Analogue inputs and outputs plugs X4, X5 and X6
Pin
X4
X5
X6
Assignment
14
AO 2
AO 4
AO 6
U; 0
–10 V
Analogue channel wiring
Ensure the following connection requirements are met so as to guarantee the measuring accuracy
of the device:
Use analogue cables with a braided shield.
Separate the laying of analogue cables and power cables. Where required, install metallic
shielding in cable channels.
Earth the screen at the place where it enters the control cabinet.
Connect the screen close and directly with AGND.
Data of the analogue inputs
Data of the analogue inputs
Feature
Value
Description
Cable length
max. 30 m
Only valid for unshielded connection cables
Cables over 30 m in length must be shielded
Modulation method
Delta-sigma
modulation
–
Shared points
between the
channels
AGND reference
ground
–
Calibration
frequency
12 months
Maintenance of accuracy class
Clamp arrangement
Shielding on com-
mon AGND pins
–
Sampling
duration/rate for
measuring values
1 ms
A reading is taken from each input channel
every millisecond, regardless of how many
channels are actually in operation.
Sampling rate
Operating mode AI-
PT
250 ms
In operating mode AI-PT, calculations are
carried out after the millisecond sampling rate. A
new value is available in the user program every
250 ms.
Digital filtering
Possible
filter settings
Time range for averaging
Time range for averaging
Operating mode AI-PT
10
10 ms
2.5 s
100
100 ms
25 s