2.13
Installing the controller
2.13.1 Controller details
Positioning
•
Fix the controller to the wall or to a standard socket.
•
Mount the controller at a height of 1.5 m above the floor.
Cabling
Note:
n
Take the following into account, otherwise faults may
occur:
-
The control cable between the controller and the
(first) connected unit is not to exceed 50m.
-
Keep control cables away from electromagnetic fields
and interference sources such as high-voltage cables
and fluorescent-light starters.
-
Stretch control cables out or wind them bifilarly.
Note:
n
Use only control cables from Biddle Biddle. Standard mod-
ular telephone cable is
not
suitable.
Multiple units operated from one controller
•
Up to 10 units can be connected to one single controller.
To do so, the units must be interlinked.
•
The following combinations of units are possible:
-
units with unit codes ending on 11;
-
units with unit codes ending on 21;
-
units with unit codes ending on 12, 13 or 14;
-
units with unit codes ending on 22, 23 or 24;
-
unit code 3000 only in conjunction with code 2023.
•
The total length of the control cables is not to exceed
100 m.
•
The distance between the controller and the first unit is
not to exceed 50 m.
Type CC 60-H2-M1
Code
U 230 V 1N~ 50 Hz
Biddle bv
Markowei 4
NL-9288 HA Kootstertille
Nº 123456/1-1 05-53
I
max
L1 xxx A
I
max
L2 -
M 30 kg
I
max
L3 -
Medium LPHW
P
motor
xxx kW
p
max
1400 kPa
P
heating
-
xxx
code