22
EXCLUSIVE
When the checks are completed:
- set the boiler to
HOT WATER ONLY
or
HEATING AND HOT WATER
mode depending on the season
- regulate the heat request temperature values according to the customer’s
needs.
IMPORTANT
The combustion analysis function is active for a time limit of 15 minutes;
the burner shuts down if an outlet temperature of 95° C is reached. It will
ignite again when the temperature falls below 75° C.
b
In case of a low temperature system we recommend carrying out the
efficiency test by taking hot water setting the boiler STATE to HOT
WATER ONLY
, opening the hot water tap to full capacity and setting
the temperature of the domestic hot water to the maximum
.
b
All controls must be carried out exclusively by the Technical
Assistance Centre
.
5.14 Range rated
This boiler can be adapted to the system thermal requirements as it is
possible to set the maximum flow rate for the boiler operation in heating
mode:
- power on the boiler
-
access the parameters as explained in paragraph “4.1 Access to the
-
select RANGE RATED and confirm it
PARAMETERS
RANGE RATED
THERMOREGULATION
TECHNICAL
INSTALLER
CALIBRATION
INSTALLATION
RANGE RATED
WEATHER COMPENSATION
PARAMETERS
CALIBRATION
TECHNICAL
INSTALLER
INSTALLATION
-
set the desired heating maximum value (rpm)
with the
“up”
and
“down”
keys, confirming the selection
RANGE RATED
5100
RPM
RANGE RATED
-
once the desired power is set (maximum heating)
note the value onto the
supplied self-adhesive label. For further checks and adjustments refer to
the set value.
b
The calibration does not cause the boiler ignition.
The boiler is supplied with the settings indicated in the multigas table.
It is nevertheless possible, according to the system requirements or the
regional regulations on the combustion gas emission limits, to set that value
by referring to the graphs below.
800
1200
1600
2000
2400
2800
3200
3600
4000
4400
4800
5200
5600
6000
6400
6800
7200
7600
8000
8400
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
G
ir
i v
en
ti
la
to
re
(r
.p
.m
.)
Portata termica (kW)
Curva portata termica - giri ven
ti
latore
Caldaia 24C PLUS
HTG curve (Qnheating)
Fan rotations (rpm)
Heat output (kW)
EXCLUSIVE 25C
800
1200
1600
2000
2400
2800
3200
3600
4000
4400
4800
5200
5600
6000
6400
6800
7200
7600
8000
8400
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
G
ir
i v
en
ti
la
to
re
(r
.p
.m
.)
Portata termica (kW)
Curva portata termica - giri ven
ti
latore
Caldaia 28C PLUS
Fan rotations (rpm)
Heat output (kW)
HTG curve (Qnheating)
EXCLUSIVE 30C
1200
1600
2000
2400
2800
3200
3600
4000
4400
4800
5200
5600
6000
6400
6800
7200
7600
8000
8400
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
HTG curve (Qnheating)
Fan rotations (rpm)
Heat output (kW)
EXCLUSIVE 35C
1200
1600
2000
2400
2800
3200
3600
4000
4400
4800
5200
5600
6000
6400
6800
7200
7600
8000
8400
8800
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
G
ir
i v
en
ti
la
to
re
(r
.p
.m
.)
Portata termica (kW)
Curva portata termica - giri ven
ti
latore
Caldaia Exclusive 42C
Fan rotations (rpm)
HTG curve (Qnheating)
EXCLUSIVE 42C
Heat output (kW)
5.15 Lights and faults
If any faults should occur, a screen will appear on the display indicating
the relative error code and a brief alphanumeric description of the same.
Pressing the
“back”
button it is possible to return to the main screen,
where a fault is signalled by this flashing icon
.
18/05/2013
12:17
MENU
INFO
SET
42
°C
1.3 bar
FRI
PLANT
HOT WATER TEMPERATURE
STATE
MENU
STATE
SET
INFO
PLANT
HOT WATER TEMPERATURE
FRI
The user can return to the fault description screen by using the
“up”
and
“down”
keys and then pressing the
“ok”
key.
The faults description screen is automatically displayed once the display
illumination time has elapsed without any button being pressed.
Press the
“up”
and
“down”
keys to display the descriptions of any other
faults that may be present.