Wiring Notes
To prevent noise incurred in PUL/DIR signal, pulse/direction signal wires and motor wires
should not be tied up together. It is better to separate them by at least 10 cm, otherwise the
disturbing signals generated by motor will easily disturb pulse direction signals, causing
motor position error, system instability and other failures.
If a power supply serves several drivers, separately connecting the drivers is recommended
instead of daisy-chaining.
It is prohibited to pull and plug connector P2 while the driver is powered ON, because there is
high current flowing through motor coils (even when motor is at standstill). Pulling or
plugging connector P2 with power on will cause extremely high back-EMF voltage surge,
which may damage the driver.
Switch Choice:
1.Microstepping choice:
SW 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SW 6
ON
ON
OFF
OFF
ON
ON
OFF
OFF
SW 7
ON
ON
ON
ON
OFF
OFF
OFF
OFF
Micro
1
2
4
8
16
32
64
128
2.Current choice
::::
SW 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
SW 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
SW 3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Current
(A)
0.25
0.5
0.75
1
1.25
1.5
1.75
2
4.Sequence Chart of Control Signals
In order to avoid some fault operations and deviations, PUL, DIR and ENA should abide by
some rules, shown as following diagram
:
NOTE
:
Enable signal is always high in this drive. Any external supply of 5 Vdc applied will disable
the Drive.