ST-120-3

3

1

Introduction

Electronic protection devices monitor the principal oper-
ating parameters and protect the compressor and the
system against abnormal operating conditions. The
protection devices SE-E* monitor the motor and dis-
charge gas temperature, rotation direction and phase
failure.

In addition to these functions, the SE-i1 monitors also
the cycling rate and the oil supply (oil level and oil flow).

During operation, numerous operating data of the com-
pressor can be tracked and evaluated via the integ-
rated interface using the BEST Software, for example,
the position in the application limits diagram. The data
are recorded and allow a specific diagnosis and optim-
ization of the compressor and system operation. For
further details, see Technical Information CT-110.

The protection devices OFC and SE-B2 are intended
for integration in the switch cabinet. They are used to
monitor the oil supply.

Only the protection devices SE-E2 and SE-i

1

 are 

authorized for use with frequency inverters (FI).

This Technical Information provides an overview of all
BITZER protection devices for HS.-, CS.-, OS.- and
VSK screw compressors and a detailed description of
the following protection devices:

• SE-E1

• SE-E3

• SE-B2

• OFC

SE-B2 and OFC are used to monitor the oil circuit for
HS.- and OS.- screw compressors in connection with
the protection devices SE-E* (see chapter SE-B2, page
8 and see chapter OFC, page 8).

For the following protection devices, a separate Tech-
nical Information is available:

• SE-E2: Technical Information ST-122

• SE-i1: Technical Information CT-1

1

0

2

Safety

2.1

Authorized staff

All work done on the protection devices, compressors
and refrigeration systems may only be performed by
qualified and authorized staff who have been trained
and instructed accordingly. The local regulations and
guidelines will apply with respect to the qualification
and expertise of the specialists.

The protection devices have been built in accordance
with state-of-the-art methods and current regulations.
Particular importance was placed on user safety.

This Technical Information must be kept available near
the refrigeration system during the whole lifetime of the
protection device.

2.2

Residual risks

Compressors and electronic accessories may present
unavoidable residual risks. This is why any person
working on this device must carefully read this docu-
ment!

The following regulations shall apply:

• the relevant safety regulations and standards (e.g.

EN 378, EN 60204 and EN 60335),

• generally accepted safety rules,

• EU directives,

• national regulations.

2.3

Safety references

are instructions intended to prevent hazards. Safety ref-
erences must be stringently observed!

!

!

NOTICE
Instructions on preventing possible damage to
equipment.

CAUTION
Instructions on preventing a possible minor haz-
ard to persons.

WARNING
Instructions on preventing a possible severe
hazard to persons.

DANGER
Instructions on preventing an immediate risk of
severe hazard to persons.

Содержание OFC

Страница 1: ...2 Schutzger te f r Schraubenverdichter der HS CS OS und VSK Serie Originaldokument Deutsch 14 Dispositifs de protection pour des compresseurs vis des s ries HS CS OS et VSK Traduction du document orig...

Страница 2: ...nitoring functions SE B2 8 6 OFC 8 7 Electrical connection 9 7 1 Schematic wiring diagrams 9 7 1 1 CS series Connection of the protection devices SE E1 SE E3 10 7 1 2 HS 53 HS 74 Connection of the pro...

Страница 3: ...nd see chapter OFC page 8 For the following protection devices a separate Tech nical Information is available SE E2 Technical Information ST 122 SE i1 Technical Information CT 110 2 Safety 2 1 Authori...

Страница 4: ...to improper connection and or faulty operation Connect properly according to the schematic wiring diagrams and check the connections for tight seat The cables and terminals of the PTC control cir cui...

Страница 5: ...E i1 HS 53 HS 85 CS 65 CS 95 Tab 1 Overview of protection devices for screw compressors K1T Time relay for oil flow monitoring C1 Electrolytic capacitor Tab 2 Legend The protection device locks immedi...

Страница 6: ...ck acting Enclosure class ter minals IP00 IP00 IP00 IP20 IP00 IP00 Suitable for opera tion with frequency inverter 80 575 V 10 20 100 Hz AC 83 690 V 10 50 60 Hz AC UL homologation Yes is being pre par...

Страница 7: ...the motor due to improper connec tion and or faulty operation The terminals M1 M2 or T1 T2 on the com pressor and 1 2 on the protection device must not come into contact with the control voltage or op...

Страница 8: ...ontact 12 and indicates the fault To reset interrupt the voltage supply for at least 5 seconds Let the compressor cool down and reset it manually 6 OFC As an alternative to the SE B2 the OFC can also...

Страница 9: ...S 74 SH 500 OS 85 Legend for schematic wiring diagram C1 Electrolytic capacitor F7 Oil flow switch F9 Monitoring oil stop valve F10 Oil filter monitoring K1T Time relay Oil supply monitoring 20 s R1 O...

Страница 10: ...e connection of the protection devices SE E1 SE E3 Legend see chapter Schematic wiring diagrams page 9 7 1 2 HS 53 HS 74 Connection of the protection devices SE E1 SE E3 with SE B2 1 2 3 4 5 R2 F7 K1T...

Страница 11: ...box Bo te de raccordement Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 OFC 2 1 Fig 4 HS 53 HS 74 screw compressors...

Страница 12: ...t Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 F7 7 8 6 5 4 2 1 3 SE B2 N B1 14 11 12 L B2 SE B2 N B1 14 11 12 L B2...

Страница 13: ...t Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 F7 7 8 6 5 4 2 1 3 SE B2 N B1 14 11 12 L B2 SE B2 N B1 14 11 12 L B2...

Страница 14: ...tionen SE E1 und SE E3 19 5 SE B2 19 5 1 berwachungsfunktionen SE B2 19 6 OFC 20 7 Elektrischer Anschluss 20 7 1 Prinzipschaltbilder 20 7 1 1 CS Serie Anschluss der Schutzger te SE E1 SE E3 21 7 1 2 H...

Страница 15: ...20 F r folgende Schutzger te sind eigene Technische In formationen erh ltlich SE E2 Technische Information ST 122 SE i1 Technische Information CT 110 2 Sicherheit 2 1 Autorisiertes Fachpersonal S mtli...

Страница 16: ...rch fehlerhaften Anschluss und oder Fehlbedienung m glich Anschl sse gem Prinzipschaltbildern korrekt ausf hren und auf festen Sitz pr fen Kabel und Klemmen des PTC Messkreises d r fen nicht mit Steue...

Страница 17: ...und C1 OFC HS OS SE i1 HS 53 HS 85 CS 65 CS 95 Tab 1 bersicht Schutzger te f r Schraubenverdichter K1T Zeitrelais zur ldurchfluss berwachung C1 Elektrolytkondensator Tab 2 Legende Schutzger t verriege...

Страница 18: ...utzart Klemmen IP00 IP00 IP00 IP20 IP00 IP00 Geeignet f r Be trieb mit Frequen zumrichter Ja 80 575 V 10 20 100 Hz 83 690 V 10 50 60 Hz UL Freigabe Ja In Vorberei tung Tab 3 bersicht Technische Daten...

Страница 19: ...Motor Druckgas oder ltemperaturen ber schritten werden Die entsprechenden PTC Tempera turf hler m ssen elektrisch in Reihe angeschlossen werden Drehrichtungs berwachung SE E1 und SE E3 berwachen die...

Страница 20: ...gerungszeit 15 20 s beim Start 2 3 s im Betrieb ldurchfluss berwachung anschlie en OFC entsprechend Prinzipschaltbildern anschlie en siehe Kapitel Prinzipschaltbilder Seite 20 HINWEIS Ausfall des OFC...

Страница 21: ...k noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 Anschlusskasten Terminal box Bo te de raccordement Abb 2 CSH und CSW Schraubenverdichter Beispiel f r Anschluss der Schutzger te S...

Страница 22: ...l box Bo te de raccordement Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 OFC 2 1 Abb 4 HS 53 HS 74 Schraubenverdicht...

Страница 23: ...t Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 F7 7 8 6 5 4 2 1 3 SE B2 N B1 14 11 12 L B2 SE B2 N B1 14 11 12 L B2...

Страница 24: ...t Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 F7 7 8 6 5 4 2 1 3 SE B2 N B1 14 11 12 L B2 SE B2 N B1 14 11 12 L B2...

Страница 25: ...SE B2 31 5 1 Fonctions de contr le SE B2 31 6 OFC 31 7 Raccordement lectrique 32 7 1 Sch mas de principe 32 7 1 1 S rie CS Raccordement des dispositifs de protection SE E1 SE E3 32 7 1 2 HS 53 HS 74...

Страница 26: ...r chapitre SE B2 page 31 et voir chapitre OFC page 31 Des Informations Techniques s par es sont dispo nibles pour les dispositifs de protection suivants SE E2 Information Technique ST 122 SE i1 Inform...

Страница 27: ...e un mauvais raccordement et ou une erreur d utilisation Effectuer les raccordements correctement selon les sch mas de principe et v rifier le serrage Les c bles et bornes de la boucle de mesure CTP n...

Страница 28: ...5 Tab 1 Vue d ensemble des dispositifs de protection pour compresseurs vis K1T Relais temporis pour le contr le de d bit d huile C1 Condensateur lectrolytique Tab 2 Legende Le dispositif de protection...

Страница 29: ...am biante admissible 30 C 60 C 30 C 70 C 30 C 60 C 30 C 60 C 30 C 70 C 20 C 60 C Fusible requis 4 A instanta n 4 A instanta n 4 A instanta n 4 A instanta n 4 A instanta n 4 A instanta n Classe de pro...

Страница 30: ...incipe voir chapitre Sch mas de principe page 32 AVIS Risque de d faillance du dispositif de protection du compresseur et du moteur due un mauvais raccordement et ou une erreur d utilisation Les borne...

Страница 31: ...d verrouiller interrompre l alimentation en tension pendant au moins 5 secondes Laisser refroidir le com presseur et le d verrouiller manuellement 6 OFC En guise d alternative au SE B2 l OFC peut gal...

Страница 32: ...la temp rature d huile C bl demeure Raccord sur le site Compresseurs vis ouverts Les dispositifs de protection pour OS 53 OS 85 doivent tre contr l s de la m me mani re que ceux pour le compresseur h...

Страница 33: ...dans la bo te de raccordement et du SE B2 dans l ar moire lectrique L gende voir chapitre Sch mas de principe page 32 7 1 3 HS 53 HS 74 Raccordement des dispositifs de protection SE E1 SE E3 avec OFC...

Страница 34: ...nt Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 F7 7 8 6 5 4 2 1 3 SE B2 N B1 14 11 12 L B2 SE B2 N B1 14 11 12 L B2...

Страница 35: ...Schaltschrank Switch Armoire lectrique cabinet schwarz black noir braun brown marron blau blue bleu N 1 14 11 12 L 2 SE E1 SE E3 F7 7 8 6 5 4 2 1 3 SE B2 N B1 14 11 12 L B2 SE B2 N B1 14 11 12 L B2 9...

Страница 36: ...ingen Germany Tel 49 0 70 31 932 0 Fax 49 0 70 31 932 147 bitzer bitzer de www bitzer de Subject to change nderungen vorbehalten Toutes modifications r serv es 80311104 04 2016 80311104 04 2016 Subjec...

Отзывы: