DD1010 FLYNET
WARNING
The sizing and laying of the power cable and the external disconnect switch are the responsibility
of the customer.
3.2.3
Wiring diagram (version with cable glands)
Connection to the power supply line is the responsibility of the installer. The customer must install
the protective conductor and the power supply cable through specialised personnel.
Protective ground connection
Connect the system protective ground to the indicator with a yellow-green cable of at least 6mm².
Use the ground screw located under the indicator.
The equipotential conductor from the scale must also be connected to the same grounding point.
Lay a three-pin cable with a cross-section suitable for the type of system. For the choice of the cable,
refer to the technical power supply characteristics.
Also provide a disconnect switch upstream of the supply line. The disconnect switch must be
accessible during system maintenance operations.
Essential characteristics of the power supply cable:
Double insulation cable with 3 coloured inner conductors
(line=brown, neutral=blue, protective ground=yellow-green)
Inner conductors with cross-section from 1.5mm² to 2.5mm²
External sheath diameter from 5 to 10mm
Key
1. L = Line, brown conductor
2. N = Neutral, blue conductor
3. T = Protective ground, yellow-green conductor
Figure 3.2-3
– Terminal board view