SS2200 Remote Controller

General Purpose, AC Voltage

General

The SS2200 Remote Controller is a microprocessor-based programmable controller specifically 
designed to control single line and dual line centralized lubricating systems. The remote controller 
will operate on time or machine cycles and will control electric or motor-driven lubricators. The 
controller is housed in a nEmA 4X polycarbonate enclosure with a clear front cover. Precise LEd 
indicators clearly display idle, lube or fault modes, and a three-digit numerical display used during 
both programming and lube system operation.

The SS2200 remote controller is easy to program. Simply advance through the programming steps  
with the select key, increasing or decreasing the displayed value for each step with the + and – keys. 
The program is permanently stored by EEPROm permanent memory.

Technical Data

Input Voltage

115 VAC, 50/60 Hz (Over voltage protected)

Pump Output

Pulsed or continuous, Form A, 115 VAC, 5 amps inrush, 2 amps continuous

Cycle Switch

12-16 VdC, 12-16 mA dC

Fault Switch

12-16 VdC, 12-16 mA dC

Fault Relay Contacts

2 amps, 125 VAC

Enclosure

nEmA 4X Polycarbonate

Ambient Temperature

20°F to 120°F

Vibration

1.5 g

Permanent Memory

EEPROm (no battery)

Installation and Connections

before making any connections, make sure they are within the rating given shown in the 

Terminal 

Connections

 schematic on right.

Input:

1. 

 The controller operates on 115 VAC 50/60 Hz electrical power, connected to  

the terminals labeled “Hot, neutral, 120 VAC input.” These terminals are overvoltage protected. 
The controller does not contain a power switch, and means of quick disconnecting  
electrical power to a unit should be easily accessible for installation, troubleshooting, and 
emergency shutoff.

Pump:

2. 

 The controller supplies output power for operating pumps as Form A, 115 VAC, 5 amp, 

inrush, 2 amp continuous from the terminals labeled “neutral, Hot, 120 VAC Pump.” This output 
can be programmed (step #P6 and P7) to be continuous or pulsed.

Relay:

3. 

 The controller contains a fault relay which is programmed to be normally open or normally 

closed (step #P9) and which changes state when a fault is detected. The relay has a normally 
open and a normally closed contact rated at 2 amp 125 VAC. The relay terminals are labeled 
“Relay, n.O., n.C.”

Cycle:

4. 

 The cycle switch which counts divider valve or reversing valve cycles must be connected to 

the terminals labeled ”+, –, cycle.” Power through the switch will be 12-16 VdC, 12-16 mA dC. if a 
cord containing an LEd is used, power polarity must be observed.

Fault Count:

5. 

 The terminals labeled “+, –, Fault Count” can be programmed for one of two outputs  

(step #P1) system fault or machine cycle count.

Terminal Connections

 

Power must be off when making  
any connections.

Содержание SS2200

Страница 1: ...ibration 1 5 g Permanent Memory EEPROM No Battery Installation and Connections Before making any connections make sure they are within the rating given shown in the Terminal Connections schematic on right Input 1 The controller operates on 115 VAC 50 60 Hz electrical power connected to the terminals labeled Hot Neutral 120 VAC Input These terminals are overvoltage protected The controller does not...

Страница 2: ...ded Lube Amber LED 2 When the controller is in the lube mode the amber LED will be on The numerical display will count down the cycle switch transitions remaining before lubrication is stopped and the idle mode begins If the key is held down during lube mode the numerical display will change to show the fault time in minutes remaining Fault Red LED 3 When the controller detects a fault the red LED...

Страница 3: ...e or key to display the c determined value Step 2 Idle Unit P2 Press the Select key until the numerical a display reads P2 Determine the units of measurement b required based on time or machine count operation programmed in step 1 Time Machine Counts 0 Minutes 0 Counts x 1 1 Hours 1 Counts x 10 Use the or key to display the c determined value If units other than minutes are used place d the unit l...

Страница 4: ...y until the controller enters the idle mode The program has been saved and the controller will operate as programmed To Change Programming To find out the current setting of any program step or to make changes enter the program ming mode by pressing the Select key until the desired step number is displayed Verify setting or make changes then press the Select key until the controller enters the idl...

Страница 5: ...the controller Pump Output The pump output from the controller can be programmed to be either continuous or pulsed programming step P6 Continuous output is used to actuate a motor starter for an electric motor driven pump Pulsed output is used to actuate an air solenoid valve for an air driven piston pump The on time for pulsed output is programmable in step P7 from 1 99 seconds The off time is fi...

Страница 6: ...e cycle takes 90 seconds set the fault time to 120 seconds Fault Mode When the controller detects one of six types of faults it will enter the fault mode The red fault LED will turn on the fault code will be displayed the pump output will be turned off and the fault relay will change state Time Base Time base operation is when minutes or hours are used to determine the length of time the controlle...