![bihl+Wiedemann AS-Interface 2.1 Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/bihl-wiedemann/as-interface-2-1/as-interface-2-1_user-manual_2750672019.webp)
AS-Interface Analog Module
Connections, Displays and Operating Keys
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
19
4.1.1.3
Positioning of Jumpers (Input-/Output Modules)
By means of the jumpers, the choice is made whether the sensors/actuators of the
modules with 2 inputs, respectively 2 outputs are supplied by AS-Interface or by a
external help voltage. In order to attach the sensors/actuators and to put the jump-
ers into the right position, the cover of the analog module must be opened.
If the attached sensors and actuators are supplied by AS-Interface, the following
position of jumpers must be used:
If the attached sensors and actuators are supplied by external help voltage, the fol-
lowing position of jumpers must be used:
Jumpers shall only be put or pulled in unpowered condition.
If the sensors are supplied by AS-Interface, only AS-Interface cable
must be used in the substructure module. A cable for external help
voltage must not be used in this case.
7
8
9
10
1
2
3
4
11
5
12
6
Cage clamp terminals
LEDs
Jumper
24V AS-i
24V ext.