D812958 00100_03
40
- RIGEL 6
INSTALLATION MANUAL
2) GENERAL INFORMATION
The
RIGEL 6
control panel comes with standard factory settings. Any change
must be made using the programmer with built-in display or universal handheld
programmer. The Control unit completely supports the EELINK protocol.
Its main features are:
- Check of 1 or 2 single-phase motors fitted with thermostat
- Control of 1 or 2 single phase motors
Note: 2 motors of the same type must be used.
- Opening/closing limit switch control inputs, separate for each motor
- Separate inputs for safety devices
- Time band management
- Integrated obstacle detection
- Motor pre-heating with integrated sensor reading
- Adjustable electrodynamic braking
- Approach speed slow-down
- Built-in radio receiver rolling code with transmitter cloning.
The board has a terminal strip of the removable kind to make maintenance
or replacement easier. It comes with a series of prewired jumpers to make the
installer’s job on site easier.
The jumpers concern terminals: 41-42, 41-43, 41-44, 41-45, 70-71, 70-72,
70-74, 76-77, 76-79, 81-82, 81-84. If the above-mentioned terminals are
being used, remove the relevant jumpers.
TESTING
The
RIGEL 6
panel controls (checks) the run relays, triacs and safety devices (pho-
tocells and edges), before performing each opening and closing cycle.
If there is a malfunction, make sure that the connected devices are working
properly and check the wiring.
ATTENTION!
if the leaf is installed in a public area or if an automatic operating
mode is enabled, we recommend a pair of photocells is installed at a height of 5
cm together with another pair at a height of 40-50 cm. Automatic mode means any
control not voluntarily activated by the user (example: TCA function, chrono, etc.)
3) TECHNICAL SPECIFICATIONS
Power supply
110-120V 50/60Hz
220-230V 50/60Hz
Low voltage/mains insulation > 2MOhm 500V
Dielectric rigidity
mains/LV 3750V~ for 1 minute
Accessories power supply
24V~ (demand max. 1A)
24V~safe
AUX 0
Powered contact
110-120 / 220-230 V~
N.O. (80W MAX)
AUX0+
AUX1+
AUX2=
80W MAX
AUX 1
Powered contact
110-120 / 220-230 V~
N.O. (80W MAX)
AUX 2
NO contact
(MAX 110-120V~ 80W)
(MAX 220-230V~ 80W)
AUX 3
NO contact (Max 24V~) 10W MAX
LOCK
Output for 12V sole-
noid lock:
10W MAX
Dimensions
see
Fig. B
Fuses
see
Fig. C
N° of combinations
4 billion
Max.n° of transmitters that
can be memorized
63
Use cycle
continuous
continuous
1 min. ON/
2 min. OFF
1 min. ON/
2 min. OFF
Operating
temperature range
-20°C/+50°C
-20°C/+55°C
-20°C/+50°C
-20°C/+55°C
Maximum motor
power 220-230V
2x375 W
1x750 W
2x250 W
1x500 W
2x650 W
1x750 W
2x500 W
1x750 W
Maximum motor
power110-120V
2x195 W
1x390 W
(110-120V) M1+M2+AUX0+AUX1+AUX2+AUX3+LOCK= 680W MAX @ T=+50°C
(220-230V) M1+M2+AUX0+AUX1+AUX2+AUX3+LOCK= 1300W MAX @ T=+50°C
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
4) TUBE ARRANGEMENT Fi g. A
Terminal
Definition
Description
Po
w
er
supply
L
LINE
Single-phase power supply
110-120V 50/60Hz
220-230V 50/60Hz
N
NEUTRAL
GND
EARTH
M
ot
or
10
MOT1 RUN
Connection motor 1. Time lag during closing.
11
MOT 1 COM
12
MOT1 RUN
14
MOT2 RUN
Connection motor 2. Time lag during opening.
Note: if “
1 MOT.ON
.” = 1 do not connect any wires to terminals 14-15-16
15
MOT 2 COM
16
MOT2 RUN
Au
x
20
110-120 / 220-230 V~
POWERED CONTACT
AUX 0 configurable output - Default setting FLASHING LIGHT.
MONOSTABLE RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/
GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTE-
NANCE / GATE STATUS / BISTABLE RADIO CHANNEL / TIMED RADIO CHANNEL.
Refer to “AUX output configuration” table.
21
22
110-120 / 220-230 V~
POWERED CONTACT
AUX 1 configurable output - Default setting ZONE LIGHT Output.
MONOSTABLE RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/
GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTE-
NANCE / GATE STATUS / BISTABLE RADIO CHANNEL / TIMED RADIO CHANNEL.
Refer to “AUX output configuration” table.
23
24
AUX 2 - FREE CONTACT
(N.O.)
AUX 2 configurable output - Default setting SCA GATE OPEN LIGHT Output.
MONOSTABLE RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/
GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTE-
NANCE / GATE STATUS / BISTABLE RADIO CHANNEL / TIMED RADIO CHANNEL.
Refer to “AUX output configuration” table.
25
26
AUX 3 - FREE CONTACT
(N.O.)
AUX 3 configurable output - Default setting MONOSTABLE RADIO CHANNEL Output.
MONOSTABLE RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/
GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTE-
NANCE / GATE STATUS / BISTABLE RADIO CHANNEL / TIMED RADIO CHANNEL.
Refer to “AUX output configuration” table.
27
28
LOCK 12V
Type of lock logic= 0 - 12V
solenoid latch output.
Output activated with a pulse each time gate is opened or closed
(MODEL ECB)
29
Type of lock logic= 1 - 12V
magnetic lock output.
Output activated when gate is closed or closing
Limit swit
ch
40
Not used
41
+ REF SWE
Limit switch common
42
SWC 1
Motor 1 closing limit switch SWC1 (N.C.).
43
SWO 1
Motor 1 opening limit switch SWO1 (N.C.).
44
SWC 2
Motor 2 closing limit switch SWC2 (N.C.).
45
SWO 2
Motor 2 opening limit switch SWO2 (N.C.).
A
cc
essories po
w
er
supply
50
24V-
Accessories power supply output.
51
24V+
52
24 Vsafe+
Tested safety device power supply output (photocell transmitter and safety edge transmitter).
Output active only during operating cycle.
Содержание RIGEL 6