background image

 

 

 

 

M870D  

 

 

 

 

 

Remote Display Manual 

 

 

 

 

 

 

 

 

 
October 28, 2013 
ML0027

 

Document Revision E

 

© 2013 by Bitronics, LLC 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание M870D

Страница 1: ...M870D Remote Display Manual October 28 2013 ML0027 Document Revision E 2013 by Bitronics LLC ...

Страница 2: ... 1 1 3 Environmental 1 1 4 Physical 2 1 5 Standards and Certifications 3 2 0 Installation 5 2 1 Initial Inspection 5 2 2 Instrument Mounting 5 2 3 Surge Protection 6 2 4 Overcurrent Protection 6 2 5 Supply Mains Disconnect 6 2 6 Power Supply Connections 7 2 7 Cleaning 7 3 0 SETUP 8 3 1 Communications Connections 8 3 2 Setup Mode 10 3 3 Measurement Screens 11 3 4 Operation 13 3 4 1 Overview 13 3 4 ...

Страница 3: ...d bootup text to AREVA 3 05 04 v1 08 0 M570D release power up sequence 10 07 05 Bootloader Description Date v1 00 0 Initial Release 4 23 02 v1 01 0 Update 7 25 02 70 SERIES MANUAL SET ML0021 M87X User Manual ML0022 70 Series UCA Object Model ML0024 M87X Modbus Plus Module Protocol ML0025 70 Series Modbus Protocol ML0026 70 Series DNP3 Protocol ML0027 M870D Remote Display Manual ML0032 M57X User Ma...

Страница 4: ...ct by personnel or enclosed in a suitable enclosure WARRANTY AND ASSISTANCE This product is warranted against defects in materials and workmanship for a period of one hundred and twenty 120 months from the date of their original shipment from the factory Products repaired at the factory are likewise warranted for eighteen 18 months from the date the repaired product is shipped or for the remainder...

Страница 5: ...Bethlehem PA 18017 VentureCom Inc Five Cambridge Center Cambridge MA 02142 SISCO Inc 6605 192 Mile Road Sterling Heights MI 48314 1408 General Software Inc Box 2571 Redmond WA 98073 Schneider Automation Inc One High Street North Andover MA 01845 Triangle MicroWorks Inc 2213 Middlefield Court Raleigh NC 27615 Greenleaf Software Inc Brandywine Place Suite 100 710 East Park Blvd Plano TX 75074 TRADEM...

Страница 6: ...istered trademarks of Systems Integration Specialists Company Inc SISCO SISCO MMS EASE Lite AX S4MMS The following are trademarks or registered trademarks of General Software Inc General Software the GS logo EMBEDDED BIOS Embedded DOS The following are trademarks or registered trademarks of the PCI Industrial Computer Manufacturers Group CompactPCI PICMG the CompactPCI logo the PICMG logo ...

Страница 7: ...he contents of the Safety Section Explanation of symbols and labels The meaning of symbols and labels that may be used on the equipment or in the product documentation is given below Installing Commissioning and Servicing Equipment connections Personnel undertaking installation commissioning or servicing work on this equipment should be aware of the correct working procedures to ensure safety The ...

Страница 8: ... energizing the equipment the following should be checked 1 Voltage rating and polarity 2 CT circuit rating and integrity of connections 3 Protective fuse rating 4 Integrity of ground earth connection where applicable 5 Equipment operating conditions The equipment should be operated within the specified electrical and environmental limits Current transformer circuits Do not open the secondary circ...

Страница 9: ... or to ground earth To avoid electric shock or energy hazards after completely isolating the supplies to the relay both poles of any dc supply the capacitors should be safely discharged via the external terminals before decommissioning 2 Disposal It is recommended that incineration and disposal to watercourses is avoided The product should be disposed of in a safe manner Any products containing ba...

Страница 10: ...character alphanumeric Standard 4 round mounting Configurable RS232 or RS485 communication PC based configuration tool for quick setup Front panel service port Front panel Demand and Energy reset if enabled 1 2 Specifications Display 3 lines of 5 digits Red LED 0 56 High 1 line by 8 character alphanumeric Red LED 0 11 High User Interface 4 pushbuttons Communication Selectable RS232 or RS485 4 wire...

Страница 11: ...ugs to maintain insulation requirements Standard 0 200 5 08mm header socket accepts other standard terminal types 6 pin removable terminal block for communications accepts 26 12AWG wire Standard 0 200 5 08mm header socket accepts other standard terminal types The recommended torque rating for the terminal block wire fasteners is 4 4 in lbs 0 5N m Standard 9 pin RS232 for service port Package 4 5 s...

Страница 12: ...AC Powerline Conducted Emissions EN 55011 2007 A2 2007 supersedes EN 55011 1998 A1 1999 Group 1 Class A Frequency 150 kHz 30 MHz Electrostatic Discharge ESD EN 61000 4 2 1995 A1 1998 A2 2001 Discharge voltage 8 KV Air 4 KV Contact Immunity to Radiated Electromagnetic Energy Radio Frequency EN 61000 4 3 2006 A1 2008 Class III supersedes EN 61000 4 3 2002 EN61000 4 3 2002 A1 2002 and ENV 50204 1996 ...

Страница 13: ...ducted Disturbances Induced by Radio Frequency Fields EN 61000 4 6 2007 supersedes EN 61000 4 6 1996 Level 3 Frequency 150 kHz 80 MHz Amplitude 10 V rms Modulation 80 AM 1 kHz AC Supply Voltage Dips and Short Interruptions EN 61000 4 11 2004 supersedes EN 61000 4 11 1994 ...

Страница 14: ...nstrument for shipping damage as it is unpacked Notify Bitronics LLC immediately if any damage has occurred and save any damaged shipping containers 2 2 Instrument Mounting The instrument may be mounted on a 19 Rack panel if desired Three units will fit side by side on a standard 5 25 high panel See Figure 2 for panel cutout dimensions The unit should be mounted using the four 10 32 studs attached...

Страница 15: ...Overcurrent Protection To maintain the safety features of this product a 2 Ampere time delay T fuse with a minimum interrupting rating of 1500 Amperes must be connected in series with the ungrounded non earthed hot side of the supply input prior to installation The fuse must carry a voltage rating appropriate for the power system on which it is to be used A UL Recognized fuse in an appropriate fus...

Страница 16: ...rear of the M870D There is one chassis ground point that MUST be connected to Earth Ground This is located on the mounting flange Connection of the chassis ground is required see Section 2 3 Bitronics recommends that all grounding be performed in accordance with ANSI IEEE C57 13 3 1983 2 7 Cleaning Cleaning the exterior of the instrument shall be limited to the wiping of the instrument using a sof...

Страница 17: ...ML0027 October 28 2013 Copyright 2013 Bitronics LLC 8 3 0 SETUP 3 1 Communications Connections ...

Страница 18: ...ML0027 October 28 2013 Copyright 2013 Bitronics LLC 9 M870D RS 232 Cable Connections to the M57x ...

Страница 19: ...on is used to go to the next configurable parameter When Exit appears in the alphanumeric display press the right arrow key to return to normal operation The instrument will automatically return to normal operation if no keys have been pressed in approximately 20 seconds This timeout prevents the instrument from inadvertently being left in setup mode The settings for Meter ID Baud and Mode must ma...

Страница 20: ...ll take effect 3 3 Measurement Screens Measurements that are shown on the M870D are setup using the Windows based 70 Series Configurator There are two folders in the Communication section which must be configured before the M870D can be used The first folder is used to setup the Port Assignments as shown in Figure 3 Set the protocol of the port to which the Remote Display is connected to Zmodem Di...

Страница 21: ...creens is limited to 64 Each screen can be assigned to a particular 70 Series IED serial port and remote display address The screen definitions are stored in the 70 Series IED and not in the Remote Display Demand and Energy values may be reset from the front panel if this option is selected in the configuration software If this option is chosen the displayed values will be reset when the right two...

Страница 22: ...ML0027 October 28 2013 Copyright 2013 Bitronics LLC 13 3 4 Operation 3 4 1 Overview ...

Страница 23: ...and Left Arrow keys Enter Firmware Upgrade Mode Combination Left and Right Arrow Keys Reset Displayed Value if enabled Table 2 Pushbutton Functions 3 4 3 Tx Rx LED The Tx Rx LED located on the front panel above the RS232 port lights whenever activity is detected on either of the instruments communications ports 3 5 RS232 Service Port The front panel port acts as an extension to the 70 Series IED s...

Страница 24: ...ror in the stored configuration parameters The default parameters have been restored Enter setup mode and check that all parameters are set properly If error persists contact the factory Remove Power Instrument configuration has been changed or new code has been downloaded Applies only to devices manufactured prior to July 2002 Remove power to the instrument for a few seconds and then reapply 5 0 ...

Страница 25: ...ML0027 October 28 2013 Copyright 2013 Bitronics LLC 16 ...

Страница 26: ...ML0027 October 28 2013 Copyright 2013 Bitronics LLC 17 ...

Страница 27: ...ML0027 October 28 2013 Copyright 2013 Bitronics LLC 18 ...

Страница 28: ...te Bitronics Name Logo E DeMicco B 05 01 09 Updated logos and cover page MarCom C 9 22 09 Updated Section 1 5 to reflect current standards updated Declaration of Conformity RAF EJD D 3 6 13 Updated Declaration of Conformity EJD E 10 28 13 Updated for 61010 1 Edition 3 Declaration of Conformity EJD ...

Страница 29: ......

Страница 30: ...Bitronics LLC 261 Brodhead Road Bethlehem PA 18017 610 997 5100 Fax 610 997 5450 www novatechweb com bitronics ...

Отзывы: