INSTALLATION MANUAL
11.5) DEFAULT MENU (
default
)
Restores the controller’s default factory settings. Following this reset, you will
need to run the AUTOSET function again.
11.6) AUTOSET MENU (
AUTOset
) FIG. G
Enables Motor Torque to be set automatically along with relevant slow-down.
Before running the AUTOSET function, adjust slow-down speed (Fig. F).
WARNING! The AUTOSET operation must be performed starting from the
closing limit switch position. If you attempt to run the AUTOSET function
in any other position, the following error message will appear: “
o
” and the
operation will not be performed.
WARNING!! The AUTOSET operation must be performed only once you have
checked that the leaf is moving accurately (opening/closing) and that the
limit switches are tripping correctly.
During this stage, it is important to avoid breaking the photocells’ beams and
not to use the START, STOP and commands or the display.
WARNING! While the AUTOSET function is running, the obstacle detection
function is not active. Consequently, the installer must monitor the auto-
mated system’s movements and keep people and property out of range of the
automated system.
When using buffer batteries, the AUTOSET function must be run with the control
panel running off mains power.
12.1) TABLE A: PARAMETERS MENU (
PARA
)
Parameter
min.
max.
default
personal Definition
Description
TCA
0 sec.
120 sec.
120 sec.
Automatic Closing Time
Pause time before automatic closing.
slow. speed
1%
99%
50%
Slow-down speed
Set slow-down speed, choosing a percentage value of the ma-
ximum speed.
t. start
30
250
150
Inrush time
Inrush time at each motor startup, during which time obstacle
detection is not active.
Given in hundredths of a second (150=1.5 s).
op.t.slow
1%
99%
25%
Opening motor torque
Sets motor’s operating force during opening at normal speed.
cls.t
1%
99%
25%
Closing motor torque
Sets motor’s operating force during closing at normal speed.
Zone
0
127
0
Zone
Serial connection address.
Set the Zone number in the range 0 to 127. The zone number
allows you to create groups of automated devices, each of which
answers to the Zone Master. Each zone can have only one Master.
The Master of zone 0 also controls the Masters and Slaves of the
other zones.
op.dist slow
(special par. 6)
0
99%
20%
Opening slow-down
distance
Set opening slow-down distance, choosing a percentage value
of the overhead door’s whole travel.
cl.dist slow
(special par. 7)
Closing slow-down
distance
Set closing slow-down distance, choosing a percentage value of
the overhead door’s whole travel.
12.2) TABLE B: LOGIC MENU (
logic
)
Logic
Default Definition
Cross out
setting
used
Description
TCA
OFF
Automatic
Closing Time
ON
Switches automatic closing on.
OFF
Switches automatic closing off.
ibl open
OFF
Block Pulses
opening
ON
The start pulse has no effect during opening.
OFF
The start pulse has effect during opening or closing.
ibl tca
OFF
Block Pulses TCA
ON
The start pulse has no effect during TCA pause.
OFF
The start pulse has effect during TCA pause.
3 step
OFF
3 step/4 step
ON
Switches to 3-step logic. A start pulse has the following effects:
door closed: opens
during opening: stops and switches on TCA (if configured).
door open: closes
during closing: stops and opens again
OFF
Switches to 4-step logic. A start pulse has the following effects:
door closed: opens
during opening: stops and switches on TCA (if configured)
door open: closes
during closing: stops and does not switch on tca (stop)
after stop: opens
pre-alar
OFF
Pre-alarm
ON
The flashing light comes on approx. 3 seconds before the motors start.
OFF
The flashing light comes on at the same time as the motors start.
photoc.open
OFF
Photocells
during opening
ON
When beam is broken, operation of the photocell is switched off during opening. During closing,
movement is reversed immediately.
OFF
When beam is broken, photocells are active during both opening and closing. When beam is broken
during closing, movement is reversed only once the photocell is cleared.
fast cls.
OFF
Fast closing
ON
Closes 3s after the photocells are cleared before waiting for the set TCA to elapse.
OFF
Command not enabled.
test phot
OFF
Photocell test
ON
Switches photocell testing on
OFF
Switches photocell testing off
If disabled (OFF), it inhibits the photocell testing function, enabling connection of devices not
equipped with supplementary test contacts.
aster
OFF
Master/slave
ON
Control panel is set up as the Master unit in a centralized serial connection system.
WARNING: the control panel set as the master must be the first in the series.
OFF
Control panel is set up as a Slave unit in a centralized serial connection system.
HYDRA N -
15
D811675 00100_02