INSTALLATION MANUAL
TABLE “B” - LOGIC MENU - (
logic
)
Logic
Deinition
Default
Cross out
setting
used
Optional extras
MOTOR TYPE
Motor type
(Set the type of motor
connected to the
board).
0
0
Motors not active
1
ELI 250 BT
2
PHOBOS BT
3
IGEA BT
4
LUX BT
5
LUX G BT
6
SUB BT
TCA
Automatic Closing
Time
0
0
Logic not enabled
1
Switches automatic closing on
FAST CLS.
Fast closing
0
0
Logic not enabled
1
Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse.
STEP-BY-STEP
MOVEMNT
Step-by-step
movement
0
0
Inputs conigured as Start E, Start I,
Ped operate with 4-step logic.
step-by-step mov.
2 STEP
3 STEP
4 STEP
CLOSED
OPENS
OPENS
OPENS
DURING
CLOSING
STOPS
OPEN
CLOSES
CLOSES
CLOSES
DURING
OPENING
STOP + TCA STOP + TCA
AFTER STOP
OPENS
OPENS
OPENS
1
Inputs conigured as Start E, Start I,
Ped operate with 3-step logic. Pulse
during closing reverses movement.
2
Inputs conigured as Start E, Start I,
Ped operate with 2-step logic. Move-
ment reverses with each pulse.
PRE-ALARM
Pre-alarm
0
0
The lashing light comes on at the same time as the motor(s) start.
1
The lashing light comes on approx. 3 seconds before the motor(s) start.
Parameter
min.
max.
Default
Personal
Deinition
Description
OP.FORCE
1
99
50
Leaf force during
opening [%]
Force exerted by leaf/leaves during opening. This is the percentage of force
delivered, beyond the force stored during the autoset cycle (and subsequently
updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It afects impact force directly: make sure that current
safety requirements are met with the set value (*). Install anti-
crush safety devices where necessary (**).
CLS.FORCE
1
99
50
Leaf force during
closing [%]
Force exerted by leaf/leaves during closing. This is the percentage of
force delivered, beyond the force stored during the autoset cycle (and
subsequently updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It afects impact force directly: make sure that current
safety requirements are met with the set value (*). Install anti-
crush safety devices where necessary (**).
OP SPEED
15
99
99
Opening speed [%}
Percentage of maximum speed that can be reached by motor(s) during
opening.
WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING: when the
display reads "SET", obstacle detection is not active.
CL SPEED
15
99
99
Closing speed [%]
Percentage of maximum speed that can be reached by motor(s) during
closing.
WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING: when the
display reads "SET", obstacle detection is not active.
SLOW SPEED
15
99
25
Slow-down speed [%]
Opening and closing speed of motor(s) during slow-down stage, given as a
percentage of maximum running speed.
WARNING: Once the parameter has
been edited, a complete uninterrupted opening-closing cycle is required.
WARNING: When the display reads “”SET””, obstacle detection is not active.
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
(**) Impact forces can be reduced by using deformable edges.