600 Gulf Freeway

Texas City, TX 77591

PHN:  (409) 935-5743

FAX:  (409) 938-4189

Copyright © 1996 - Bebco Industries, Incorporated - All Rights Reserved

Environmental Control Units Division

Bebco Industries

ECU Division Technical Bulletin RDP-12-R1.0

05/97

Opening:  21 Sq Ft Maximum

Area:  80 Sq Ft Maximum

Technical Description

Model RDP-12 is a remote-mount

pressurization unit for control rooms or buildings
containing no internal source of flammable vapors
or gases.  The unit utilizes a primary and secondary
fan to pressurize rooms or buildings with opening(s)
not exceeding a total of 21 square feet and a floor
area not exceeding 80 square feet.  The primary
fan is controlled by a variable speed drive to maintain
a safe (0.25") pressure when the doorway is sealed.
The secondary fan engages upon loss of safe
pressure, to generate a minimum air velocity of
sixty (60) feet per minute through the doorway, and
functions as a redundant fan if the primary fan fails.
This unit, combined with an intake system that
draws fresh air from a nonhazardous area, reduces
the hazardous (classified) area rating within the
room or building from Class I, Division 1 or 2 to
nonhazardous, in accordance with NFPA 496,
Chapter 5.

Basic Operation

Unit must be powered by a local disconnect

switch connected ahead of building power or
connected to a separate power source.  The unit is
started by closing the building door and placing the
secondary fan switch in the "automatic" position
and the primary fan switch in the "on" position.  The
primary fan then engages to regulate air flow and
maintain a safe pressure.  When the door is opened,
pressure will fall below the alarm setpoint.  The
primary fan will then increase velocity, and the unit
will activate an alarm signal delay timer and a
secondary fan delay timer.  These timers are field-
adjustable to permit immediate or delayed response
to changes in pressure.  Both timers are activated
and reset as pressure falls below and rises above
the alarm setpoint.  If the secondary fan or alarm
engages, they disengage when the door is sealed
and pressure rises above the alarm setpoint.

DIVISION 1 AREA APPLICATION NOTE:

INSTALLER MUST PROVIDE DISCONNECT EQUIPMENT TO

AUTOMATICALLY  REMOVE POWER FROM ALL NONRATED

DEVICES, UPON FAILURE OF THE PRESSURIZATION UNIT.

Standard Controls

Primary Fan "On" Indicator
- indicates that primary fan is engaged
- flashes when the ESD or ECO is engaged

Primary Fan Control Switch
- engages and disengages primary fan

Secondary Fan Control Switch
- off, manual and automatic positions

Alarm "Engaged" Indicator
- indicates alarm signal is active
- flashes when alarm signal is bypassed

Alarm Signal Bypass Switch
- allows bypass of alarm relay

RDP Horizontal Side

Angle View

Control Enclosure

Содержание RDP-12

Страница 1: ... a local disconnect switch connected ahead of building power or connected to a separate power source The unit is started by closing the building door and placing the secondary fan switch in the automatic position and the primary fan switch in the on position The primary fan then engages to regulate air flow and maintainasafepressure Whenthedoorisopened pressure will fall below the alarm setpoint T...

Страница 2: ...tedbuilding Inaddition thehousingcanbesupplied with an optional emergency remote control junction box for ECO or ESD IS barrier applications Theblowerhousingisfittedwithprimaryandsecondary fans mounted in a compact in line arrangement with the secondary fan mounted directly behind the primary fan Each motor is connected with approved MI mineral insulated cabletoseparatedisconnectswitchesmounted ex...

Страница 3: ... HW Hard Wiring Selection of this option requires the use of conduit seals and wiring approved for the location IS Intrinsically Safe Selection of this option allows use of intrinsically safe cabling approved for the location NOTE Loops are self powered 5 VDC 20 ma signals regardless of wiring method selection Signals must be maintained independently by normally closedswitchestopreventshutdownorov...

Страница 4: ...GDM 100 Hydrogen Sulfide Monitor HGDS 100 Hydrogen Sulfide Sensor OGDM 100 Oxygen Deficiency Monitor OGDS 100 Oxygen Deficiency Sensor GDPS 100 24 VDC Monitor Power Supply GDSB 1216 Sensor Stack Mount Bracket REMOTE MOUNT DISCHARGE COMPONENTS ADGA 12 Adj Discharge Grill Assembly DE 12 Discharge Extension DN 12 Discharge Ninety DCF 12 Discharge Curb Flange 10 75 6 5 9 5 18 Control Enclosure Front V...

Отзывы: