
bolts of the motor power
supply
Unloaded
start
All
Slider position indicator
The compressor module compares the measured val-
ues with programmed data, sending signals via Mod-
bus and indicating the operating condition by means of
differently coloured LEDs. The compressor will be shut
down in case of operation beyond the application limits,
lack of oil, excessive motor temperature, wrong rotation
direction or critical motor start, see chapter Protective
functions, page 13.
5
Electrical connection
Keep the compressor module energized when the mo-
tor is not running. This ensures an unloaded start. With
CS. compressors, the module activates the oil heater, if
necessary, thus ensuring the lubricity of the oil even
after a long standstill period.
De-energize the module only if you plan a long stand-
still period of the compressor or for maintenance pur-
poses.
5.1
Schematic wiring diagram for CSW105
Abbr. Component
B2
Superior controller
B5
Slider position indicator (SPI)
B6
High pressure transmitter
B7
Low pressure transmitter
F1
Main fuse
F2
Compressor fuse
F3
Control circuit fuse
F5
High pressure switch
Abbr. Component
F8
Oil level switch (minimum oil level)
F13
Overload protective device
F15
Oil level switch (m
ax
imum oil level, option
of
the compressor)
F17
Control transformer fuse
F24
Phase monitoring fuse
H10
Light "collective fault"
K1
Main contactor (star-delta)
K2
Delta contactor (star-delta)
K3
Star contactor (star-delta)
K4
Auxiliary relay
M1
Compressor
Q1
Main switch
R1
Oil heater
R2
Oil temperature sensor
R3..8 Temperature sensor in the motor
R10
Optional temperature sensor
S1
Control switch (on/off)
S2
Reset of CM-SW-01
T1
Control transformer (example for 230 V, re-
quired according to EN60204-1)
Y1
Solenoid valve "capacity regulator CR+"
Y2
Solenoid valve "capacity regulator CR-"
Y6
Solenoid valve "ECO"
Y11
Solenoid valve "V
i
"
Y12
Solenoid valve "V
i
slider -"
Y13
Solenoid valve "oil return from the flooded
evaporator"
Tab. 1: Legend for CSW105 schematic wiring diagram with CM-
SW-01 and star-delta start
The CSW105 compressor has a connection for oil and
gas return as an option for systems with flooded evap-
orator. For connection position, see Operating Instruc-
tions SB-170, chapter Mounting, Connections and di-
mensional drawings, position 17. The electrical integra-
tion of this option is shown in the paths 24 to 26. The
switching times of the solenoid valve must be controlled
by the superior system controller and individually tested
for each system.