USER MANUAL 1.2 | B-FORTIS CC-PRIME SERIES
Berghof Automation GmbH | Arbachtalstrasse 26 | 72800 Eningen | www.berghof-automation.com
27
Digital inputs plug X3
Pin
Label
Assignment
15
I 15
+24 V
16
I 16
+24 V
Data of the the digital inputs
Feature
Value
Description
Cable length
max. 30 m
For unshielded connection cables
Cables over 30 m in length must be shielded
Cable cross-section
in control cabinet
after voltage drop
Only select after voltage drop (there are no
further practical restraints).
Field wiring
according to
regulations and
standards
Comply with all local regulations and the
stipulations of EN 61131-2.
Rated load voltage
24 V DC (SELV)
–
Protection against
reverse polarity
yes
–
Potential isolation
no
–
Status display
yes
One orange LED per input
Fig. 8: Principle circuit diagram input, positive switching