M 01/2009
page 34/61
9.5
Repetition of a section or several sections within a program
The example of a set-point ramp temperature program of chap. 9.3 will serve as an example. The shaded
sections 02 and 03 shall be repeated e.g. 30 times.
Program
section
Set-point
temp.
Fan Section
time
Operation
line1
Target
section
No. of
cycles
Min.
tolerance
Max.
tolerance
01 50
100
%
00:30:00
Off 1 0
-1999
+9999
02
100
100 %
01:30:00
Off
1
0
-5
+5
03
200
100 %
01:00:00
Off
1
0
-2
+2
04 200
100
%
03:20:00
Off 1 0 -1999
+9999
05 100
100
%
00:00:01
Off 1 0 -1999
+9999
The following table shows the resulting program, whereby the differences to the table above are shaded.
Program
section
Set-point
temp.
Fan Section
time
Operation
line1
Target
section
No. of
cycles
Min.
tolerance
Max.
tolerance
01 50
100
%
00:30:00
Off 1 0
-1999
+9999
02 100
100
%
01:30:00
Off 1 0 -5 +5
03 200
100
%
01:00:00
Off 2
30 -2 +2
04 200
100
%
03:20:00
Off 1 0 -1999
+9999
05 100
100
%
00:00:01
Off 1 0 -1999
+9999
Sections 02 and 03 will be executed in total 31 times; only then, the program will continue.
Entry of the values into the screen program table:
PGM
08:49:07 15.12.05
To have sections repeated indefinitely, enter the number of cycles “Cy” as -1.
9.6
Behavior after power failure in Program Mode
Execution of the program is resumed at the point where the interruption occurred with the latest set-points
reached during program course. The power failure is noted in the event list. No error message is dis-
played indicating that a power failure has taken place.
Содержание APT.line M Series
Страница 54: ...M 01 2009 page 54 61 15 6 Dimensions M 53 ENT ENT ENT...
Страница 55: ...M 01 2009 page 55 61 15 7 Dimensions M 115 ENT ENT ENT...
Страница 56: ...M 01 2009 page 56 61 15 8 Dimensions M 240 6 8 ENT ENT ENT...
Страница 57: ...M 01 2009 page 57 61 15 9 Dimensions M 400 ENT ENT ENT...
Страница 58: ...M 01 2009 page 58 61 15 10 Dimensions M 720 ENT ENT ENT...