BFT VIRGO SMART BT A Скачать руководство пользователя страница 22

D812939 00096_03

VIRGO SMART BT A

 - 47

ENGLISH

INSTALLATION MANUAL

Logic

Definition

Default

Cross out

setting

used

Optional extras

AUX 0

Configuration of 

AUX 0 output. 20-21

6

0

Output configured as 2nd Radio Channel.

1

Output configured as SCA (gate open light).

2

Output configured as Courtesy Light command.

3

Output configured as Zone Light command.

AUX 3

Configuration of 

AUX 3 output.  

26-37

0

4

Output configured as Stair Light

5

Output configured as Alarm

6

Output configured as Flashing light

7

Output configured as Latch

8

Output configured as Magnetic lock

9

Output configured as Maintenance

10

Output configured as Flashing Light and Maintenance.

FIXED CODE

Fixed code

0

0

Receiver is configured for operation in rolling-code mode. 

Fixed-Code Clones are not accepted.

1

Receiver is configured for operation in fixed-code mode. 

Fixed-Code Clones are accepted.

Protection 

level

Setting the 

protection level

0

0

A - The password is not required to access the programming menus 

B - Enables wireless memorizing of transmitters. 

Operations in this mode are carried out near the control panel and do not require access:

- Press in sequence the hidden key and normal key (T1-T2-T3-T4) of a transmitter that has already been 

memorized in standard mode via the radio menu.

- Press within 10 sec. the hidden key and normal key (T1-T2-T3-T4) of a transmitter to be memorized.

The receiver exits programming mode after 10 sec.: you can use this time to enter other new transmitters 

by repeating the previous step.

C - Enables wireless automatic addition of clones.

Enables clones generated with the universal programmer and programmed Replays to be added to the 

receiver’s memory.

D - Enables wireless automatic addition of replays.

Enables programmed Replays to be added to the receiver’s memory.

E - The board’s parameters can be edited via the U-link network

1

A - You are prompted to enter the password to access the programming menus  

The default password is 1234.

    No change in behaviour of functions B - C - D - E from 0 logic setting

2

A - You are prompted to enter the password to access the programming menus  

The default password is 1234.

B - Wireless memorizing of transmitters is disabled.

C - Wireless automatic addition of clones is disabled. No change in behaviour of functions D - E from 0 logic 

setting

3

A - You are prompted to enter the password to access the programming menus  

    The default password is 1234.

B - Wireless memorizing of transmitters is disabled.

D - Wireless automatic addition of Replays is disabled. 

    No change in behaviour of functions C - E from 0 logic setting

4

A - You are prompted to enter the password to access the programming menus  

   The default password is 1234.

B - Wireless memorizing of transmitters is disabled.

C - Wireless automatic addition of clones is disabled. 

D - Wireless automatic addition of Replays is disabled. 

E - The option of editing the board’s parameters via the U-link network is disabled.

Transmitters are memorized only using the relevant Radio menu.

IMPORTANT: This high level of security stops unwanted clones from gaining access and also stops radio 

interference, if any.

SERIAL 

ODE

Serial mode  

(Identifies how board 

is configured in a BFT 

network connection).

0

0

Standard SLAVE: board receives and communicates commands/diagnostics/etc.

1

Standard MASTER: board sends activation commands (START, OPEN, CLOSE, PED, STOP) to other boards.

ADDRESS

Address

0

[ ___ ]

Identifies board address from 0 to 119 in a local BFT network connection. 

(see U-LINK OPTIONAL MODULES section)

EXPI1

Configuration of 

EXPI1 input on 

input-output expan-

sion board.  

1-2

1

0

Input configured as Start E command.

1

Input configured as Start I command.

2

Input configured as Open command.

3

Input configured as Close command.

4

Input configured as Ped command.

5

Input configured as Timer command.

6

Input configured as Timer Pedestrian command.

7

Input configured as Phot (photocell) safety. 

8

Input configured as Phot op safety (photocell active during opening only).

9

Input configured as Phot cl safety (photocell active during closing only).

10

Input configured as Bar safety (safety edge).

11

Input configured as safety Bar OP, safety edge with inversion active only while opening, if while closing 

the movement stops.

12

Input configured as safety Bar CL, safety edge with inversion active only while closing, if while opening 

the movement stops.

13

 Input configured as Phot test safety, tested photocell. Input 3 (EXPI2) on input/output expansion board is 

switched automatically to safety device test input, EXPFAULT1.

14

Input configured as Phot op test safety, tested photocell active only while opening. Input 3 (EXPI2) on input/

output expansion board is switched automatically to safety device test input, EXPFAULT1

15

Input configured as Phot cl test safety, tested photocell active only while closing. Input 3 (EXPI2) on input/

output expansion board is switched automatically to safety device test input, EXPFAULT1

16

Input configured as Bar safety, tested safety edge. Input 3 (EXPI2) on input/output expansion board is 

switched automatically to safety device test input, EXPFAULT1.

17

Input configured as safety Bar OP test, safety edge with inversion active only while opening, if while closing 

the movement stops. Input 3 (EXPI2) on input/output expansion board is switched automatically to safety 

device test input, EXPFAULT1.

18

Input configured as safety Bar CL test, safety edge with inversion active only while closing, if while opening 

the movement stops. Input 3 (EXPI2) on input/output expansion board is switched automatically to safety 

device test input, EXPFAULT1.

Содержание VIRGO SMART BT A

Страница 1: ...IRE AUTOMATIZACIONES A BRAZO PARA PORTONES CON BATIENTE AUTOMATIZA ES DE BRA O PARA PORT ES DE BATENTE Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully...

Страница 2: ...an eye on the roller shutter while it is moving and keep peopleawayuntilithasclosedcompletely Exercise care when activating the release if such a device is fitted as an open shutter could drop quickly...

Страница 3: ...E E click click 180 18 0 S ON OFF MANUALE D USO MANOVRA DI EMERGENZA USER GUIDE EMERGENCY OPERATION MANUEL D UTILISATION DE LA MANOEUVRE D URGENCE BEDIENUNGSHANDBUCH NOTFALLMAN VER MANUAL DE USO MANI...

Страница 4: ...ekeyoperated must be installed at a height of at least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light flashing light in a visible position and also at...

Страница 5: ...PA OL PORTUGU S DEUTSCH ITALIANO INSTALLAZIONE VELOCE QUICK INSTALLATION INSTALLATION RAPIDE SCHNELLINSTALLATION INSTALACI N R PIDA INSTALA O R PIDA A B 188 292 224 5 x 0 7 5 m m 2 5 x 0 7 5 m m 2 2 x...

Страница 6: ...115 118 50 90 92 95 100 102 105 107 110 110 110 115 115 60 90 92 95 100 102 105 107 107 110 110 115 115 70 90 92 95 97 100 102 107 107 110 110 112 115 80 90 92 95 97 100 102 105 107 107 110 112 112 9...

Страница 7: ...B 62 min 300 1 2 3 4 D E 25 MAX D o or ou oder o ou P D L F MAX M10 MAX L 25 mm Destra Right Droitea Rechts Derecha Direita Sinistra Left Gauche Links Izquierda Esquerda Non in dotazione Not supplied...

Страница 8: ...M8 85 MAX M6 8 H Non in dotazione Not supplied Ne sont pas fournis Nicht im lieferum No asignadas en el equipamiento base N o fornecidas Non in dotazione Not supplied Ne sont pas fournis Nicht im lief...

Страница 9: ...LEKTRISCHE VERRIEGELUNG aus Sicherheitsgr nden empfohlen FECHADURA EL TRICA recomendada por raz es de seguran a FECHADURA EL TRICA recomendada por raz es de seguran a 1x P 2x R 1x P 2x R 1x P 2x R 2x...

Страница 10: ...a Pot ncia m xima 110W Ciclo massimo Maximum cycle Cycle maximum Max Zyklus Ciclo m ximo Ciclo m ximo 20 cycle h Con logica inversione direzione di apertura 000 DIR INT With reverse logic opening dire...

Страница 11: ...otoc lulas no comprobadas para fotoc lulas comproabdas v anse las siguientes p ginas Conex o de 1 par de fotoc lulas n o verificadas para fotoc lulas verificadas consultar p ginas seguintes Alimentazi...

Страница 12: ...em remotes end o o MIN 1 MAX 3 AUTO OPEN AUTO CLOSE Exit Men Confirm Switch on display Scroll up Scroll down ar automatic operation residential sr semiautomatic operation residential ac automatic oper...

Страница 13: ...6 1 2 1 2 3 4 5 52 50 TX1 RX1 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 T...

Страница 14: ...8 rst8 8888 1 2 3 4 6 5 3s UNIDA THALIA N O P ON OFF PROGRAMMATORE PALMARE UNIVERSALE UNIVERSAL PALMTOP PROGRAMMER PROGRAMMATEUR DE POCHE UNIVERSEL UNIVERSELLEN PALMTOP PROGRAMMIERER PROGRAMADOR DE BO...

Страница 15: ...ge test failed Check safety edge connection and or logic settings ER03 Opening photocell test failed Check photocell connection and or parameter logic setting ER04 Closing photocell test failed Check...

Страница 16: ...racket F to the leaf Insert the lever arm L into the output shaft of the gearmotor and secure it using the special pin P and the self locking nut D Release the actuator by operating the release lever...

Страница 17: ...l connecting cables must be kept far enough away from the dissipater WARNING For connection to the mains power supply use a multicore cable with a cross sectional area of at least 3x1 5mm2 of the kind...

Страница 18: ...not used leave jumper inserted SAFE logic 1 Input configured as Phot test tested photocell fig M ref 2 Switches photocell testing on at start of operation When beam is broken photocells are active du...

Страница 19: ...emand wherenecessary editthemasdescribed in the programming section WARNING Check that the force of impact measured at the points provided for by standard EN 12445 is lower than the value laid down by...

Страница 20: ...ening closing cycle is required WARNING When the display reads SET obstacle detection is not active Maintenance 0 250 0 Programming number of operations for maintenan ce threshold in hundreds Allows y...

Страница 21: ...t measured at the points provided for by standard EN 12445 is lower than the value laid down by standard EN 12453 If in doubt use auxiliary safety devices This feature is useful when dealing with inst...

Страница 22: ...ess memorizing of transmitters is disabled C Wireless automatic addition of clones is disabled D Wireless automatic addition of Replays is disabled E The option of editing the board s parameters via t...

Страница 23: ...igured as Stair Light EXPO2 Configuration of EXPO2 output on input output expansion board 6 7 11 5 Output configured as Alarm 6 Output configured as Flashing light 7 Output configured as Latch 8 Outpu...

Отзывы: