15
DESCRIPTION
MYNUTE GREEN 50 R.S.I.
Heating
Nominal heat input in heating mode
kW
47,00
kcal/h
40.420
Nominal heat output (80°/60°)
kW
45,78
kcal/h
39.369
Nominal heat output (50°/30°)
kW
49,91
kcal/h
42.926
Reduced heat input (G20/G31)
kW
9,00/12,00
kcal/h
7.740/10.320
Reduced heat output (80°/60°) (G20/G31)
kW
8,78/11,70
kcal/h
7.554/10.062
Reduced heat output (50°/30°) (G20/G31)
kW
9,72/12,71
kcal/h
8.359/10.929
Nominal Range Rated heat output (Qn)
kW
47,00
kcal/h
40.420
Minimum Range Rated heat output (Qn) (G20/G31)
kW
9,00/12,00
kcal/h
7.740/10.320
Useful efficiency (Pn max - Pn min)
(G20/G31)
%
97,4-97,6 / 96,8-97,5
Efficiency 30% (47° return)
(G20/G31)
%
102,5 / 100,1
Combustion performance via analysis socket
%
97,0
Useful efficiency Pn max - Pn min (50°/30°)
(G20/G31)
%
106,2-108 / 103,2-105,9
Useful efficiency 30% (30° return)
(G20/G31)
%
108 / 106,2
Average Range Rated efficiency Pn (80°/60°)
%
97,6
Average Range Rated efficiency Pn (50°/30°)
%
106,9
Electric power
W
164
Category
II2H3P
Country of destination
-
Power supply voltage
V - Hz
230 - 50
Degree of Protection
IP
X5D
Pressure drops at moment of stopping
W
69
Pressure drops on flue with burner on
%
3
Pressure drops on flue with burner at minimum
%
1,30
Maximum quantity of condensate (50/30°C - CH4)
l/min
5,2
Heating operation
Safety valve calibration pressure
bar
3,5
Maximum operating pressure of heating circuit
bar
4
Minimum pressure for standard operation
bar
< 0,5
Maximum temperature
°C
90
Selection field for H
2
O temperature in heating
°C
20-45/20-80
Pump: maximum capacity available for the system
mbar
500
at an output of
l/h
1.000
Water content in the heating circuit
l
3,2
Gas pressure
Methane gas nominal pressure (G 20)
mbar
20
LPG liquid gas nominal pressure (G 31)
mbar
37
Hydraulic connections
Heating input - output
Ø
3/4”
Water tank delivery - output
Ø
3/4”
Gas input
Ø
3/4”
TECHNICAL DATA