INSTALLATION MANUAL
Logic
Definition
Default
Cross out
setting
used
Optional extras
PRESS SWC
Closing limit switch
pressure
0
0
Movement is stopped only when the closing limit switch trips: in this case, the tripping of the closing
limit switch must be adjusted accurately (Fig.g Ref.B).
1
Use when there is a mechanical stop in closed position.
This function allows leaves to press against the mechanical stop without the Amperostop sensor
interpreting this as an obstacle.
Thus the rod continues its stroke for a few seconds after meeting the closing limit switch or as far as
the mechanical stop. In this way, the leaves come to rest perfectly against the stop by allowing the
closing limit switches to trip slightly earlier (Fig.g Ref.A).
ICE
Ice feature
0
0
The Amperostop safety trip threshold stays at the same set value.
1
The controller automatically adjusts the obstacle alarm trip threshold at each start up.
Check that the force of impact measured at the points provided for by standard EN 12445 is lower
than the value laid down by standard EN 12453. If in doubt, use auxiliary safety devices.
This feature is useful when dealing with installations running at low temperatures.
WARNINg: once this feature has been activated, you will need to perform an autoset opening and
closing cycle.
1 MOT.ON
1 motor active
0
0
Both motors active (2 leaves).
1
Only motor 1 active (1 leaf).
OPEN IN OTHER
DIRECT.
Open in other
direction
0
0
Standard operating mode (See Fig.g Ref. C).
1
Opens in other direction to standard operating mode (See Fig. g Ref.D)
SAFE 1
Configuration of
safety input SAFE 1.
72
0
0
Input configured as Phot (photocell).
1
Input configured as Phot test (tested photocell).
2
Input configured as Phot op (photocell active during opening only).
3
Input configured as Phot op test (tested photocell active during opening only).
SAFE 2
Configuration of
safety input SAFE 2.
74
6
4
Input configured as Phot cl (photocell active during closing only).
5
Input configured as Phot cl test (tested photocell active during closing only).
6
Input configured as Bar, safety edge.
7
Input configured as Bar, tested safety edge.
8
Input configured as Bar 8k2.
SAFE 3
Configuration of
safety input SAFE 3.
77
2
0
Input configured as Phot (photocell).
1
Input configured as Phot test (tested photocell).
SAFE 4
Configuration of
safety input SAFE 4.
79
4
2
Input configured as Phot op (photocell active during opening only).
3
Input configured as Phot op test (tested photocell active during opening only).
SAFE 5
Configuration of
safety input SAFE 4.
79
0
4
Input configured as Phot cl (photocell active during closing only).
5
Input configured as Phot cl test (tested photocell active during closing only).
SAFE 6
Configuration of
safety input SAFE 6.
84
6
6
Input configured as Bar, safety edge.
7
Input configured as Bar, tested safety edge.
IC 1
Configuration of
command input IC 1.
61
0
0
Input configured as Start E.
1
Input configured as Start I.
IC 2
Configuration of
command input IC 2.
62
4
2
Input configured as Open.
3
Input configured as Close.
IC 3
Configuration of
command input IC 3.
64
2
4
Input configured as Ped.
5
Input configured as Timer.
IC 4
Configuration of
command input IC 4.
65
3
6
Input configured as Timer Pedestrian.
36 -
THALIA P