Tachometer Maintenance
83871-01
128 I Field Wiring Diagram (Dual Setpoint Tach) (Cont) I
1. Wiring Recommendations:
a. Signal Module to Proximitor, 18 to 22 AWG solid or stranded 3 - wire shielded with insulating
sheath. 1000 feet (305 metres) maximum.
b. Signal Module to Recorder, 18 to 22 AWG solid or stranded 2 - wire shielded with insulating
sheath.
/ 2 \ Shields terminated to Signal Module Common.
A To electrically isolate and protect coaxial connection, use connector protector kit part number
40113-02.
4. To minimize ground loops, a single point earth ground (GND) to system common (COM)
connection is recommended.
5. Proximitor case must be electrically isolated from earth ground. Electrical isolation: 500 Vac (RMS)
minimum. Isolation kit part number 19094-01 may be used to satisfy isolation requirement.
/ 8 \ Maximum cable length between Signal Input Relay Module and Proximitor must not exceed 1000
feet (305 metres).
5 3
Содержание 3300/50
Страница 5: ...Tachometer Operation Blank Page 83870 01 i v...
Страница 7: ...Tachometer Operation 83870 01 Blank Page v i...
Страница 9: ...Tachometer Operation Blank Page 83870 01 v i i i...
Страница 37: ......
Страница 41: ...Tachometer Maintenance Blank Page i v...
Страница 43: ...Tachometer Maintenance Blank Page v i...
Страница 108: ...Tachometer Maintenance 83871 01 34 Appendix SCHEMATICS AND TECHNICAL DRAWINGS 63...
Страница 109: ......
Страница 114: ...A t It gg 0 4 4 0 5 I I I T z r a r t 4 4 4 4 4 4 JL 3 3 0 0 5 0 TACHOMETER PWA AND SCHEMATIC DRAWINGS S H E E T 5 O F 9...
Страница 116: ...4 w t g17 i I 4 4 4 Z V 7 4 t 1I t 3 3 0 0 5 0 TACHOMETER PWA AND SCHEMATIC DRAWINGS S H E E T 7 O F 9...
Страница 120: ...v S i g n a l I n p u t R e l a y M o d u l e E p o x y S c h e m a t i c Page 1 o f 2...