USER MANUAL 1.2 | B-FORTIS CC-PRIME SERIES
Berghof Automation GmbH | Arbachtalstrasse 26 | 72800 Eningen | www.berghof-automation.com
33
1,000
1,000 ms (1 s)
250 s
If filtering is active, an average is calculated for the set time range. However a value is still issued
during the sampling rate interval. For example, if the filter is set to 1,000, the average of the
measurements for the previous 1,000 ms / 1,000 measurements is issued each millisecond (or, in
the case of operating mode AI-PT, the average for the last 250 ms / 1,000 measurements).
The filtering can be activated and configured using CODESYS V3. The sampling rate is constant.
It can only be filtered with a whole multiple of the sampling rate.
Operating modes for the analogue inputs
HINWEIS
Damage to channel
High voltages can damage analogue channels, stopping them from working correctly.
Ensure the input voltage does not exceed ±30 V.
Operating mode: voltage input AI (U)
Feature
Value
Description
Connections per
input
–
AI (U/T) and AGND or AI (U) and AGND;
connect screening with AGND.
Measuring range
–10 to +10 V
–
Input impedance in
signal range
100 kΩ
between AI (U/T) and AGND or
between AI (U) and AGND
Max. errors at 25°C
±0.25% (±50 mV)
–
Temperature
coefficient
±40 ppm/K
(±0.4 mV/K)
–
Digital resolution
24 bit
–
Data format in
user program
32 bit real
(floating-point number) in millivolts (mV)
Maximum
permissible
permanent overload
Max. ±30 V
compared to AGND
±30 V = max. voltage on AI channel
Output of digital
value in case of
overload
–
If a voltage of ±10 V is applied to an AI (U), a
plausible value is still given up to approx.
±15 V. The specified accuracy is only valid for
the range
–10 to +10 V.
From a voltage of ±16 V, the values are
distorted considerably and from +23 V an