background image

 

 

 

Warning bout forbidden use 

 

 

The compressor must not be used for any other purposes that are non-compliant with its intended use.

 

 

Under no circumstances must the limit operating parameters of the compressor be exceeded and changed - 

refer to section 10 "Technical data".

 

 

To use it for compression of other gases than air, it is required to ob

tain the manufacturer’s consent. The 

above consent must be in written form.

 

 

The compressor must not be used in potentially explosive atmospheres within the meaning of Directive 

2014/34/UE.

 

 

The compressor must not suck any toxic, acid-containing, flammable or explosive gases and vapours.

 

 

Never direct a jet of compressed air at people or animals.

 

 

Safe use of the compressor 

 

 

The compressor must be operated in accordance with all guidelines included in this operating and 

maintenance manual.

 

 

The sucked air must be clean and must not contain any harmful substances.

 

 

The  heated  cooling  air  may  be  used  for  heating  purposes  if  only  its  harmfulness  to  people  and  animals  is 

excluded. Otherwise, it is necessary to provide the appropriate treatment of cooling air.

 

 

Compressed air may only be used for breathing after its appropriate treatment.

 

 

Compressed air not subjected to the appropriate treatment must not be used in production processes in 

which there is contact of air with food.

 

 

The compressor delivered is designed to compress only air.To use it for compression of other gases, it is 

required  to  obtain  the  manufacturer’s  consent.  The  above  consent  must  be  in  written  form.  The 

compressor must not be used for any other purposes that are non-compliant with its intended use. 

 

 

Fulfil the obligation to register the compressor air receiver in the Office of Technical Inspection 
(UDT).The compressor documentation is accompanied by the set of the required documentation 
of the air receiver (if applicable) and safety valve. 

 

 

1.3. Qualification requirements for operation of the compressor. 

 

The personnel who installs, operates and maintains the compressor should have the appropriate 
education  and  qualifications  enabling  safe  operation  of  electrotechnical  and  electrical 
equipment. 

 

Installation,  operation  and  maintenance  of  the  compressor  may  only  be  carried  out  by  the 
persons  who  are  familiar  with  this  operating  and  maintenance  manual,  follow  instructions 
included in it, know safety regulations and recognised technical rules. 

 

1.4. Operation 

While operating the compressor: 

 

-

 

Observe the instructions provided in the Operating and Maintenance Manual and Warranty Book. 

 

-

 

Follow  the  periodic  inspection  schedule  during  both  warranty  period  and  after  its  completion. 
Regular performance of periodic inspections is necessary to ensure the required reliability and life 
of the BERG equipment. The inspections performed according the schedule reduce the number of 
repairs and their cost. 

 

-

 

The  technical  and  operating  inspections  should  be  carried  out  in  accordance  with  the  schedule 

and conditions by the factory service or authorised service, using the manufacturer’s consumables 

and spare parts. 

 

-

 

During the warranty period, use only the manufacturer’s consumables and spare parts.

 

 

 

The detailed list of maintenance operations can be found in the "Maintenance and 
inspections" section. 

 

Содержание KOMPBERG ZXF132

Страница 1: ...OPERATING AND MAINTENANCE MANUAL Oil free screw compressor KOMPBERG ZXF132...

Страница 2: ...h the choice you have made and the cooperation you started with us Our compressors are machines of top quality which is the guarantee for a long years and reliable performance Our sales and service st...

Страница 3: ...ompressor operating description and drawings 12 Technological diagram 19 6 Start up 22 6 1 Start up preparation 22 6 2 Restart after longer downtime 23 7 Maintenance 23 7 1 General requirements 23 7 2...

Страница 4: ...ce and maintenance of the compressor and control system Technical documentation of the electrical part It includes the data necessary to perform correct connections and repairs of the electrical equip...

Страница 5: ...tten form The compressor must not be used for any other purposes that are non compliant with its intended use Fulfil the obligation to register the compressor air receiver in the Office of Technical I...

Страница 6: ...The machine is used in a way non compliant with its intended use Unauthorised modifications are carried out on the product Interventions are carried out by unauthorised persons Any repair attempts ar...

Страница 7: ...ock air flow to and from the room Ensure sufficient inflow of cooling air and discharge of hot air outside the room Temperature in a room with the compressor should be within the range of 5 C to 40 C...

