Chapter 3
Configuration
Page 15
Step 3
Select ‘Actual’ and enter the correct current value and then select ‘Save’.
Settings
Go to Main Menu > Setup > Input(s) > ‘
Choose Current Input’
> Settings
Gauge Min
This is the minimum scale for Gauge View.
Gauge Max
This is the maximum scale for Gauge View.
Configuring Loadshed relay operation.
All three ‘Current’ status pages have the ability to drive the Loadshed relay output on the back of
the meter.
This is provided so the operator can automatically drop a
NON-ESSENTIAL
section of their AC
loads. Preventing a current rise to a level that will overload the ships generators and cause the
Circuit Breaker to trip and lose power to all AC consumers.
Wire the Loadshed relay as per the ‘Wiring Diagram’ at the front of the booklet, please note that a
snubber diode is required to be fitted across the relay coil for inductive loads.
Each ‘Current’ status page can be set at a different level but please note the output will be active
from the first ‘Loadshed’ becoming active until the last one clears.
To
set the ‘Loadshed’ value, navigate to,
‘Main Menu’ > ‘Setup’ > ‘Input’ “required current status page” > ‘Settings’ > ‘Max Current’.
A default value of 40A is preset. Select ‘Max Current’ then enter then required value.