5.3.4. Analogue inputs and outputs (AIO)(not for S06)
The CC-Prime has up to 12 analogue inputs (AI) and 6 analogue outputs (AO) on plugs X4, X5
and X6. The layout of the I/O is identical on all 3 plugs.
The following counterpieces have been tested for the SC-SMT 3.81 (Weidmüller) plug-in
connector and are approved for use with the ECC22XX:
Weidmüller BCZ 3.81/14/180 (F, LH, LR)
Weidmüller BCF 3.81/14/180 (F, LH, LR)
Phoenix FK-MCP 1,5/14-ST-3.81-LR
Fig. 12: analogue inputs a.outputs plugs X4, X5 a.X6 (Weidmüller SC-SMT 3.81/14/180 LF 3.2)
Analogue inputs and outputs plugs X4, X5 and X6
Pin
X4
X5
X6
Assignment
1
AI 1
AI 5
AI 9
U/T; ±10 V; PT100/1000
2
AI 1
AI 5
AI 9
I; ±20 mA
3
–
–
–
AGND
4
AI 2
AI 6
AI 10
U; ±10 V
5
AI 2
AI 6
AI 10
I; ±20 mA
6
–
–
–
AGND
7
AI 3
AI 7
AI 11
U/T; ±10 V; PT100/1000
8
AI 3
AI 7
AI 11
I; ±20 mA
9
–
–
–
AGND
10
AI 4
AI 8
AI 12
U; ±10 V
11
AI 4
AI 8
AI 12
I; ±20 mA
12
–
–
–
AGND
13
AO 1
AO 3
AO 5
U; 0
–10 V