7.2
CSW105: monitored functions
Monitored functions
Time delay
after com-
pressor start
Warning
Critical alarm
Fault
Low pressure
---
---
---
< NV
CM-SW-01 locks out immedi-
ately.
High pressure
---
---
---
> PS
CM-SW-01 locks out immedi-
ately.
Application limits
(Condensing temperature,
evaporation temperature)
120 s
< 2 K within the
application lim-
its
> 2 K outside
the application
limits
CM-SW-01
locks out after
30 s.
> 4 K outside the application lim-
its
CM-SW-01 switches off immedi-
ately.
Oil temperature
---
> 115°C
---
> 120°C
CM-SW-01 switches off immedi-
ately.
Minimum oil level
---
5 s
---
CM-SW-01 locks out after 90 s.
Motor temperature
---
---
---
CM-SW-01 locks out immedi-
ately.
Rotation direction
3 s
---
---
CM-SW-01 locks out immedi-
ately.
Phase failure
3 s
---
---
CM-SW-01 switches off immedi-
ately.
Operating recognition with
FI operation
7 s
---
---
CM-SW-01 locks out immedi-
ately.
Tab. 3: State of delivery of CM-SW-01 with CSW105
7.3
OS.95: monitored functions
Monitored functions
Time delay
after com-
pressor start
Warning
Critical alarm
Fault
Low pressure
---
---
---
< NV
CM-SW-01 locks out immedi-
ately.
High pressure
---
---
---
> PS
CM-SW-01 locks out immedi-
ately.
Application limits
(Condensing temperature,
evaporation temperature)
120 s
< 2 K within the
application lim-
its
> 2 K outside
the application
limits
CM-SW-01
locks out after
30 s.
> 4 K outside the application lim-
its
CM-SW-01 switches off immedi-
ately.