Страница 8: ...lve Do not remove the temperature sensor transmitter or pressure transmitter 2 3 Other hazards The compressor installation switching on off and maintenance must be carried out by the qualified personn...

Страница 9: ...nal fan motor power kW 11 Cooling air requirement m3 h 19500 Power lead cross sectional area mm2 3x150 PE Protection A 315 Capacity measured acc to EN ISO 1217 2006 and EN ISO 5167 2 Noise level acc t...

Страница 10: ...entilation is insufficient windows openings in a wall etc in the compressor room air exchange should be provided by fans To ensure correct heat extraction the fans should have total capacity about 15...

Страница 11: ...ised personnel or qualified electrician is allowed to perform electrical connections Use the required safety measures in accordance with the suitable regulations Calculate the power cable cross sectio...

Страница 12: ...eck valve 38 Main motor 11 Unloading valve 39 Fan motor 12 Silencer 40 Fan 13 Oil sight glass 41 Shock absorber 14 Oil tank 42 Oil drain 15 Oil pump 43 Oil inlet 16 Thermostatic valve 44 Coupling 17 S...

Страница 13: ...13...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...il temperature directs the oil directly through the oil filter 19 to the overflow valve 20 and manifold 21 or at temperature exceeding 55 C to the oil cooler 18 and then through oil filter 19 to the m...

Страница 19: ...25 Solenoid valve 8 Venturi nozzle 26 Air filter pollution sensor 9 Second stage cooler 27 Temperature sensor 10 Check valve 28 Safety valve 11 Unloading valve 29 Pressure sensor 12 Silencer 30 Tempe...

Страница 20: ...figure it is marked with a symbol 22 COMPRESSOR COOLING The compressor is cooled in a forced manner by means of a fan with its own electric drive The air is sucked in through the inlets on the front...

Страница 21: ...21 Screw air end CD14D1 Suction regulator Operating panel Controller instruction is an integral part of the OMM of compressor KOMPBERG ZXF132...

Страница 22: ...eration min 2500l When the compressed air receiver tank is located outside the compressor room install the pressure gauge connected to the tank or pressure conduit supplying the tank in a visible loca...

Страница 23: ...procedures The following general requirements must be met while performing the maintenance Place the warning sign as shown below in a visible location while the maintenance work is in progress WARNING...

Страница 24: ...m failure to observe the present safety rules or from carelessness during operation work and maintenance even in circumstances not expressly mentioned in this Operating and Maintenance Manual In order...

Страница 25: ...mponents requiring maintenance Maintenance operations 7 3 1 Air filter cartridge The filter cartridge can t be soaked in oil or other liquids Change the filter cartridge every 2000 work hours or once...

Страница 26: ...ould be completely replaced Carefully placed the filter mat in the housing Filtration mat exchange 7 3 3 Oil filter Change the oil filter every 8000 hours or once a year screwing out screwing in Oil f...

Страница 27: ...e procedure Stop the compressor and wait until the overpressure in the screw assembly body and oil system reaches the atmospheric pressure look at the microprocessor controller Safeguard the compresso...

Страница 28: ...rtridges should be disposed of according to the valid legislation on handling wastes waste code 16 01 07 7 3 7 Oil cooler exchanger interstage final air The safety of the screw compressor requires reg...

Страница 29: ...tely in case of Overheating Smoke or burning smell Excessive vibration Bearing noise The machine can be restarted after removing the cause of any failures Periodic motor inspections The motor inspecti...

Страница 30: ...g this operation Keep away from the stream of air blown out caution the air may be hot In case of the valve leaks contact the manufacturer service to arrange its repair The valve cannot be repaired by...

Страница 31: ...r settings in the controller low setting insufficient compressor install additional source of compressed air capacity in relation to air requirement leak in the system check the tubing for leaks remov...

Страница 32: ...32...

Страница 33: ...mber Quantity 1 Air filter BL 480061 BL 480048 1 2 Compressed air filter cartridge Element for F 24 GW 24 G 1 3 Oil filter B 480001 1 4 Coupling insert BS 482047 1 5 Oil l 480069 40 l 6 Thermostat car...

Отзывы: