ST-150-2
4
!
!
NOTICE
The compressor module may be damaged or
fail!
Never apply any voltage to the terminals of CN7
to CN12 – not even for test purposes!
The voltage applied to the terminals of CN13
must not exceed 10 V!
The voltage applied to terminal 3 of CN14 must
not exceed 24 V! Do no apply voltage to the
other terminals!
Never apply voltage to the voltage outputs, not even for
testing.
3
Technical data
Compressor module
Operating voltage
115 .. 230 V +10%/-15%, 50/60 Hz, max. 600 VA
Required fuse (F3)
4 A time-lag at 230 V / 8 A time-lag at 115 V
Inputs, outputs and peripheral devices
Relay outputs for motor contact-
ors
Terminal strip CN2, terminals 1 and 2
Maximum continuous current 2.5 A
Switching voltage 240 V AC
Maximum switching current 2.5 A
Switching capacity 300 VA inductive (NC contact: D300, NO contact: C300)
Input for release signal
Terminal strip CN2, terminal 3
115 .. 230 V +10%/-15%, 50/60 Hz, max. 2,5 A
Signal output "collective
fault" (H10)
Terminal strip CN2, terminal 4
115 .. 230 V +10%/-15%, 50/60 Hz, max. 2,5 A (C300)
Connection for high pressure
switch (F5)
Terminal strip CN3
115 .. 230 V +10%/-15%, 50/60 Hz, max. 2,5 A
Terminal 1: Output, NO contact
Terminal 2: Input
HS. and OS. compressors
Voltage supply of the optional
solenoid valve in the oil return
line (Y9)
Terminal strip CN4
Output with overload protection, voltage output corresponds to the selected op-
erating voltage
Semiconductor switch, not potential free
Use a solenoid coil with maximum power consumption of 12 W at 230 V / 14 W
at 115 V.
CS.105
Oil heater (R1)
Terminal strip CN4
Output with overload protection, voltage output corresponds to the selected op-
erating voltage
Semiconductor switch, not potential free
Use an oil heater with maximum power consumption of 300 W at 230 V. The
output is only suitable for oil heater connection at 230 V supply voltage.
All screw compressors
Voltage supply of the solenoid
valves for capacity control and
V
i
slider
Terminal strip CN6
Output with overload protection, voltage output corresponds to the selected op-
erating voltage
Semiconductor switch, not potential free
All solenoid valves are included in the extent of delivery of the compressor.
Use only original spare parts!