SS2200 Remote Controller
General Purpose, AC Voltage
General
The SS2200 Remote Controller is a microprocessor-based programmable controller specifically
designed to control single line and dual line centralized lubricating systems. The remote controller
will operate on time or machine cycles and will control electric or motor-driven lubricators. The
controller is housed in a nEmA 4X polycarbonate enclosure with a clear front cover. Precise LEd
indicators clearly display idle, lube or fault modes, and a three-digit numerical display used during
both programming and lube system operation.
The SS2200 remote controller is easy to program. Simply advance through the programming steps
with the select key, increasing or decreasing the displayed value for each step with the + and – keys.
The program is permanently stored by EEPROm permanent memory.
Technical Data
Input Voltage
115 VAC, 50/60 Hz (Over voltage protected)
Pump Output
Pulsed or continuous, Form A, 115 VAC, 5 amps inrush, 2 amps continuous
Cycle Switch
12-16 VdC, 12-16 mA dC
Fault Switch
12-16 VdC, 12-16 mA dC
Fault Relay Contacts
2 amps, 125 VAC
Enclosure
nEmA 4X Polycarbonate
Ambient Temperature
20°F to 120°F
Vibration
1.5 g
Permanent Memory
EEPROm (no battery)
Installation and Connections
before making any connections, make sure they are within the rating given shown in the
Terminal
Connections
schematic on right.
Input:
1.
The controller operates on 115 VAC 50/60 Hz electrical power, connected to
the terminals labeled “Hot, neutral, 120 VAC input.” These terminals are overvoltage protected.
The controller does not contain a power switch, and means of quick disconnecting
electrical power to a unit should be easily accessible for installation, troubleshooting, and
emergency shutoff.
Pump:
2.
The controller supplies output power for operating pumps as Form A, 115 VAC, 5 amp,
inrush, 2 amp continuous from the terminals labeled “neutral, Hot, 120 VAC Pump.” This output
can be programmed (step #P6 and P7) to be continuous or pulsed.
Relay:
3.
The controller contains a fault relay which is programmed to be normally open or normally
closed (step #P9) and which changes state when a fault is detected. The relay has a normally
open and a normally closed contact rated at 2 amp 125 VAC. The relay terminals are labeled
“Relay, n.O., n.C.”
Cycle:
4.
The cycle switch which counts divider valve or reversing valve cycles must be connected to
the terminals labeled ”+, –, cycle.” Power through the switch will be 12-16 VdC, 12-16 mA dC. if a
cord containing an LEd is used, power polarity must be observed.
Fault Count:
5.
The terminals labeled “+, –, Fault Count” can be programmed for one of two outputs
(step #P1) system fault or machine cycle count.
Terminal Connections
Power must be off when making
any connections.