Страница 1: ...BAJA SILUETA INVERTER DC SERIES BSBSI24CTK...

Страница 2: ......

Страница 3: ...General Information 1 Part 2 Indoor Units 6 Part 3 Outdoor Units 21 Part 4 Installation 50 Part 5 Control 61 The specifications designs and information in this book are subject to change without noti...

Страница 4: ......

Страница 5: ...General Information General Information 1 Part 1 General Information 1 Model Lists 2 2 External Appearance 3 2 1 Indoor Units 3 2 2 Outdoor Units 3 3 Nomenclature 4 4 Features 5...

Страница 6: ...Model Lists 2 General Information 1 Model Lists Universal Outdoor unit Model Compressor type Compressor Brand Matched indoor units BSBSIC24CTK Rotary DC Inverter GMCC BSBSIE24CTK...

Страница 7: ...External Appearance General Information 3 2 External Appearance 2 1 Indoor Units High static pressure duct 2 2 Outdoor Units Single fan outdoor unit...

Страница 8: ...r Unit 3 2 Outdoor Unit B S B S I C 24 C T K Serie Calor Modelo Condensadora Condensadora unidad exterior Inverter Baja Silueta Silent Air BGH B S B S I E 24 C T K Serie Calor Modelo Evaporadora Evapo...

Страница 9: ...r more choice for you 4 4 Low ambient kit is standard for outdoor units except 12K 4 5 Network control function is standard for the indoor units except 12K 4 6 Standard auto restart function and follo...

Страница 10: ...pe 1 Features 7 2 Specifications 10 3 Dimensions 11 4 Service Space 12 5 Wiring Diagrams 13 6 Static Pressure 14 7 Electric Characteristics 15 8 Sound Levels 16 9 Accessories 17 10 The Specification o...

Страница 11: ...or from rear to the bottom in order to matching the installation condition 1 3 Fresh air intake function Install one duct from the reserved fresh air intake to outdoor Continually inhale the fresh air...

Страница 12: ...te on off and central control ports Reserved remote on off ports and central control ports can connect the cable of an on off controller or a central controller to realize remote on off control functi...

Страница 13: ...th a receiver in the E box Move out the display and fix it in other place even in the distance of 10m The unit will realized remoter control The wired controller and the display board can display the...

Страница 14: ...3 h 1400 1100 1000 Indoor external static pressure Hi Pa 70 Indoor noise level Hi Med Lo dB A 45 43 41 Throttle type Indoor unit Dimension WxDxH mm 920x635x270 Packing WxDxH mm 1135x655x350 Net Gross...

Страница 15: ...mensions H G E F A B D C L M Capacity KBtu Outline dimension mm Air outlet opening size Air return opening size Size of outline dimension mounted plug A B C D E F G H I J K L M 24 920 270 635 570 65 7...

Страница 16: ...Service Space Duct Type 12 4 Service Space Ensure enough space required for installation and maintenance All the indoor units reserve the hole to joint the fresh air pipe The hole size as following...

Страница 17: ...Wiring Diagrams 13 Duct Type 5 Wiring Diagrams BSBSI24CTK...

Страница 18: ...ure 14 Duct Type 6 Static Pressure 24 000Btu h Super high speed 1400 1300 Low speed 10 20 30 40 50 60 70 80 90 Pa 800 900 1000 1100 Air volume m h 3 External static pressure Pa High speed Mid speed 12...

Страница 19: ...Electric Characteristics 15 Duct Type 7 Electric Characteristics Model Indoor Unit Power Supply Hz Voltage Min Max MFA BSBSIE24CTK 50 220 240 198 254 15 Notes MFA Max Fuse Amps A...

Страница 20: ...Sound Levels Duct Type 16 8 Sound Levels Suction Discharge Microphone 1 4m Concealed Duct Type Duct Duct Model Noise level dB A H M L BSBSIE24CTK 45 43 41...

Страница 21: ...tion sheath 2 Binding tape 1 Seal sponge 1 Drainpipe Fittings for cooling heating Drain joint 1 Seal ring 1 Wired controller Its Frame Wired controller 1 Others Owner s manual 1 Installation manual 1...

Страница 22: ...ase Frequency and Voltage 220 240V 50Hz POWER WIRING mm 2 3 1 0 CIRCUIT BREAKER A 15 OUTDOOR UNIT POWER Phase 1 phase Frequency and Voltage 220 240V 50Hz POWER WIRING mm2 3 2 5 CIRCUIT BREAKER A 30 In...

Страница 23: ...Field Wiring 19 Duct Type 11 Field Wiring...

Страница 24: ...Field Wiring Duct Type 20 For model 18 60...

Страница 25: ...2 1 Part 3 Outdoor Units 1 Specification 22 2 Dimensions 23 3 Service Space 24 4 Piping Diagrams 25 5 6 Electric Characteristics 26 7 Operation Limits 27 8 Sound Levels 28 PointCheckFunction 29 9 Trou...

Страница 26: ...Number of circuits 6 Outdoor air flow Hi Low m 3 h 2700 Sound level sound pressure Hi Low dB A 54 Throttle type EXV Capillary Outdoor unit Dimension W x D x H mm 842 324 695 Packing W x D x H mm 965 3...

Страница 27: ...Dimensions 23 2 Dimensions Model Unit mm A B C D E F H BSBSIC24CTK 842 560 335 360 312 324 695...

Страница 28: ...Service Space 24 3 Service Space More than 60cm More than 30cm More than 60cm More than 200cm Air inlet Air inlet More than 30cm Air outlet Wall or obstacle Maintain channel...

Страница 29: ...ATOR HEAT EXCHANGE CONDENSER Compressor 2 WAY VALVE 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2 Evaporator temp sensor T1 Room temp sensor T3 Condenser temp sensor T5 Discharge temp sensor T4 Ambient t...

Страница 30: ...Electric Characteristics 26 5 Electric Characteristics Model Outdoor Unit Hz Voltage Min Max BSBSIC24CTK 50 220 240 198 254...

Страница 31: ...on Limits 27 6 Operation Limits 18 60k 17 30 15 50 Indoor temperature WB Outdoor temperature DB Cooling Standard operation 17 30 15 24 Indoor temperature DB Outdoor temperature WB Heating Standard ope...

Страница 32: ...Sound Levels 28 7 Sound Levels Model Noise level dB A H BSBSIC24CTK 54...

Страница 33: ...l show 70 If the indoor unit is not connected the digital display tube will show 08 Outdoor ambient temp T4 09 Compressor discharge temp Tp The display value is between 30 120 degree If the temp is lo...

Страница 34: ...ction 10 1 1 Display board Duct OPERATION TIMER DEF FAN ALARM Temporary button Operation lamp Timer indicator Infrared signal receiver Alarm indicator PRE DEF indicator cooling and heating type or fan...

Страница 35: ...E0 2 Communication malfunction between indoor and outdoor units X X X E1 3 Open or short circuit of T1 temperature sensor X X X E2 4 Open or short circuit of T2 temperature sensor X X E3 5 Open or sh...

Страница 36: ...ormal Check whether the resistance of the evaporator temp sensor is correct according to Annex 1 Judge 2 Room temp sensor is abnormal Replace evaporator temp sensor No Yes Check whether the resistance...

Страница 37: ...on in the following part Indoor alarm lamps flash at 1Hz Judge 1 Condenser temp sensor is abnormal Check whether the resistance of the condenser temp sensor is correct according to Annex 1 Judge 2 Out...

Страница 38: ...few minutes then check whether the system can run normally Replace indoor PCB Trouble is solved Yes No Check whether the water drain pipe is blocked No Solve to make the water can flow fluently Yes C...

Страница 39: ...E6 PFC module protection Only for 30K 36K with 1 phase P0 Top temperature protection of compressor P1 High pressure protection P2 Low pressure protection P3 Current protection of compressor P4 Discha...

Страница 40: ...ge 4 Check whether the signal wiring between the indoor and outdoor units is broken Yes Replace the broken wiring No Judge 2 Check whether the signal wiring is shield cable or whether the shield cable...

Страница 41: ...nnecting wiring between the IPM module negative pole and the CN13 on the power board is broken off E3 display Communication malfunction in outdoor IC and DSP Replace the outdoor main board Yes Insert...

Страница 42: ...he condenser temp sensor is broken off Connect the wiring well Yes No Check whether the resistance of condenser temp sensor is wrong refer to the Annex 1 Yes Replace condenser temp sensor No Judge 2 O...

Страница 43: ...compressor Check the voltage of outdoor unit power supply whether the voltage between L 1 and N is about 172 265V No Replace the power board then check whether the system can run normally Check the p...

Страница 44: ...t system such as clogging of capillary etc P0 display Top temperature protection of compressor Judge 1 Whether compressor operates Yes No Whether the connection is good Method Charge refrigerant Yes W...

Страница 45: ...lace high pressure switch No Check whether the refrigerant system is ok Replace outdoor main board No Judge 3 Check whether the outdoor ambient temperature is too high Yes Stop the unit No Judge 4 Che...

Страница 46: ...o Judge 4 The refrigerant of the system is leakage Yes Method Connect the pressure gauge to the gauge joint of the system check whether the pressure is lower than 0 14MPa Leak hunting Charge nitrogen...

Страница 47: ...hether the outdoor ambient temperature is too high Yes Stop the unit Replace outdoor main board No No Judge 3 Check whether the outdoor unit is bad ventilation Yes Make the outdoor unit ventilate well...

Страница 48: ...temp is more than 115 C No Check whether the wiring connection is right between compressor discharge temp sensor and PCB according to wiring diagrams Yes Method Check whether the resistance of compres...

Страница 49: ...the resistance of condenser temp sensor is correct refer to the Annex 1 Yes Replace outdoor main board No Replace the temperature sensor Yes Judge1 The outdoor temp is too high Replace outdoor main bo...

Страница 50: ...eck whether there is the condition that value of resistance is 0 Yes Replace the single phase bridge No No Check whether the connecting line of every reactor is normal If the line is broken the resist...

Страница 51: ...k or not No Yes Check whether the three phase bridge is normal No Replace the three phase bridge No Yes Check whether the 3300 F 400V electrolytic capacitor is normal No Replace this electrolytic capa...

Страница 52: ...ocked and the indoor fan is normal Yes Clean the heat exchanger and the air outlet Replace the temperature sensor No Check whether the indoor fan is normal Check refrigerant system such as clogging of...

Страница 53: ...76 1 34105 116 0 40060 3 41 5878 37 5 87359 77 1 29078 117 0 38991 2 39 8239 38 5 62961 78 1 25423 118 0 37956 1 37 1988 39 5 39689 79 1 21330 119 0 36954 0 35 2024 40 5 17519 80 1 17393 120 0 35982...

Страница 54: ...Installation 50 Part 4 Installation 1 Precaution on Installation 51 2 Vacuum Dry and Leakage Checking 52 3 Additional Refrigerant Charge 54 4 Water Drainage 55 5 Insulation Work 58 6 Wiring 59 7 Test...

Страница 55: ...unit should be closed absolutely as original state Every time you connect it first loosen the nuts at the part of stop value then connect the flare pipe immediately in 5 minutes If the nuts have been...

Страница 56: ...ruction environment common vacuum dry special vacuum dry Common vacuum dry procedure z Vacuum dry for the first time connect the all purpose detector to the inlet of liquid pipe and gas pipe and run t...

Страница 57: ...the second time Fill nitrogen to 0 5Kgf cm2 Because nitrogen is for drying gas it has vacuum drying effect during vacuum destroy But if the moisture is too much this method can t dry thoroughly So pl...

Страница 58: ...losions and accidents so always ensure that the appropriate refrigerant is charged e Refrigerant containers shall be opened slowly f Always use protective gloves and protect your eyes when charging re...

Страница 59: ...revent atomization Drainpipe should be installed before installing indoor unit After powering on there is some water in water receiver plate Please check if the drain pump can operate correctly All co...

Страница 60: ...D mm Thick Hard PVC 14 25 3 0 Hard PVC 14 88 30 3 5 Hard PVC 88 334 40 4 0 Hard PVC 175 334 50 4 5 Hard PVC 334 80 6 0 4 5 Drainage test 1 Drainage without drain pump After finishing drainpipe instal...

Страница 61: ...lamp flashes even overflow from the water receipt plate z Keep on pouring water until it gives an alarm signal for high water level check if the pump drains water at once If the water level can t fall...

Страница 62: ...2 Thickness choice for insulation material Insulation material thickness is as follows Pipe diameter mm Adiabatic material thickness Refrigerant pipe 6 4 25 4 10mm 28 6 38 1 15mm Drainage pipe Inner...

Страница 63: ...e pipes Make sure there s no clearance in the joining part of the accessorial insulation material and local preparative insulation material 5 3 Drainage pipe insulation 1 The connection part should be...

Страница 64: ...tioner is pre heated by turning on the power 3 According to the user s requirement install the remote controller when the remote controller s signal can reach the indoor unit smoothly 4 Test operation...

Страница 65: ...Control 61 Control Part 5 Control 1 Controller 62...

Страница 66: ...unction for wireless remote controller Model and Specification Model RG51Q1 BG C E Rated voltage 3 0V Dry batteries R03 LR03 2 Min voltage for sending signal of CPU 2 0V Effective receiving distance 8...

Страница 67: ...n or turning off the air conditioner 8 FAN SPEED Fan speed will be selected in following sequence once pressing this button AUTO LOW MED HIGH 9 TIME ON For time ON setting Once pressing this button th...

Страница 68: ...TO COOL DRY HEAT and FAN as the following figure indicates 3 SWING Button Push this switch button to change the louver angle 4 RESET Button When the RESET button is pushed all of the current settings...

Страница 69: ...tton one time then the operation modes will change In turn as follows AUTO COOL DRY HEAT FAN Remark no heating mode if wire controller is set as the cool only 2 Timer on button Push the button to set...

Страница 70: ...AUTO COOL DRY HEAT FAN 2 Fan speed button FAN SPEED Press FAN SPEED to select fan speed from AUTO LOW MED and HIGH NOTE some air conditioners have no MED fan speed and then the MED is regarded as HIGH...

Страница 71: ...play the set temperature Press the buttons of and to set temperature at the mode of FAN there is no figure display in the area Installation Installation Notice When the air conditioner needs the const...

Страница 72: ...Controller Control 68 NOTE Never turn screws too tightly or else the cover would be dented or the Liquid Crystal breaks Please leave enough long cable for maintenance of the Wire Controller Board...