3 | COMMISSIONING AND MAINTENANCE

21

Refrigerant label

In base alla Normativa CE n. 517/2014 su determinati gas florurati ad
effetto serra, è obbligatorio indicare la quantità totale di refrigerante
presente sistema installato. Tale informazione è presente nella targhetta
tecnica presente nell'unità esterna.

A

Standard charge

B

Additional charge

C

Total charge

D

Equivalent total weight of CO2

To write the tag:

- note the quantity onto the label with indelible ink
- place the refrigerant gas label on the outdoor unit

This unit contains fluorinated greenhouse gases covered by the
Kyoto protocol. Maintenance and disposal activities must be carried
out exclusively by skilled personnel.

Global warming potential of the R32 refrigerant gas: GWP=675

If necessary, the refrigerant must be recovered and not dispersed
into the environment.

It is forbidden to disperse the refrigerant into the environment.

3.3

Ordinary maintenance

Routine maintenance is fundamental for keeping the equipment efficient,
safe and reliable. It can be performed periodically by the Technical
Support Service, whose staff is technically qualified and can use genuine
spare parts, if necessary.

For units installed in a seaside environment, the maintenance
intervals shall be halved.

Original conditions must be restored after performing the required
maintenance operations.

All described operations MUST be carried out under the following
conditions:

- cold device
- device NOT supplied with electric power
- suitable personal protection equipment

Do not open the access covers and carry out technical or cleaning
activities before disconnecting the unit from the power grid by
positioning the system's main switch in the "OFF" position.

- position the system's main switch in the "OFF" position.

Wait 10 minutes before touching the device electric components.

Check with a tester that the voltage between the power supply
connectors of the main electronic board is lower than 10 Vdc.

Yearly operations

The annual maintenance plan includes the following checks:

- power supply voltage
- electric connection tightening
- status of cooling and hydraulic joint
- finned coil cleaning
- electric absorption
- fan grille cleaning

Cleaning the heat exchanger fins

The thermal exchange bank must be cleaned with compressed air.
Cleaning must be carried out at least once a year, according to the
location of the unit, as dirt accumulating between the fins narrows the
passage section and reduces the exchange capability.

- check the alignment of the bank's aluminium fins and, if

necessary, straighten them with the appropriate comb

- check that the condensate discharge pipe is clean

Do not use any means to accelerate the defrosting.

Do not use systems different from the ones indicated in this manual.

Emptying of the evaporator

This operation may be necessary to perform reparations on the low
pressure side (evaporator), the device reallocation or the replacement of
the indoor unit without losing the whole refrigerant charge.
Proceed as follows:

- remove the covering plug from the shut-off valve
- check that the three-way shut-off valve is fully open
- let the device operate in cooling mode for 10 - 15 minutes
- stop the device for about 3 minutes
- connect the charging tube of the pressure gauge unit to the

three-way valve service connection on gas side

- vent the air from the charging tube
- close the two-way shut-off valve on liquid side
- operate the equipment in cooling mode until pressure gauge

reads a suction pressure of approx. -1 MPa

- close the three-way shut-off valve on gas side
- stop the unit
- disconnect the pressure gauge unit
- refit the valve covering plug

Carefully check for absence of leakages from the closing point of the
plug.

3.4

Segnalazione di funzionamento e allarmi

Signals are displayed by means of LEDs on the unit main electronic
board.
Proceed as follows to access the filters:

Содержание 20171586

Страница 1: ...Installer manual BREVA EX EN...

Страница 2: ...he device s correct and easy installation Thank you again and keep up the good work BERETTA S p A COMPLIANCE BREVA EX heat pumps are compliant with the following European Directives Low Voltage Direct...

Страница 3: ...to service 3 3 Ordinary maintenance 3 4 Segnalazione di funzionamento e allarmi 4 DISPOSAL The following symbols are used on the product The R32 refrigerant gas is slightly inflammable and odourless A...

Страница 4: ...rigerant gas operate carefully so as to avoid damaging the gas circuit and the fin bank Do not place any inflammable object spray cans within a 1 metre radius from the air expulsion According to EU Re...

Страница 5: ...ectronic board that is triggered when the heat exchanger is clogged by frost formations suction temperature sensor which transmits the detected value to the electronic board that is triggered in order...

Страница 6: ...Wh annum 269 Heating performance 3 Capacity at rated air flow kW 5 20 Capacity at minimum air flow kW 1 60 Capacity at maximum air flow kW 6 10 Absorbed power at rated air flow kW 1 40 Absorbed power...

Страница 7: ...x current input A 12 50 Minimum current consumption A 2 50 Electrical characteristics Power supply V Ph Hz 220 240 1 50 Compressor Compressor Tipo Rotativo Doppio Oil Tipo RM LP56EG Oil charge l 0 48...

Страница 8: ...7 3 5 A 6 5 A Heating Combinations Single nominal capacity Total nominal capacity Total power input Total current input COP Energy class SCOP Energy class Indoor units Indoor units A B Unit A Unit B M...

Страница 9: ...nd delivers it to the room air thereby heating it During the summertime the cycle is reversed and the thermal energy is extracted from the room air which is cooled and is delivered to the outdoor air...

Страница 10: ...ocument envelope Instruction s book for the installer and for the Technical Service in Italian Instruction s book for the installer and for the Technical Service in English Warranty Spare parts labels...

Страница 11: ...cking material must not be disposed of in the surrounding environment and must be kept out of children reach as it can be dangerous It must be disposed of according to the regulations in force 2 6 Pla...

Страница 12: ...ent the air flow from being blocked or install a roofing to protect it Adequate anti freeze systems should be used for installations in extremely cold areas where there is a possibility of freezing Wh...

Страница 13: ...ing table Model 18000 2 Connection pipes h1 m 7 50 h2 m 7 50 h max m 15 H m 15 H m 15 L1 L2 m 20 L1 L2 m 30 Maximum length with standard charge m 20 Additional charge g m 20 The R32 refrigerant gas is...

Страница 14: ...8 60 Pipe A mm inches mm 6 35 1 4 17 9 52 3 8 22 12 7 1 2 26 15 88 5 8 29 bring line ends with flare connection close to their coupling on the unit manually rotate the flare nuts by 3 4 turns tighten...

Страница 15: ...lug 5 Hex wrench If required remove the valve covering plug operate on the valve shaft with an hex wrench open or close according to what is needed immediately stop as soon as the valve shaft has reac...

Страница 16: ...let the vacuum pump work for at least 15 minutes reach a pressure that is close to 0 1 Mpa close the low pressure valve of the pressure gauge unit switch off the vacuum pump wait 5 minutes check that...

Страница 17: ...se the same vacuum pump with different refrigerants The vacuum pump requires regular maintenance and the oil s clarity must also be checked After having created the vacuum and established the electric...

Страница 18: ...must be powered with a separate electric circuit 1 Electric connection input position the system s main switch in the OFF position Wait 10 minutes before touching the device electric components Check...

Страница 19: ...esponds to the nominal value 10 with a maximum phase imbalance of 3 all of the power network disconnect devices must be equipped with contact openings 3 mm in order to allow for complete disconnection...

Страница 20: ...nded operating conditions the unit is able to stop and start up again Should any of the above listed controls have problems turn the device off and call the Technical Service immediately Do not touch...

Страница 21: ...ck with a tester that the voltage between the power supply connectors of the main electronic board is lower than 10 Vdc Yearly operations The annual maintenance plan includes the following checks powe...

Страница 22: ...ion booklet for the installer Tabella allarmi Faults are signalled by means of LED 1 blinking Led 1 Description 1 External unit microprocessor fault 2 Power module fault IPM 3 Main electronic board pr...

Страница 23: ...shall be disposed of separately so as to recover and recycle them Refrigerant and oil must be recovered and not dispersed into the environment At the end of its service life the device shall be dispo...

Страница 24: ...1 277111 Fax 39 0341 277263 info berettaboilers com www berettaclima it As the manufacturer is constantly improving its products the aesthetic or dimensional features the technical data the equipment...

Отзывы: