The Control Word is the active control word.
Use the Serial Control Word for configuration of the CM-RC-01.
5.4.1
Data valid bit
When the data valid bit is set to “1” setpoint and commands are accepted from the serial control
interface.
When the data valid bit is set to “0” all other bits in the control word and the setpoint are ignored.
This means that if the start command was active just before the data valid bit is set to “0” the
command remains active until the data valid bit is set to “1” and the start bit is set to “0”.
Please note that the Serial Control Source must be 1 (Modbus).
5.5
Examples of Serial Control Word setups:
Command
Hexadecimal
value
Decimal
value
Binary
Rese
rv
ed
D
ata
vali
d
Rese
rv
ed
Rese
t
Start
Rese
rv
ed
Operati
o
n
enab
le
Rese
rv
ed
No command
43F
1087
0000 0
1
00
0
0
11
1
111
Start
47F
1151
0000 0
1
00
0
1
11
1
111
Reset
4BF
1215
0000 0
1
00
1
0
11
1
111
Stop
437
1079
0000 0
1
00
0
0
11
0
111
‘No command’ is the neutral value allowing digital control.
The neutral value of the control word is 43F hex (= 1087 dec = 10000111111 binary)
To start the compressor, the control word must be 47F hex (= 1151 dec = 10001111111 binary)
To disable this interface: Please see section 10.3.7 Configuration
In the status word the actual status of the CM-RC-01 can be seen.
5.6
Status Word bit definitions
CM-RC-01 Status Word
Bit
Function
Description
0
Control
ready
The control is ready to switch on
0: Control not operational
1: The control is ready for operation
1
Operation
ready
The CM-RC-01 is ready to operate
0: Output is not ready
1: Output is ready
2
Operation
enabled
0: Output is off. Compressor is stopped
1: Compressor is on
3
Fault
0: No fault present
1: A fault is present. The compressor is stopped
4
Reserved
5
Reserved
6
Start disabled 0: Start is enabled.