Order no. 7590 40 02

Operation instructions

IR configuration hand-held
transmitter for presence
detector

Berker GmbH & Co. KG

Klagebach 38  

58579 Schalksmühle/Germany

Telefon: + 49 (0) 23 55/90 5-0

Telefax: + 49 (0) 23 55/90 5-111

www.berker.com

09/2011

97-75904-002

Warranty

We reserve the right to make technical and 
formal changes to the product in the interest of
technical progress.

Our products are under guarantee within the
scope of the statutory provisions. 

If you have a warranty claim, please contact
the point of sale or ship the device postage
free with a description of the fault to the
appropriate regional representative. 

GB

The remote control allows the user to set or
modify settings on the presence detectors
1701 06, 1701 07, 7524 10 01, 7524 10 02.
when the potentiometer is on "auto test". It
allows single and multiple settings. 
The SET key is used to send the IR messages
to the occupancy sensors. Multiple settings
can be stored in Memo 1 and Memo 2 and
recalled to set several devices.

Single setting

Example:
do a reset. 

Multiple settings

Define the parameters to be changed and
press SET to send. 

Example: for 25 minutes and corridor use,
press 20', 5' and corridor.

In the case of 2 opposite states the green LED
denotes ON and the red LED denotes OFF
(except Presence/ Absence).

When no function is selected all LED’s are

OFF.

+

+

+

+

Technical specifications 

Power supply : 1x 3V CR2032
Shelf life of battery : 2,5 years
Protection index : IP 30

The acknowledgment LED
blinks during the sending
of the IR message.

Use 

Battery replacement 

-

LED

Description 

Key

Meaning

Indication

Function

Presence

Green LED on

Presence on (automatic mode).

Absence 

Red LED on

Absence on (semi automatic mode).

Power Up

Green LED on

The light is automatically switched ON for   
30 s after power up.

Red LED on

During warm up phase, the light output is off.

Reset

LED on

To return to factory settings 
(Lux = 400, time = 20min., presence on,
power up off and cell active).

Test

LED on

To validate the detection area

Time

LED on

To set the time. 
It is possible to add times 
Ex.: press 2’ and 5’, time value is 7’.

Day level 
1000 Lux

LED on

To set the value on 1000 Lux

Learn

LED on

To learn the current Lux level

Corridor
200 Lux

LED on

To set the value on 200 Lux

Office
400 Lux

LED on

To set the value on 400 Lux

Lux +

LED on

To increase the Lux level (+100)

Lux –

LED on

To decrease the Lux level (-100)

Active cell

Green LED on

The light is continuously measured.

Passive cell

Red LED on

The product doesn't switch the light off even
if the ambient luminosity is sufficient.

Settings available

Presence detectors 

1701 06
1701 07
7524 10 01
7524 10 02 

Key

Meaning

Indication

Function

Press

LED is on until a setting is changed.

To load/unload Memo 1.

Long press 

LED is on during 5s., then blinks until release press.
After release, the LED goes off in case of setting
change.

To save the current setting as Memo 1.

Press

LED is on until a setting is changed.

To load/unload Memo 2.

Long press 

LED is on during 5s., then blinks until release press.
After release, the LED goes off in case of setting
change.

To save the current setting as Memo 2.

Short press (<5s)

LED flashes.

To send an IR message of the current setting.

Long press (>5s but <10s)
only available if no setting
active.

LED blinks until release press.

To toggle addressing mode on DALI/DSI
detectors (1701 07, 7524 10 02).

Memo and SET keys

Æ

§