1. Select
Network
>
System Manager
.
2. Expand the System Manager
Provision
.
3. Change the
Network ID
as required.
You must use an unused ISA100 network ID. Consult with your plant ISA100 wireless network
administrator as needed.
Set Join Key (ISA100)
For security purposes, we recommend you change the Ranger Pro Gateway join key.
To change the join key:
1. Select
Network
>
System Manager
.
2. Expand the System Manager
Provision
.
3. Change the
Join Key
as required.
4.3 Provision Field Devices (ISA100)
The Ranger Pro Gateway does not currently support OTA provisioning. Ranger Pro configuration
software is able to manually provision compatible Ranger Pro ISA100 field devices. Refer to the
Ranger Pro User Guide (125M6113).
Before deploying Ranger Pro ISA100 field devices, we recommend you provision each device to
join your network. Depending on the number of field devices and their current sleep state,
provisioning can take up to several hours.
When you provision the device, you:
l
Set the network ID to match the gateway network ID.
l
Set the network join key to match the gateway network join key.
4.4 Configure Field Devices
Once Ranger Pro field devices have joined the network, they can be configured using the Ranger
Pro Gateway web interface.
You can configure these options:
l
Tag
(up to 16 Characters)
l
Role
(IO (Default), Router and Router IO) (ISA100)
To configure device
Tag
:
l
Select
Network
> relevant device in the device list.
l
Expand the
Device Information
.
l
Change the
Device Tag
as required.
To configure device
Role
(ISA100):
35/46
Ranger Pro ISA100 Wireless Gateway
User Guide
158M1430 Rev. -