background image

Power Up

A parameter of the detector allows the choice of state for 

the lighting after power up (mains return).  

During warm up phase, the green LED blinks. 

In the Power up ON state the lighting will automatically 

be energised when mains power is initially supplied or 

returned to the sensor.  

In the Power up OFF state the lighting will not  

be energised and the sensor will not operate during warm 

up period. 

This parameter is modified using the installer remote 

control 7590 40 02.

POWER UP state :

• 

 ON

 : The light is immediately switched ON for 30s. after 

power up.  

In case of detection, the light (in automatic mode) 

remains on during the time delay; otherwise the light is 

switched off.

• 

 OFF

 :

 The detector switches to the selected mode after 

warm up. 

Active/passive cell
Active cell 

The photocell will inhibit the output from the sensor if the 

ambient light level is sufficient. 

If the sensor detects occupancy whilst the ambient light 

level is below the required Lux level, the lights will be 

activated. However if the ambient light level increases to 

a value where it is above the required Lux level during a 

certain time, the sensor will detect it and switch off the 

light.

Passive cell

The photocell will inhibit the output from the sensor if at 

the time of detection the ambient light level is sufficient. 

In case of detection, if the ambient light level increases, 

the photocell will not turn off the light. 

Action

Einstellungen 

Potentiometer 

Use Auto settings 

(factory) or  

set by the remote 

control or via ETS 

to switch the light 

automatically for a 

defined time.

Auto Settings

Put the Lux potentiometer on “auto test”.  

The settings are predefined :

Lux = 400,  

time = 20min, 

q

 : test mode for 2min.

Remote control settings 7590 40 02

(manual settings inhibited). 

auto

test

on

lux

auto

test

on

lux

1 min

1 h

20 min 

Adr

1 min

1 h

20 min 

Adr

auto

test

on

lux

auto

test

on

lux

Automatically switch on 

the light for a defined 

time.

Installer settings

auto

test

on

lux

auto

test

on

lux

1 min

1 h

20 min 

Adr

1 min

1 h

20 min 

Adr

auto

test

on

lux

auto

test

on

lux

Test and validate the 

detection zone.

Test mode 

Move the potentiometer 

1

 to “auto test”.  

On this position, the remote control 7590 40 02 can 

be used.

auto

test

on

lux

auto

test

on

lux

1 min

1 h

20 min 

Adr

1 min

1 h

20 min 

Adr

auto

test

on

lux

auto

test

on

lux

Move the 

potentiometer 2 to 

«Adr.» or use remote 

control 7590 40 02 

(long push > 5s. on the 

SET key).

Move the potentiometer 

2

 to «Adr.» or use remote 

control 7590 40 02 (long push > 5s. on the SET key).

auto

test

on

lux

auto

test

on

lux

1 min

1 h

20 min 

Adr

1 min

1 h

20 min 

Adr

auto

test

on

lux

auto

test

on

lux

Product description and operation principles

Occupancy sensors 75241003 are presence detectors 

designed to detect low amplitude movements (e.g. 

person sitting at a desk).

Detection is by means of a pyro-electric sensor located 

under detection lens.

The occupancy sensor measures the  

brightness in the room on a continuous basis and 

compares it to the level preset on the potentiometer 

(or by means of the remote control 7590 40 02) or ETS 

parameter. 

These products are part of the KNX installation system.

Configuration

•  S-mode ETS : Application software “IR  

presence detector V1.1”. Database and  

description available from manufacturer.

Physical addressing

Set potentiometer 

2

 to «Adr.» position, the red LED 

switches on. To exit this state, move the potentiometer to 

another value.

Features

•  One direct lighting control channel (relay  

output of the product).

•  One lighting control channel on the KNX bus.

•  Control of presence/ absence mode.

•  Time and brightness adjustment via ETS or remote 

control 7590 40 02.

•  Area linking : the occupancy sensor in a room can 

switch the light on in the corridor beside or the 

opposite.

•  2 monitoring channels (work independently of the light 

measurement).

Settings

The Lux threshold and time out period can be set with the 

potentiometers, by using the installer IR remote control 

(7590 40 02) or via ETS.

Test Mode

This mode makes it possible to validate the 

detection area. To select this mode, set the potentiometer 

1

 to the position «auto test». 

The green or red LED behind the lens is on for  

2 seconds after detection.  

The red LED indicates that the light level measured is 

lower than current setting.  

If the green LED is on, the light level measured is higher 

than current setting.

There is a time out during 2 minutes which is reactivated 

after each detection. 

The output (local relay and remote KNX load) is  switched 

during 2s. after each detection.

It is also possible to use the remote control  

7590 40 02 to set the detector in test mode.

Functional modes

The detector has 2 different modes.

-  Presence detection (automatic).

-  Absence detection (semi-automatic)

The power up and cell operation can be set for each 

mode.   

A KNX pushbutton linked to the product makes it possible 

to reverse the lighting output state. 

This state is maintained for the time period set by the 

potentiometer 

2

 or the remote control  

7590 40 02.

Automatic mode (presence detection)

In this mode the light is controlled by motion in the 

detection area and ambient light levels. 

If presence is detected whilst the light levels are below 

the required Lux level, the sensor is  

activated and keeps the light on whilst there is still 

occupancy and for the time out period afterwards. 

Once the sensor has deactivated the lights, it will require 

a new occupancy whilst the ambient light levels are below 

the required Lux levels to activate the lights again.

This mode can be changed via the IR remote control 7590 

40 02 (default mode is presence detection : automatic).

Semi automatic mode (absence detection)

The sensor needs to be activated by a KNX  

pushbutton or a user remote control input.  

Once the sensor is activated, it will hold the lights on 

whilst there is still occupancy and for the time out period 

afterwards.  

Once the sensor has deactivated the lights, it will require 

another input from the wallswitch or the remote control to 

switch the lights on. 

Factory settings

Luminosity threshold

400 lux

Lighting time

20 Min.

Mode

Presence

Power Up

OFF

Active cell (Luminosity Cell)

ON

6LE000240B

Order no. 7524 10 03

KNX IR presence detector

Berker GmbH & Co. KG

Klagebach  38  

58579 Schalksmühle/Germany

Telefon: + 49 (0) 23 55/90 5-0   

Telefax: + 49 (0) 23 55/90 5-111   

www.berker.com

04/2017

97-75241-003

Description

auto

test

on

lux

1 min

1 h

20 min 

Adr

Settings

auto

test

on

lux

1 min

1 h

20 min 

Adr

1 min

1 h

20 min 

Adr

auto

test

lux

on

h

Y

X

Y

h

X

h

x
y

ech40%

Detection areas

h

2,5m 3m

3,5m

x

5m

5m

5m

y

7m

8m

9m

2,5 m

2,5 m

2,5 m

6 m

1 m

Overlap

The light measurement accuracy (Lux) is affected by 

the environment (furniture, ground, walls...). If necessary, 

the level has to be adjusted by potentiometer or remote 

control.

Instances of lighting levels

Position of 

potentiometer

Lux value

approximate *

Application

auto test 

preset

1

200

Corridor

>1 ... 2 <

> 200 ... 400 <

2

400

Offices

>2 ... On <

> 400 ... 1000 <

On

1000

Offices

Remote control for settings

The installer remote control 7590 40 02

can be used to set the following 

features if the potentiometer is set on «auto test» :

-  Lux levels  

(

)

-  Time (

)

-  Absence/presence detection 

- Power up behaviour 

-  Active/passive cell 

.

- Direct/ indirect lighting

Override remote control

The remote control 7590 40 01 allows  

the switching ON or OFF of the light 

(

+

 

+

) The 7590 40 02 allows the same 

functionality as the wallswitch.

-

+

M

-

+

M

-

+

M

z

m

Brightness measurement sensor

(under the detection lens)

Detection lens

Fixing springs

LED’s for testing ,  

KNX addressing and  

IR acknowledgement

IR receiver 

(remote controls)

Potentiometers 

1

 and 

2

IR sensor (detection)

1

2

Technical features
Electrical characteristics

Supply voltage :                              KNX bus 30 V 

s

  SELV

Busline consumption :  

12mA

Functional characteristics

Lighting output operating time :  

1min. 

 1 h

Brightness level : 

 5 

 1000 Lux

Recommended installation height :  

2,5 m 

 3,5m

Detection range :  

Ø 7m  

  

(installed product height : 2.5m) 

Products can be connected in parallel. 

Hole size required :  

60mm

Environment

(See) derating Curve 

 

Storage temperature : 

      -20 °C  

 +60 °C

Class of insulation :  

 II 

  

IK 03 

Index of protection :  

IP41 

Fire resistance :  

650°C

Pollution category:                           

 2                             

 

Overvoltage Category : 

 III

Max. altitude :  

2000m 

Configuration mode : 

 S mode 

Transmission mode :  

TP1

Upstream protection (out 230V~) : 

  circuit breaker 16A

Connection  capacity :

  

  

0.5mm

2

 to 1,5mm

2

 flexible, 

  

0.5mm

2

 to 1,5mm

2

 rigid

Warranty

We reserve the right to make technical and formal changes 

to the product in the interest of technical progress.

Our products are under guarantee within the scope of the 

statutory provisions. 

If you have a warranty claim, please contact the point of 

sale or ship the device postage free with a description of 

the fault to the appropriate regional representative. 

The “y” values are given for lateral 

range. The range may be reduced if 

walking towards the sensor.

q

6LE000240B

1

6LE000240B

2

This device must be installed by a suitably

qualified electrician according to the

installation’s standards.

Correct Disposal of this product (Waste Electrical & Electronic 

Equipment).

(Applicable in the European Union and other European countries 

with separate collection systems).

This marking shown on the waste or its literature indicates that it 

should not be disposed with other household wasted at the end 

of its working life. To prevent possible harm to the environment or 

human health from uncontrolled waste disposal, please separate this product 

from other types of wastes and recycle it responsibly to promote the sustainable 

reuse of material resources.

Household users should contact either the retailer where they purchased this 

product, or their local government office, for details of where and how they can 

take this device for environmentally safe recycling.

Business users should contact their supplier and check the terms and condi-

tions of the purchase contract. This product should not be mixed with other 

commercial wastes of disposal.

 Usable in all Europe 

å

 and in Switzerland

16A

10A

Temperature (°C)

Current (A)

40°C

45°C

Содержание 7524 10 03

Страница 1: ...ined for the time period set by the potentiometer 2 or the remote control 7590 40 02 Automatic mode presence detection In this mode the light is controlled by motion in the detection area and ambient light levels If presence is detected whilst the light levels are below the required Lux level the sensor is activated and keeps the light on whilst there is still occupancy and for the time out period...

Страница 2: ...ined for the time period set by the potentiometer 2 or the remote control 7590 40 02 Automatic mode presence detection In this mode the light is controlled by motion in the detection area and ambient light levels If presence is detected whilst the light levels are below the required Lux level the sensor is activated and keeps the light on whilst there is still occupancy and for the time out period...

Страница 3: ...tąpi po kolejnym wykryciu obecności gdy poziom światła otoczenia będzie poniżej wymaganego natężenia oświetlenia Ten tryb pracy można zmienić za pomocą zdalnego sterownika na podczerwień 7590 40 02 domyślny tryb wykrywania obecności automatyczne Tryb półautomatyczny wykrywanie nieobecności Czujnik uaktywnia się przyciskiem KNX lub zdalnym sterownikiem lub zdalnym sterownikiem użytkownika Po aktywa...

Страница 4: ...tąpi po kolejnym wykryciu obecności gdy poziom światła otoczenia będzie poniżej wymaganego natężenia oświetlenia Ten tryb pracy można zmienić za pomocą zdalnego sterownika na podczerwień 7590 40 02 domyślny tryb wykrywania obecności automatyczne Tryb półautomatyczny wykrywanie nieobecności Czujnik uaktywnia się przyciskiem KNX lub zdalnym sterownikiem lub zdalnym sterownikiem użytkownika Po aktywa...

Отзывы: