Chapter 3 

Configuration

 

Page 15 

 

Step 3 

Select ‘Actual’ and enter the correct current value and then select ‘Save’. 

Settings

 

Go to Main Menu > Setup > Input(s) > ‘

Choose Current Input’ 

> Settings 

 

Gauge Min 

This is the minimum scale for Gauge View. 

 

Gauge Max 

This is the maximum scale for Gauge View. 

 

 

Configuring Loadshed relay operation.

 

 

All three ‘Current’ status pages have the ability to drive the Loadshed relay output on the back of 
the meter. 

 

This  is  provided  so  the  operator  can  automatically  drop  a 

NON-ESSENTIAL 

section  of  their  AC 

loads.  Preventing  a  current  rise  to  a  level  that  will  overload  the  ships  generators  and  cause  the 
Circuit Breaker to trip and lose power to all AC consumers. 

 

Wire the Loadshed relay as per the ‘Wiring Diagram’ at the front of the booklet, please note that a 
snubber diode is required to be fitted across the relay coil for inductive loads. 

 

Each ‘Current’ status page can be set at a different level but please note the output will be active 
from the first ‘Loadshed’ becoming active until the last one clears. 

 

To 

set the ‘Loadshed’ value, navigate to, 

‘Main Menu’ > ‘Setup’ > ‘Input’ “required current status page” > ‘Settings’ > ‘Max Current’. 

A default value of 40A is preset. Select ‘Max Current’ then enter then required value. 

Содержание 600-ACSM

Страница 1: ...Page 1 BEP 600 ACSM AC SYSTEMS MONITOR Installation and Operating Instructions INST 600 ACSM_v2...

Страница 2: ...Page 2 This page has been deliberately left blank...

Страница 3: ...us Page 7 Onscreen Keyboard 8 Saving 9 Lock Unlock the Screen 9 Dimensions 10 2 INSTALLATION 11 Plug Information 11 Wiring Diagram 12 3 CONFIGURATION 13 AC Voltage 13 AC Current 14 Configuring Loadshe...

Страница 4: ...hese instructions pertain to the installation of the 600 ACSM and not to the overall wiring of the vessel If an inverter is installed on the vessel its power leads must be disconnected at the battery...

Страница 5: ...s Load shedding relay output with adjustable set point times Adjustable backlighting backlighting on with key press input for external dimming control Remote alarm output Load shedding relay input Spl...

Страница 6: ...Chapter 1 Basics Page 6 Hardware Layout Screw Cover Screw Cover Escape button Up button Down button Enter button Socket A Socket B USB Socket...

Страница 7: ...tton Brings up Main menu from any of the status pages Enters the desired selection from a menu Enters selected character on a calibration page Status Page A Status Page is the first screen that the me...

Страница 8: ...accept Any existing labels will be overwritten by first character input Tip To quickly move selection box through the keyboard press and hold the Up or Down buttons Step 2 Repeat Step 1 until the requ...

Страница 9: ...ettings file with these changes selecting no will keep the changes however the user settings file will not be overwritten and meter will revert back to last save on power up Note Refer to the Settings...

Страница 10: ...Chapter 1 Basics Page 10 Dimensions 89 19 3 1 2 20 28 13 16 29 43 1 3 16 8 17 5 16 17 6 11 16 99 39 3 15 16 84 7 3 5 16 10 1 3 8 62 32 2 7 16...

Страница 11: ...Chapter 2 Installation Page 11 2 Installation Plug Information...

Страница 12: ...ATIVE BUS BAR REMOTE ALARM OUTPUT LOAD SHEDDING RELAY OUTPUT SNUBBER DIODE BACKLIGHTING CONTROL INPUT AC VSEN 4 VOLTAGE INPUTS 1 2 3 CT 10 3 CURRENT INPUTS 1 2 3 AC1 P V1 N V2 V3 AC2 P N C AC3 P N Wir...

Страница 13: ...ut Calibration Step 1 Insert a ground wire into the pin of the input you are configuring Select Zero on the meter and then select Yes Step 2 Remove ground and then wire the Input AC Positive into the...

Страница 14: ...ou need to alter the calibration follow the steps below Go to Main Menu Setup Input s Choose Current Input Calibration Step 1 Select Zero Ensure there is zero current then select Yes to confirm Step 2...

Страница 15: ...of their AC loads Preventing a current rise to a level that will overload the ships generators and cause the Circuit Breaker to trip and lose power to all AC consumers Wire the Loadshed relay as per...

Страница 16: ...Step 2 Use the soft keyboard to enter new timer value Step 3 When both the timers have been set you are able to Enable Load Shed at the Load shed function Alarms All inputs have the ability to have a...

Страница 17: ...s Icon Colour Description Green Alarms Enabled No Alarm Active Red Alarms Enabled Alarm Active Grey Alarms Disabled Red or Green Alarms Muted Configuring Alarms All inputs have two alarm parameters th...

Страница 18: ...oze This is a non selectable option When alarm is in snooze mode it will show the countdown of remaining snooze time Default Snooze Use this setting to change the default snooze time for selected inpu...

Страница 19: ...rcentage between 0 100 100 being the brightest Backlight Timeout Level The backlighting level for when meter is running in Timeout Mode Set as a percentage between 0 100 100 being the brightest Backli...

Страница 20: ...s at a predetermined hold time see below Hold Time The hold time is the time it takes for the meter to change from one Status Page to the next in Automatic Scroll mode Inputs Choose Main Menu Setup In...

Страница 21: ...splay Type There are 2 Display Types that can be chosen from Not all Display Types are available on all inputs Text Gauge Below is a table showing what Display Types are available for each Input Type...

Страница 22: ...ettings are modified and the save prompt window opens the password will need to be entered To set up a new password select Setup Password and then New Password The password will need to be entered twi...

Страница 23: ...fault filename is user ini so this filename or a custom filename can be chosen Note If there is already a file with the same name on the memory stick please choose another filename Import Settings Sel...

Страница 24: ...pletely Turn the meter supply off and then on again for a reboot Colour Test General colour test for LCD screen Factory Reset At any time the meter can be restored to a factory state This can be very...

Страница 25: ...ght Mode Invert Status Pages Input s System Beep On Key Press Power Down Power Down Timeout Setup Password Simulation Mode Units Utilities InputConfiguration Type Label Status Page Display Type Alarm...

Отзывы: