background image

D812939 00096_03

44 

- VIRGO SMART BT A

INSTALLATION MANUAL

TABLE “A” - PARAMETERS MENU - (

PARA

)

Parameter

min.

max.

Default Personal

Definition

Description

OPEN DELAY

TI E

0

10

3

Motor 2 opening delay 

time [s]

Motor 2 opening delay time with respect to motor 1.

CLS DELAY

TI E

0

25

6

Motor 1 closing delay 

time [s]

Motor 1 closing delay time with respect to motor 2.

NOTE: 

if the time is set to maximum, before starting, engine 1 waits for the 

complete shut down of engine 2.

TCA

0

120

10

Automatic closing time 

[s]

Waiting time before automatic closing.

TRF.LGHT.CLR.T

1

180

40

Time-to-clear traffic light 

zone [s]

Time-to-clear for the zone run through by traffic controlled by the traffic light.

OP.DIST.SLOUD

0

50

10

Slow-down distance 

during opening [%] 

Slow-down distance for motor(s) during opening, given as a percentage 

of total travel. 

WARNING: Once the parameter has been edited, a 

complete uninterrupted opening-closing cycle is required.  

WARNING: when the display reads “SET”, obstacle detection is not active.

ATTENTION: with actuators with integrated locks, the permanently active 

slowdown to a value higher than 5 is mandatory.

WARNING: in GIUNO, the slow-down distance is set with the sliding sensors

CL.DIST.SLOUD

0

50

10

Slow-down distance 

during closing [%] 

Slow-down distance for motor(s) during closing, given as a percentage 

of total travel. 

WARNING: Once the parameter has been edited, a 

complete uninterrupted opening-closing cycle is required.  

WARNING: when the display reads “SET”, obstacle detection is not active.

ATTENTION: with actuators with integrated locks, the permanently active 

slowdown to a value higher than 5 is mandatory.

WARNING: in GIUNO, the slow-down distance is set with the sliding sensors

6) SAFETY DEVICES

Note: only use receiving safety devices with free changeover contact.

6.1) TESTED DEVICES Fig. M

6.2) CONNECTION OF 1 PAIR OF NON-TESTED PHOTOCELLS FIG. L

7) CALLING UP MENUS: FIG. 2

7.1) PARAMETERS MENU (

PARA

) (PARAMETERS TABLE “A”)

7.2) LOGIC MENU (

LOGIC

)

 

(LOGIC TABLE “B”) 

7.3) RADIO MENU

 

(

radio

) (RADIO TABLE “C”)

-   IMPORTANT NOTE: THE FIRST TRANSMITTER MEMORIZED MUST BE 

IDENTIFIED BY ATTACHING THE KEY LABEL (MASTER).

In the event of manual programming, the first transmitter assigns the RECEIVER’S 

KEY CODE: this code is required to subsequently clone the radio transmitters.

The Clonix built-in on-board receiver also has a number of important advanced features: 

•  Cloning of master transmitter (rolling code or fixed code).

•  Cloning to replace transmitters already entered in receiver.

•  Transmitter database management.

•  Receiver community management.

To use these advanced features, refer to the universal handheld programmer’s 

instructions and to the general receiver programming guide.

7.4) DEFAULT MENU (

default

)

Restores the controller’s DEFAULT factory settings. Following this reset, you will 

need to run the AUTOSET function again. 

7.5) LANGUAGE MENU (

language

)

Used to set the programmer’s language on the display. 

7.6) AUTOSET MENU (

AUTOset

•  Launch an autoset operation by going to the relevant menu.

•  As soon as you press the OK button, the “.... ....  ....” message is displayed and the control 

unit commands the device to perform a full cycle (opening followed by closing), during 

which the minimum torque value required to move the leaf is set automatically.

  The number of cycles required for the autoset function can range from 1 to 3.

  During this stage, it is important to avoid breaking the photocells’ beams and not 

to use the START and STOP commands or the display.

  Once this operation is complete, the control unit will have automatically set the 

optimum torque values. Check them and, where necessary, edit them as described 

in the programming section.

WARNING!! Check that the force of impact measured at the points 

provided for by standard EN 12445 is lower than the value laid down 

by standard EN 12453.

Impact forces can be reduced by using deformable edges.

Warning!! While the autoset function is running, the obstacle detection 

function is not active. Consequently, the installer must monitor the 

automated system’s movements and keep people and property out 

of range of the automated system.

7.7)INSTALLATION TEST PROCEDURE

1.  Run the AUTOSET cycle (*)

2.  Check the impact forces: if they fall within the limits (**) skip to point 10 of the 

procedure, otherwise

3. Where necessary, adjust the speed and sensitivity (force) parameters: see 

parameters table.

4.  Check the impact forces again: if they fall within the limits (**) skip to point 10 

of the procedure, otherwise

5.  Apply a shock absorber profile

6.  Check the impact forces again: if they fall within the limits (**) skip to point 10 

of the procedure, otherwise

7. Apply pressure-sensitive or electro-sensitive protective devices (such as a 

safety edge) (**)

8.  Check the impact forces again: if they fall within the limits (**) skip to point 10 

of the procedure, otherwise

9.  Allow the drive to move only in “Deadman” mode

10. Make sure all devices designed to detect obstacles within the system’s operating 

range are working properly

(*) Before running the autoset function, make sure you have performed all the 

assembly and make-safe operations correctly, as set out in the installation 

warnings in the drive’s manual.

(**) Based on the risk analysis, you may find it necessary to apply sensitive 

protective devices anyway

7.8) STATISTICS MENU

Used to view the version of the board, the total number of operations (in 

hundreds), the number of transmitters memorized and the last 30 errors (the 

first 2 digits indicate the position, the last 2 give the error code).  Error 01 is the 

most recent.

7.9) PASSWORD MENU 

Used to set a password for the board’s wireless programming via the U-link 

network. With “PROTECTION LEVEL” logic set to 1,2,3,4, the password is required 

to access the programming menus. After 10 consecutive failed attempts to 

log in, you will need to wait 3 minutes before trying again. During this time, 

whenever an attempt is made to log in, the display will read “BLOC”. The default 

password is 1234.

8) CLOSING LIMIT SWITCH PRESSURE Fig. O Ref. A-B

OPENING DIRECTION Fig. J

9) CONNECTION WITH EXPANSION BOARDS AND UNIVERSAL HANDHELD 

PROGRAMMER (Fig. N) 

Refer to specific manual.

10) U-LINK OPTIONAL MODULES

Refer to the U-link instructions for the modules. 

The use of some models causes lowered radio capacity. Adjust the system using an 

appropriate antenna tuned to 433MHxz.

11) RESTORING FACTORY SETTINGS FIg.P

WARNING: 

this operation will restore the control unit’s factory settings and all 

transmitters stored in its memory will be deleted.

WARNING! Incorrect settings can result in damage to property and injury to 

people and animals. 

- Cut off power to the board (Fig.P ref.1)

- Open the Stop input and press the - and OK keys together (Fig.P ref.2)

- Switch on the board’s power (Fig.P ref.3)

- The display will read RST; confirm within 3 sec. by pressing the OK key (Fig.P ref.4)

- Wait for the procedure to finish (Fig.P ref.5)

- Procedure finished (Fig.P ref.6)

WARNING!  Incorrect settings can result in damage to property and injury to people 

and animals.  

WARNING: Check that the force of impact measured at the points 

provided for by standard EN 12445 is lower than the value laid down 

by standard EN 12453.

Impact forces can be reduced by using deformable edges.

For best results, it is advisable to run the autoset function with the motors idle (i.e. 

not overheated by a considerable number of consecutive operations).

Содержание VIRGO SMART BT A

Страница 1: ...IRE AUTOMATIZACIONES A BRAZO PARA PORTONES CON BATIENTE AUTOMATIZA ES DE BRA O PARA PORT ES DE BATENTE Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully...

Страница 2: ...an eye on the roller shutter while it is moving and keep peopleawayuntilithasclosedcompletely Exercise care when activating the release if such a device is fitted as an open shutter could drop quickly...

Страница 3: ...E E click click 180 18 0 S ON OFF MANUALE D USO MANOVRA DI EMERGENZA USER GUIDE EMERGENCY OPERATION MANUEL D UTILISATION DE LA MANOEUVRE D URGENCE BEDIENUNGSHANDBUCH NOTFALLMAN VER MANUAL DE USO MANI...

Страница 4: ...ekeyoperated must be installed at a height of at least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light flashing light in a visible position and also at...

Страница 5: ...PA OL PORTUGU S DEUTSCH ITALIANO INSTALLAZIONE VELOCE QUICK INSTALLATION INSTALLATION RAPIDE SCHNELLINSTALLATION INSTALACI N R PIDA INSTALA O R PIDA A B 188 292 224 5 x 0 7 5 m m 2 5 x 0 7 5 m m 2 2 x...

Страница 6: ...115 118 50 90 92 95 100 102 105 107 110 110 110 115 115 60 90 92 95 100 102 105 107 107 110 110 115 115 70 90 92 95 97 100 102 107 107 110 110 112 115 80 90 92 95 97 100 102 105 107 107 110 112 112 9...

Страница 7: ...B 62 min 300 1 2 3 4 D E 25 MAX D o or ou oder o ou P D L F MAX M10 MAX L 25 mm Destra Right Droitea Rechts Derecha Direita Sinistra Left Gauche Links Izquierda Esquerda Non in dotazione Not supplied...

Страница 8: ...M8 85 MAX M6 8 H Non in dotazione Not supplied Ne sont pas fournis Nicht im lieferum No asignadas en el equipamiento base N o fornecidas Non in dotazione Not supplied Ne sont pas fournis Nicht im lief...

Страница 9: ...LEKTRISCHE VERRIEGELUNG aus Sicherheitsgr nden empfohlen FECHADURA EL TRICA recomendada por raz es de seguran a FECHADURA EL TRICA recomendada por raz es de seguran a 1x P 2x R 1x P 2x R 1x P 2x R 2x...

Страница 10: ...a Pot ncia m xima 110W Ciclo massimo Maximum cycle Cycle maximum Max Zyklus Ciclo m ximo Ciclo m ximo 20 cycle h Con logica inversione direzione di apertura 000 DIR INT With reverse logic opening dire...

Страница 11: ...otoc lulas no comprobadas para fotoc lulas comproabdas v anse las siguientes p ginas Conex o de 1 par de fotoc lulas n o verificadas para fotoc lulas verificadas consultar p ginas seguintes Alimentazi...

Страница 12: ...em remotes end o o MIN 1 MAX 3 AUTO OPEN AUTO CLOSE Exit Men Confirm Switch on display Scroll up Scroll down ar automatic operation residential sr semiautomatic operation residential ac automatic oper...

Страница 13: ...6 1 2 1 2 3 4 5 52 50 TX1 RX1 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 T...

Страница 14: ...8 rst8 8888 1 2 3 4 6 5 3s UNIDA THALIA N O P ON OFF PROGRAMMATORE PALMARE UNIVERSALE UNIVERSAL PALMTOP PROGRAMMER PROGRAMMATEUR DE POCHE UNIVERSEL UNIVERSELLEN PALMTOP PROGRAMMIERER PROGRAMADOR DE BO...

Страница 15: ...ge test failed Check safety edge connection and or logic settings ER03 Opening photocell test failed Check photocell connection and or parameter logic setting ER04 Closing photocell test failed Check...

Страница 16: ...racket F to the leaf Insert the lever arm L into the output shaft of the gearmotor and secure it using the special pin P and the self locking nut D Release the actuator by operating the release lever...

Страница 17: ...l connecting cables must be kept far enough away from the dissipater WARNING For connection to the mains power supply use a multicore cable with a cross sectional area of at least 3x1 5mm2 of the kind...

Страница 18: ...not used leave jumper inserted SAFE logic 1 Input configured as Phot test tested photocell fig M ref 2 Switches photocell testing on at start of operation When beam is broken photocells are active du...

Страница 19: ...emand wherenecessary editthemasdescribed in the programming section WARNING Check that the force of impact measured at the points provided for by standard EN 12445 is lower than the value laid down by...

Страница 20: ...ening closing cycle is required WARNING When the display reads SET obstacle detection is not active Maintenance 0 250 0 Programming number of operations for maintenan ce threshold in hundreds Allows y...

Страница 21: ...t measured at the points provided for by standard EN 12445 is lower than the value laid down by standard EN 12453 If in doubt use auxiliary safety devices This feature is useful when dealing with inst...

Страница 22: ...ess memorizing of transmitters is disabled C Wireless automatic addition of clones is disabled D Wireless automatic addition of Replays is disabled E The option of editing the board s parameters via t...

Страница 23: ...igured as Stair Light EXPO2 Configuration of EXPO2 output on input output expansion board 6 7 11 5 Output configured as Alarm 6 Output configured as Flashing light 7 Output configured as Latch 8 Outpu...

Отзывы: