Change of parameter value is similar to item 3.3.1.
Parameter value limits:
operation time of fuel delivery screw, seconds:
1-99;
interval between fuel portions, seconds:
1-99.
To leave the fuel delivery setup window, move the cursor – frame to icon
«Back»,
, and press the encoder button, the Controller will go back to menu « PID
mode settings».
3.3.3 Fan Adjustment
To change maximum and minimum fan capacity it is required to go to the menu
«Fan Adjustment». By turning encoder select menu item «Fan Adjustment»,
, press
the encoder button – fan operation parameter setup window will open (Picture 12).
Picture 12 – Fan Adjustment Window
Change of parameter value is similar to item 3.3.1.
Parameter value limits:
minimum fan capacity,%:
1-98;
maximum fan capacity,%:
1-99.